Owner`s manual

Page 10
DV 42 ST See-through Gas Fireplace
rev.110308
Installation
Vertical Vent Installations
Vertical vent Installations.
minimum 2' (two feet) above the highest point where
vent passes through the roof.
minimum 6' (six feet) from a mechanical air inlet
minimum 18" (1½ feet) from a parapet wall.
Maximum vent height is 32 feet above replace.
Note: Flame characteristics will change if the maximum vent height is used.
Minimum clearance to combustible construction around the vent pipe
is 1" on all sides must be maintained, except on horizontal venting where the
top of the pipe must have a clearance of at least 2".
2. Oset Vertical Installations
A maximum of two osets (each oset has two 90° bends) may be made if
the length of the osets does not exceed 25% of the vertical vent height, when
measured center to center of piping.
Example: Typical vent installation.
32' vertical vent
2 - 2' osets required
25% of 30' = 7½' maximum oset allowed
This venting conguration meets requirements.
1. Straight Vertical Installation
Figure 17. Straight, vertical venting run.
Figure 17b. Vertical venting with 2 osets (1 oset= two 90° bends).
Figure 17a. Vertical venting with 1 oset (1 oset= two 90° bends).
PEXT
Solid Sectio
n
PEXT
Solid
Section