AS-i Safety Output Relay with four standard inputs User Manual ...
Subject to modifications without notice. Generally, this manual refers to products without mentioning existing patents, utility models, or trademarks. The absence of any such references does not indicate that a product is patent-free. © Euchner GmbH + Co. KG Kohlhammerstr.
AS-i Safety Output Relay with four standard inputs Table of Contents Table of Contents AS-i Safety Output Relay with four standard inputs 1 1.1 2 Symbol Catalog .................................................................................... 7 Abbreviations ................................................................................................... 7 General Remarks .................................................................................. 8 2.1 Product information..................
AS-i Safety Output Relay with four standard inputs Table of Contents 7 Safety Requirements ......................................................................... 18 8 Installation Instructions..................................................................... 19 8.1 SOM-4E-0A-C1 ................................................................................................ 19 8.2 Dimensions .....................................................................................................
AS-i Safety Output Relay with four standard inputs Declaration of Conformity Declaration of Conformity Subject to reasonable modifications due to technical advances Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Id.-No.: 103573 Issue date - 28.5.2009 EUCHNER GmbH + Co. KG Tel. +49/711/75 97-0 • Fax.
AS-i Safety Output Relay with four standard inputs Declaration of Conformity 6 Subject to reasonable modifications due to technical advances Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Id.-No.: 103573 Issue date - 28.5.2009 EUCHNER GmbH + Co. KG Tel. +49/711/75 97-0 • Fax.
AS-i Safety Output Relay with four standard inputs Symbol Catalog 1. Symbol Catalog Information! This symbol indicates important information. Attention! This symbol warns of a potential failure. Non-compliance may lead to interruptions of the device, the connected peripheral systems, or plant, potentially leading to total malfunctioning. Warning! This symbol warns of an imminent danger. Non-compliance may lead to personal injuries that could be fatal or result in material damages and destruction. 1.
AS-i Safety Output Relay with four standard inputs General Remarks 2. General Remarks Please read this chapter carefully before working with the documentation and the "AS-i Safety Output Relay with four standard inputs". 2.1 Product information This user manual is valid for the following EUCHNER GmbH + Co. KG devices: AS-i Safety Output Relay with four standard inputs 2.
AS-i Safety Output Relay with four standard inputs Safety 3. Safety This chapter contains user safety information. Warning! Please read this chapter carefully before using the AS-i Safety Output Relay in combination with other machine safeguarding components on protected machinery. 3.1 Experienced staff The AS-i Safety Output Relay must only be installed, operated, and maintained by qualified staff. Qualified is a person who 3.
AS-i Safety Output Relay with four standard inputs Safety 3.4 Disposal Information! Electronic waste is hazardous waste. Please comply with all local ordinances when disposing this product! The device does not contain batteries that need to be removed before disposing it. 10 Subject to reasonable modifications due to technical advances Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Id.-No.: 103573 Issue date - 28.5.2009 EUCHNER GmbH + Co. KG Tel. +49/711/75 97-0 • Fax.
AS-i Safety Output Relay with four standard inputs Product Description 4. Product Description This chapter is intended to inform the reader about the special characteristics of the AS-i Safety Output Relay with four standard inputs. It describes the design and the functionality of the devices. Warning! This chapter must be read before installation and operation of the device in conjunction with other safety components on protected machinery. 4.
AS-i Safety Output Relay with four standard inputs Product Description 4.2 Technical Data Inputs 3 standard inputs + 1 EDM Outputs 1 relay 3 A, 24 V, DC-13 or 3 A, 230 V, AC-15 respectively AS-i profile S.7.A.E ID1 Code 5hex (default), user changeable External device monitoring (EDM) Supplied from AS-i, about 24 V, about 10 mA Displays 3 LEDs yellow (I 1, I 2, I 3) Status input I1, I2, I3 1 LED yellow (1.Y1) Status EDM input 1.
AS-i Safety Output Relay with four standard inputs Product Description 4.
AS-i Safety Output Relay with four standard inputs Product Description 4.4 Electronic connection Terminal settings Description I1, I2, I3 Inputs I1, I2 and I3 1.13, 1.14 Output connection set 1 1.23, 1.24 Output connection set 2 I-, I+ Supply voltage for inputs 1.Y1 EDM (External Device Monitoring) AS-i+, AS-i– Connection to AS-i bus I– I1 I+ I2 RUN I+ I3 I+ 1.Y1 PRG L 1.13 1.14 ADDR L1 L2 L3 1.Y1 K1 1.13 1.14 1.23 1.
