Owner`s manual
Page 11
DV 42 ST See-through Gas Fireplace
rev.110308
Reduced Vertical Installation
(Available with Linear LDVPV47 Power Vent ONLY)
It is possible to reduce vertical vent runs from 5"/8" venting to 4"/7" venting. Reduced
vertical venting may only be used when the Linear (In-line) Power Vent is required.
This is commonly due to longer than normal vent runs, or unusually long horizontal
Vent runs.
Installation
Figure 18. Reducing Vertical Vent from 5/8" to 4/7".
Installing The Horizontal and
Vertical Exterior Power Vent
A Power Vent is required where the Termination is located too far away from
the gas replace and/or if the vent run is beyond the scope of this document, or
the specications recommend vent augmentation. There are four 4/7 Power Vent
models available. These Power Vents are required for Superior venting, safe opera-
tion and years of trouble free operation.
The available European Home Power Vent models are:
LDVPV47 (Linear, Interior In-line Power Vent, document, XG0700).
EDVPV47 (External Power Vent Module, document, XG0750).
EDVRSPV47 (Exterior Vertical Roof mount 4/7 stainless steel Power Vent system,
document, XG1303)
EDVWSPV47 (Exterior Horizontal Wall mount 4/7 stainless steel Power Vent system,
document, XG1302).
Finishing Around the Fireplace
Combustible mantels and mouldings may be safely installed over the top and on the
front of the replace provided that they do not project beyond shaded area shown in
Figure 24. Side wall clearances are 3". Combustible surrounds may be installed with
3" clearance to the side of the replace as shown in Figure 25.
Fireplace Facing
When selecting the nish material for your replace, it is important to remember the
following: THE DOOR OPENING MUST NOT BE OBSTRUCTED IN ANY WAY - to do
so restricts the air supply for the control compartments and heat exchanger
it also prevents access for servicing controls.
The face of the replace may be painted to match the room decor, provided you use
a heat-resistant paint. Decorative facing must not extend past the replace opening
at all, because it will interfere with the access to retainers for removal of glass door.
Horizontal Run (in)
Mantels and Surrounds
NOTE: National Canadian Gas Association mantel test requirements are for re hazard
prevention to combustible materials.
New technology, to meet consumer and government demands for the wise use of
energy, has prompted us to manufacture many models of replaces which are hot,
fuel and energy ecient.
Please be aware; temperatures over the mantel will rise above normal room temperature
and walls above replace may be hot to touch.
Figure 24. Combustible mantles and facings, (Both Sides Typical).
Non-Combustible
Facing Material
Steel Stud construction
allowable within this area
Top of
fireplace
WARNING!
When covering the upper metal portion of the replace, up to 6" (as shown,
Fig.24 and Fig.25) with a non-combustible material Please Note: The
decorative facing materials may be subject to temperatures in excess of 250°
F. This should be considered when selecting facing materials.
We recommend careful consideration be given to the eects of elevated
mantel temperatures which may be in excess of product design, for example:
candles, plastic or pictures. This can cause melting, deformation, discoloration
or premature failure of T.V. and radio components.










