12.6. Changing device conguration (using DIP switches)
Tip!
You will nd an animation on device conguration at www.euchner.com.
DIP switches
The devices can be congured using the DIP switches. The following settings are possible:
Ì Changing system family (AR/AP switching)
Ì Deactivating guard locking monitoring
Ì Activating release monitoring (possible only with active guard locking monitoring)
Position of the switches
Item Description
1 DIP switches
2 Sticker with factory setting
Function of the switches
Detail Switch Function
A 1+2 On: Device is operated as AP system
Off: Device is operated as AR system
B 3+4 On: Guard locking monitoring is deactivated
Off: Guard locking monitoring is active (usually factory setting)
C 5 On: Conguration possible
Off: Conguration inhibited (factory setting)
D 6 On: Release monitoring is activated
Off: Release monitoring is deactivated (usually factory setting)
12.6.1. Changing system family (AR/AP switching)
CAUTION
Malfunction due to incorrect conguration or incorrect connection.
Ì Note that the terminal assignment also changes on changing the conguration (see chapter 12.9.
Terminal assignment and contact description on page 30).
1. Switch off power supply.
2. Set DIP switches 1, 2 and 5 as shown.
For changing from AR => AP For changing from AP => AR
1
ON
2 3 4 5 6 1
ON
2 3 4 5 6
3. Switch on power supply for 5 s.
¨ The change is conrmed by the illumination of the Power LED. All other LEDs are off.
4. Switch off power supply and set DIP switch 5 to OFF.
¨ The next time the device is started, it operates in the operating mode set.
1
2
1
ON
2 3 4 5 6