AS-i Safety Output Relay with four standard inputs Product Description 4.5 Operating interface I– I1 I+ I2 RUN I+ I3 I+ 1.Y1 PRG I 1 I 2 I 3 1.Y1 Switch to select the operational mode: FAULT ALARM PWR PRG Safety relevant AS-i address can be programmed OUT Secure operation not possible. ADDR RUN Secure operation possible, non-safety relevant AS-i address can be programmed. Addressing jack (ADDR) 1.13 1.14 1.23 1.24 ASI + ASI – NC NC 4.
AS-i Safety Output Relay with four standard inputs Maintenance 5. Maintenance 5.1 Controlling safe shutdowns The plant safety engineer is responsible for verifying that the AS-i Safety Output Relay with four standard inputs works correctly as part of the safety system.
AS-i Safety Output Relay with four standard inputs Address Assignment 6. Address Assignment The device offers two different types of AS-i addresses: The safety relevant (single) AS-i address is the target address for the device through which it receives the signal for the safe release of the output. This address is not used for communication; the device only uses it to listen to ongoing communications. This address can only be programmed if the switch is set to PRG.
AS-i Safety Output Relay with four standard inputs Safety Requirements 7. 18 Safety Requirements • The device uses two redundant, force-guided relays. • The module recognizes if one of the relays does not switch (for instance if the contacts are welded). • The contact sets 1.13/1.23 and 1.14/1.24 use the same relay; they do not operate independently. • The contacts 1.13, 1.23, 1.14, 1.24 are potential-free. A cross-short check is not available.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8. Installation Instructions 8.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8.3 I– I1 RUN Front view and connections I+ I2 I+ I3 I+ 1.Y1 PRG I 1 I 2 I 3 1.Y1 FAULT PWR ALARM OUT ADDR 1.13 1.14 1.23 1.24 ASI + ASI – NC NC PRG sicherheitsrelevante AS-i-Adresse kann programmiert werden. Kein Schutzbetrieb möglich // Programming of safety relevant AS-i address enabled. Protective mode disabled // mode de protection non possibile.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8.3.1 Connecting a safety contactor I– I1 RUN I+ I2 I+ I3 I+ 1.Y1 PRG L 1.13 1.14 ADDR L1 L2 L3 1.Y1 K1 1.13 1.14 1.23 1.
AS-i Safety Output Relay with four standard inputs Installation Instructions Programming the safety relevant AS-i address (PRG) 1.13 1.14 ASI+ ASI– 1.23 nc + 1.24 nc Safety Address I– I1 I+ I2 I+ 1.Y1 I+ 1.Y2 AB Slave AS-i safety output with 4 standard inputs = I– I1 I+ I2 Run I+ 1.Y1 I+ 1.Y2 Prg I1 I2 1.Y 1.Y1 2 4 standard (1 EDM) inputs Pw r 1 safety relay output relay inputs Fa u Ou lt t Ala rm 8.4 Prg 1.13 1.14 ASI+ ASI– 1.23 nc 1.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8.4.1 Address assignment LCD 1.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8.4.2 Checking safety relevant address 15 LCD 1. ↓ OK CONFIGURATION OK ACTUAL CONFIG 10 – | 11 – 12 – | 13 – 14 | 15 – X OK ↓ OK QUICK SETUP AS-I SAFETY DIAGNOSIS SLAVE ADDR TOOL 14 - ...- 15 A - 7F15 OK OK FLAGS ACTUAL CONFIG LPF ASI MASTER AS-i Adresse 1 5 OK! 7 F 1 5 IO ID ID1 ID2 ESC OK ↓ I– I1 I+ I2 AS-I CIRCUIT 1 AS-I CIRCUIT 2 I+ 1.Y1 I+ 1.
AS-i Safety Output Relay with four standard inputs Installation Instructions Programming of the non-safety relevant AS-i address (RUN) 1.13 1.14 ASI+ ASI– 1.23 nc + 1.24 nc Safety address 4 standard (1 EDM) inputs I– I1 I+ I2 I+ 1.Y1 AS-i safety output with 4 standard inputs = I+ 1.Y2 AB Slave I– I1 I+ I2 Run I+ 1.Y1 I+ 1.Y2 Prg I1 I2 1.Y 1.Y1 2 1 safety relay output relay inputs Pw r Fa u Ou lt t Ala rm 8.5 Prg 1.13 1.14 ASI+ ASI– 1.23 nc 1.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8.5.1 Address assignment LCD 1.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8.5.
AS-i Safety Output Relay with four standard inputs Installation Instructions 8.6 Montage Operating temperature: 0 °C … +55 °C Temperature rating for cable: 60/75 oC Use copper conductors only 1 x 0.5 - 1.5 mm² (16AWG: min. 24/max.12) 5 ... 6 mm / PZ2 0,8 Nm 7 LB.IN 10 2 2 x (0,5 .... 1,5) mm 10 2 2 x (0,5 .... 1,5) mm AWG 2 x 24 ...