Installation manual

23
VENTING
Element4 Gas Fireplaces EuropeanHome.com
The replaces in this manual are direct vent replaces that use a co-axial or “pipe within a pipe” venting system. The outer “pipe”
or vent conducts fresh, outside air into the replace and the inner vent carries the exhaust outside. This technology, which can run
either horizontally through a side wall or vertically through the roof, produces an ecient system because conditioned building
air is not used for combustion.
NOTE: The replaces described in this manual use 5”/8” venting.
All of the following points apply to every installation:
Only the direct vent components from M&G DuraVent (listed in Table 5) are approved for use with these replaces. The
installation instructions are in Appendix One. Please read, understand and follow these instructions.
Every Element4 replace is shipped with a North American venting adapter. It MUST be the rst piece of venting installed.
All measurements are taken from the center of the vent connector on the top of the replace (see Figure 20) and all
congurations must fall within the acceptable range of the venting charts.
The maximum allowable rise is 36’/11.0 m and the maximum allowable run is 9’10/3.0 m but not in combination; see Figure 21
and Graph 1.
When venting with a horizontal termination, the minimum vent conguration is a 39”/1.0 m vertical rise to a 90° elbow plus a
19”/500 mm horizontal run to a wall termination. When venting with a vertical termination, the minimum vent conguration is
3’3”/1000 mm and the maximum rise is 36’/11.0 m maximum.
When using wall terminations no more than two horizontal 45° or 90° elbows are allowed.
When using vertical terminations no more than four 90° elbows OR eight 45° elbows OR a combination totaling no more
than 360° elbow degrees. For example, a combination of two 90° elbows and two 45° elbows is allowed (90° + 90° + 45°+ 45°
equals 270°) but a combination of three 90° elbows and three 45° elbows is not allowed (the total equals 405°.) These elbows
can be installed either horizontally or vertically.
A minimum clearance of 3”/75 mm must be maintained between combustible materials and the top of any horizontal vent
pipe surface; a minimum clearance of 1”/25 mm must be maintained between combustible materials and any other vent pipe
surface.
There may be no venting component higher than the termination.
Whenever venting passes through a wall, a heat shield, or ‘wall thimble’ from the manufacturer listed in Table 5 must be
installed.
For venting congurations greater than those shown a power vent must be used. Contact your retailer for more details.
CONFIGURING THE VENTING