Installation
The Venting Graph: DV 42*
Measure the vertical height from the replace hearth to the center of the termination
and the horizontal run from the replace ue collar to the wall ange of the termination.
Plot on the Venting Graph Figure 14 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the installation is
acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 108" and the horizontal run to
the wall ange of the vent termination is 180" then the vent conguration is
acceptable.
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 60" and the horizontal run to the wall
ange of the vent termination is 72" then the vent conguration is acceptable.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 60" and the horizontal
run to the wall ange of the vent termination is 144" then the vent conguration
is NOT acceptable.
Figure 14. DV 42* Top Vent Venting Graph for wall mounted terminations.
Figure 15. Top vented, wall mounted installation with 1 elbow ( one 90° bend). The vent
run must comply with Venting Graph for top vent, wall mounted terminations, Figure 14.
Figure 15a. Top vented, wall mounted multi-elbow installation. See Venting Graph for
top vent, wall mounted terminations, Figure 14.
Section 3-3-1: VENTING LAYOUT: wall mounted termination.
Selection of components and details of venting layout must adhere to the
following:
Vent terminations must not be recessed in walls or siding.
All through-the-wall terminations within 3’ of the replace must have a
European Home Heat Shield (RHS101) installed. See Section 3-3-3.
All through-the-wall terminations beyond 3' of the replace must have a
European Home Heat Shield (RHS8) installed. See Section 3-3-3.
Once the proposed venting layout has been determined refer to Figure 14
to ensure the layout is acceptable.
Notes for top vented replaces with wall mounted terminations:
All measurements for vertical or horizontal runs are measured from center
of the vent pipe.
Venting runs must fall within the limits set by the venting graph, see Figure 14.
Wall Mounted Terminations
The following details are some possible congurations for wall mounted terminations.
See below.
Solid Section
Flex Section
Hearth
30”min
15’foot Max.
RHS8 Heat
Shield
Termination
Exterior
Wall
8' MIN AT MAX
Horizontal
WARNING:
An inspection of the explosion relief appers and door
MUST be made prior to lighting the replace. Faulty seal
on the door gasket and/or explosion ports will result in
combustion products leaking into the living space and
may result in carbon monoxide poisoning.
RHS8 Heat
Shield
Termination
Hearth
Exterior
Wall
36" Max.
Flex section
Min.
46"
A
C
B
36
If your installation does not fall
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
46”
36”
Please contact European
Home for installations
which fall outside this
vent graph.