Installation
Frame in the enclosure for the unit with framing materials. The framed opening
for the assembled replace is 45" wide, x 40" high x 23 ¾" deep, see Figure 2
.
NOTE: When constructing the framed opening, please ensure there is access
to install the gas line when the unit is installed. See Figure 22.
Figure 2. Framing dimensions.
Figure 2a. Framing dimensions, back-framing
Figure 3. Combustible Framing for shelves over the replace, Rear vent.
Notes:
Install supplied metal headers (Part No. H42ST060)
above replace after unit is in place.
Use supplied hardware to attach to framing. Both
Walls Typical. May not be exactly as shown.
Framing Kit, 4-pcs. (Part No. L42FS01B) Install
with supplied hardware. Both walls and sides
Typical. See Figure 2a below.
40”
Both walls Typical. May
not be exactly as shown.
Backframe Min. 42”
both sides Typical
Com
b
usti
bl
e materia
l
s may
b
e use
d
,
(left & right), surround & bottom.
Above fireplace see Fig. 24 & 25.
Framing Kit, (Part No. L42FS01B,
4-pcs. Fasten to Combustible
framing with supplied hardware.
12” Min.
Combustible
shelf
Supplied shield
90°
1” Min
1” Min
L.P. & N.G
Clearances
When installing a shelf over the top of the replaces, the following must be observed:
For Rear Vent applications, the minimum clearance is 2" from the rear of the replace
to a wall, or any combustible materials, and 12" clearance from the top of the replace
to the underside of any combustible shelf materials.
For Top Vent applications, the minimum clearance is 2" from the rear of the replace
to a wall, or any combustible materials, and 21" to the underside of any combustible
shelf materials.
(Minimum 2" clearance must still be maintained around the vent pipes.)
Figure 4. Combustible Framing for shelves over the replace, top vent.
Figure 5. Non Combustible Framing with alcove above replace, right side. Combus-
tible framing above replace, left side, see gure 2. (Top Vent).
DV 42 ST 12" 21" 2" 1" 0" 6"
MODEL
Top - Rear Vent *
Top - Top Vent
Back
Sides
Floor
Mantel
41”Min N.G.
54”Min L.P.
21”
Min.
PEL Short
90 elbow
Supplied shield
Combustible Shelf
N.G. & L.P
2” Min.
Non
Combustible
Header
7”
Floor
Alcove over
Fireplace Non
-
Combustible
Materials Only
36”
30 1/2”
door
opening
40”
7”
Combustible
Header
Min. 1”
Supplied
Header
10”
Top vent
N.G. & L.P
Note:
When facing with the
Overlay Method the depth
is increased by 1". See
Planning Guide for more
information.
23¾"
or
24¾"
40"
36"
45"