2 Mounting instructions 
2.1 Delivery 
The PHÖNIX type 740.0060/65 level switch can be delivered in the configurations shown below: 
Fig. 3a: as delivered
Fig. 3b: with inverted switching di-
rection
2.2  Reversing the direction of switching 
A reversal of the direction of switching involves the opposite switching function. Please note that the ca-
ble-gland is always directed downwards, as shown in fig. 3a and 3b. 
Instruction: 
•  Remove the switch cover 
• 
Remove the safety access panel (type 740.0060 only) 
•  If necessary remove all connecting wires from the terminal 
• 
Take off screw, hexagon bolt and - for aluminium housing - the earth terminal 
•  After turning the circuit board 180° remount with screws , hexagon bolt and.- for aluminium housing- 
the earth terminal. 
•  Reconnect the wires into the terminal 
• 
Put on the safety access panel (type 740.0060 only, very important !!) 
OFF 
OFF 
ON 
ON 