Operating Instructions

Operating Instructions
Electronic-Key-System EKS2
12
(translation of the original operating instructions) 2546099-01-10/21
12.2. EKS2 status and fault displays
Error
code
ENUM in .NET Error Meaning
State of safe-
ty outputs
Reset
LED indicator
Troubleshooting
green red yellow
Normal operation
- The device starts. Communication not possible. All off
0x00 The device is in operation. Depending on
the selected
operating
mode
Depending on the card status (see “12.1. Smartcard status and fault
displays”)
General errors
0x01 Enum(EKSError) +
Value(EKS Error Code)
Internal error The device has an internal error.
At least two
outputs on
Reset not possible Replace the device.
0x02 Enum(EKSError) +
Value(EKS Error Code)
Conguration error Invalid conguration Reset not possible
1 x
Restart the machine.
Output error
0x10 Enum(EKSError) +
Value(EKS Error Code)
Invalid output state The output state is invalid (1-to-n):
Ì Several outputs are switched (short circuit).
Ì Wrong output is switched.
Ì The output cannot be switched.
At least two
outputs on
Select operating
mode again or restart
via .NET library
2 x
Internal error or connection
error. Check connections.
0x11 Enum(EKSError) +
Value(EKS Error Code)
Voltage is too high or
too low.
Voltage monitoring at the outputs reports an
error:
Ì The output voltage is too high.
Ì The output voltage is too low.
Select operating
mode again or restart
via .NET library
2 x
Check connections.
Environment error
0x20 Enum(EKSError) +
Value(EKS Error Code)
Supply voltage too
high
All off
Select operating
mode again or restart
via .NET library
3 x
Check connections and power
supply.
0x21 Enum(EKSError) +
Value(EKS Error Code)
Supply voltage too low
0x22 Enum(EKSError) +
Value(EKS Error Code)
Temperature too high Check ambient conditions.
0x23 Enum(EKSError) +
Value(EKS Error Code)
Temperature too low At least two
outputs on
Communication error
0x30 - Communication
timeout
The polling time of 1 s was exceeded.
.NET library does not send an error code. Error
appears only in the transfer protocol.
Irrelevant Reset possible
6 x
No or invalid card inserted.
Check connections.
6 x
Card is valid. Check connec-
tions.
- ? Faulty communication Only in .NET library: incorrect USB connection or
faulty cable.
Irrelevant Check connections.
Plausibility error
0x40 InvalidSelectedMO
InvalidConrmedMO
Invalid selection of
operating mode
Invalid selection of operating mode:
Ì The selected operating mode does not match
the authorization.
Ì The conrmed operating mode does not match
the selected operating mode.
Irrelevant Reset possible See “Normal operation”