Operating Instructions

Operating Instructions
Non-Contact Safety Switch CES-I-BP-.-C07-…
20
(Translation of the original operating instructions) 2528734-02-08/19
11.1.2. Typical system times
Please refer to the technical data for the exact values.
Ready delay: After switch-on, the device carries out a self-test. The system is ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time t
on
is the time from the moment when the actuator is in the
operating distance to the moment when the safety outputs switch on.
Risk time according to EN 60947-5-3: If an actuator moves outside the operating distance, the safety outputs (FO1A
and FO1B) are switched off after the risk time at the latest.
Discrepancy time: The safety outputs (FO1A and FO1B) switch with a slight time offset. They have the same signal state
no later than after the discrepancy time.
Test pulses at the safety outputs: The device generates its own test pulses on the safety outputs (FO1A and FO1B). A
downstream control system must tolerate these test pulses.
This can usually be set up in the control systems by parameter assignment. If parameter assignment is not possible for your
control system or if shorter test pulses are required, please contact our support organization.
11.1.3. Dimension drawing for safety switch CES-I-BP-C07-…
13,5
M12x1
22
±0,1
19
8
4,8
6
18
40
26,5
LEDs
Active face
Plug connector
LEDs
NOTICE
Ì Covers are included.
Active face