Installation
Figure 17. Rear Vent Venting Graph for wall mounted terminations.
Figure 17b. Rear Vented, wall mounted Multi-elbow termination installation.
Installation for DV 42* must have a minimum vertical rise of 50". The vent run must
comply with the Venting Graph for rear vent, wall mounted terminations, Figure 17.
Figure 17a. Straight run, rear rented, wall mounted termination for DV 42*, Figure 17.
Notes for Wall Mounted Terminations on Rear Vented Fireplaces
All dimension lengths for vertical or horizontal runs are measured from center
of the vent pipe.
Venting runs must fall within the limits set by the venting graphs, see Figure
17.
Fireplace must be converted to rear vent conguration prior to running vent,
see Figure 7 and 8.
The Venting Graph
Measure the vertical height from the replace hearth to the centre of the termination
and the horizontal run from the replace ue collar to the wall ange of the termination.
Plot on the Venting Graph Figure 17 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the installation is
acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal run to the wall
ange of the vent termination is 138" then the vent conguration is acceptable.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal run to the wall
ange of the vent termination is 72" then the vent conguration is acceptable.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 60" and the horizontal run
to the wall ange of the vent termination is 144"then the vent conguration is NOT
acceptable.
26 5/8”
18”
A
B
C
50”
48”
If your installation does not fall
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
36” Max.
50” Min.
12”
Max.
Flex or Rigid
Section
23 3/8”
Min.
26 5/8”
26 5/8”
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
NOTE:
12” MAX. horizontal run with no vertical lift,
N.G. ONLY.
12” MAX.
36” Max.
50” Min.
12”
Max.
Flex or Rigid
Section
23 3/8”
Min.
26 5/8”
26 5/8”
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
NOTE:
12” MAX. horizontal run with no vertical lift,
N.G. ONLY.
12” MAX.
WARNING:
An inspection of the explosion relief appers and door
MUST be made prior to lighting the replace. A faulty seal
on the door gasket and/or explosion ports will result in
products of combustion leaking into the living space and
may result in carbon monoxide poisoning.
Please contact European
Home for installations
which fall outside this
vent graph.