SC 600 PLUS INDEX INTRODUCTION Page 22 Page 22 Page 22 Page 22 1.1 1.2 1.3 1.4 CHAP. 1 General features Product identification code Dimensions Identification data INSTALLATION Page 23 Page 23 Page 23 Page 24 2.1 2.2 2.3 2.4 CHAP. 2 Important general information for the installer Kit for mounting Installing the Master control board Installing the Plus SC 600 console FUNCTIONALITY Page 25 3.1 CHAP. 3 Functions controlled by the PLUS SC 600 TECHNICAL SPECIFICATIONS Page 26 Page 26 4.1 4.
C H A P. 1 - I n t r o d u c t i o n SC 600 PLUS CHAPTER 1: INTRODUCTION G E N E R A L F E AT U R E S 1.1 The SC600 PLUS system allows users to control the machine room of a refrigeration plant in which there is more than one compressor. It guarantees uniform operation and proper distribution of operating times among individual machines.
C H A P. 2 - I n s t a l l a t i o n SC 600 PLUS CHAPTER 2: INSTALLATION IMPORTANT GENERAL INFORMATION FOR THE USER 2.1 1. Install the device in places where the protection rating is observed and try not to damage the box when drilling holes for wire/pipe seats. 2. Do not use multi-polar cables in which there are wires connected to inductive/power loads or signalling wires (e.g. probes and digital inputs). 3.
C H A P. 2 - I n s t a l l a t i o n SC 600 PLUS Fig. 2 : Main MASTER control board components 2.4 INSTALLING THE PLUS SC 600 CONSOLE Fig. 3 parts. SCHEDA MASTER PHONE CABLE : Main PLUS SC 600 control console : Example of PLUS SC 600 installation. Fig. 4 PLUS SC 600 Pag. 24 MAINTENANCE AND USE MANUAL Rev.
C H A P. 3 - F u n c t i o n a l i t y SC 600 PLUS Effect all electrical connections as illustrated in the diagram for the corresponding model (see relative table in APPENDICES). To effect correct electrical connection and maintain the protection rating, use lead grippers and/or duct grippers to ensure a good seal. Route the wiring inside the unit in as tidy a fashion as possible: be especially careful to keep power wires away from signal wires. Use clips to hold wires in place.
SC 600 PLUS C H A P. 4 - Te c h n i c a l c h a r a c t e r i s t i c s CHAPTER 4: TECHNICAL CHARACTERISTICS 4.1 TECHNICAL CHARACTERISTICS POWER SUPPLY Voltage Max power 230 V~ ± 10% 50Hz ~ 8 VA AMBIENT CONDITIONS Operating temperature Storage temperature Relative ambient humidity -10 ÷ 60°C -30 ÷ 70°C Below 90% GENERAL CHARACTERISTICS Pressure sensor type Measuring range 4...20 mA -0,5...30 bar OUTPUT CHARACTERISTICS Outputs on relay n° 10 Outputs on relay N.A.
C A P. 5 - P a r a m e t e r s p r o g r a m m i n g SC 600 PLUS CHAPTER 5: PARAMETER PROGRAMMING PLUS SC 600 CONTROL PANEL 5.1 The Control Console is used to program and display the parameters. The Console can be installed directly in the machine room (e.g. power cabinet front) or in any other position where visual control of plant operation might be useful. The Control Console features CONTROL KEYS, INFO/WARNING ICONS and a DISPLAY which is used to program and view all the main parameters.
C A P. 5 - P a r a m e t e r s p r o g r a m m i n g SC 600 PLUS LCD DISPLAY 5.2 1 3 2 5 4 7 6 9 8 11 10 13 12 15 14 17 16 19 18 20 22 21 23 33 24 25 26 27 28 29 30 31 1. status of digital output 1 status of digital output 1 3. status of digital output 2 4. status of digital output 2 5. status of digital output 3 6. status of digital output 3 7. status of digital output 4 32 (compress. 1) on = active, off = not active (compress.
C A P. 5 - P a r a m e t e r s p r o g r a m m i n g SC 600 PLUS 20. state (alarm) on = tripped alarm not muted but stopped on its own 21. displays pressure read by the intake sensor (low pressure) 22. displays pressure read by the delivery sensor (high pressure) 23. shows date and time 24. indicates compressor call (general) 25. [SPARE] 26. [SPARE] 27. [SPARE] 28. [SPARE] 29. indicates fan call (general) 30. [SPARE] 31. indicates alarm (general) 32. indicates system stand-by 33.
SC 600 PLUS C A P. 5 - P a r a m e t e r s p r o g r a m m i n g OUTPUTS: (normally open non-powered contacts) - Compressor 1 - Compressor 2 - Compressor 3 - Compressor 4 or separation compressor 1 - Separation compressor 2 - Separation compressor 3 or fan 1 - Condenser fan 1 or 2 - Condenser fan 2 or 3 - Condenser fan 3 or 4 - Alarm GENERAL FEATURES 5.4 For safety reasons and to simplify the operator’s work, the PLUS SC 600 has two programming levels; the first level is used to modify SET parameters (i.
C A P. 5 - P a r a m e t e r s p r o g r a m m i n g SC 600 PLUS PROGRAMMING AND DISPLAY OF PRESSURE SETPOINT 5.7 During display of high and low pressure: 1. Push the SET COMPRESSOR key to display the current SETPOINT. 2. Push the SET COMPRESSOR key and press one of the ( ) or ( ) keys to modify the SETPOINT for activing the compressors. 3. Release the SET COMPRESSOR key to return to the high and low pressure display; modifications will be saved automatically.
SC 600 PLUS 5.9 C A P.
C A P.
SC 600 PLUS C A P. 6 - Description of operation CHAPTER 6: DESCRIPTION OF OPERATION 6.1 OPERATION The SC 600 PLUS system manages 4 compressors and 4 fans, or 3 compressors each with a separation and 3 fans, according to the parameter settings made during programming. Fans can be disabled.
C A P. 7 - D i a g n o s t i c s SC 600 PLUS OPERATION “WITH ROTATION” 6.5 Each activation request is followed by a fixed 10-second delay (indicated by the flashing LED of the corresponding compressor) and then activation of the compressor with the shortest working time; subsequently, compressors with working times longer than that of the previous one are switched on.
SC 600 PLUS ALARM CODE C A P. 7 - D i a g n o s t i c s PROBABLE CAUSE SOLUTION E1 Faulty high pressure sensor. E3 EEPROM ALARM An error in the EEPROM memory has been detected (all outputs except alarm output are deactivated). Master/slave software incompatibility error. One or more compressors has reached the number of working hours at which maintenance is required. Clock battery flat. Unit in manual pre-alarm. • Check the sensor is working properly.
C A P. 7 - D i a g n o s t i c s SC 600 PLUS ALARMS DATABASE 7.2 The SC600 PLUS system can save up to 40 alarm events.To display the recorded alarm codes press the ALARM MUTE key for at least 2.5 seconds. Sector n. 22 of the LCD display (see section 5.2) shows the dominant (highest priority) error code at the time of saving. Sector n. 23 indicates the data saving date (if alarm refers to current day the time is shown).
SC 600 PLUS A L L E G AT I / A P P E N D I C E S ALLEGATI / APPENDICES A.1 DICHIARAZIONE DI CONFORMITA’ CE / CE DECLARATION OF CONFORMITY COSTRUTTORE / MANUFACTURER PEGO SRL Via Piacentina,6b - 45030 Occhiobello (RO) - ITALY DENOMINAZ IONE DEL PRODOTTO / NAME OF PRODUCT MOD.
A L L E G AT I / A P P E N D I C E S SC 600 PLUS SCHEMA DI CONNESSIONE SCHEDA MASTER MASTER CARD TERMINAL BLOCK 25 1 26 2 3 27 4 28 5 6 29 7 30 8 9 31 10 32 11 12 33 13 35 34 14 15 16 17 18 36 37 19 38 20 21 39 22 40 23 41 42 43 44 45 A.
SC 600 PLUS A.3 A L L E G AT I / A P P E N D I C E S COLLEGAMENTO TRA CONSOLE PLUS SC 600 E SCHEDA MASTER CONNECTION BETWEEN PLUS SC 600 CONSOLE AND MASTER BOARD SCHEDA DI GESTIONE (MASTER) MASTER BOARD CAVO TELEFONICO PHONE CABLE CONSOLE OPERATIVA (SLAVE) SLAVE BOARD Pag. 40 A.3 Rev.
A L L E G AT I / A P P E N D I C E S SC 600 PLUS NOTE / NOTES .............................................................................................................................................................. .............................................................................................................................................................. .................................................................................................................................
SC 600 PLUS NOTE / NOTES .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. ........
NOTE / NOTES SC 600 PLUS .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. ........
Via Piacentina, 6/b 45030 Occhiobello ROVIGO - Italy Tel. : +39 0425 762906 Fax : +39 0425 762905 E-mail : info@pego.it - www.pego.it PEG O S. R. L.