Installation manual

26
VENTING
Element4 Gas Fireplaces EuropeanHome.com
3’3”
1.0 m
6’6”
2.0 m
Vertical
Rise
HORIZONTAL TERMINATION GRAPH
Graph 1 shows, for all models, the maximum horizontal vent run (to the outside wall) for a given vertical vent rise. The installed
venting conguration MUST be within the dimensions shown within the grayed area.
When using a wall-mounted termination a maximum of 2 horizontally-mounted elbows (45° or 90°) may be used.
- For each 45° elbow, 20”/500 mm must be subtracted from the horizontal length allowance.
- For each 90° elbow, 40”/1000 mm must be subtracted from the horizontal length allowance.
Example A: With a total rise of 6’6/1.5 m and one horizontal 90° elbow, a total run of 3’3”/1.0 m is allowed
Example B: If the rise is 16’4”/5.0 m then the run can be no longer than 8’2”/2.5 m.
Example C: If the run is 4’11”/1.5 m then the rise must be at least 9’10”/3.0 m.
Graph 1. Horizontal Terminations
1’7”
0.5 m
3’3”
1.0 m
4’11”
1.5 m
6’6”
2.0 m
8’2”
2.5 m
9’10”
3.0 m
9’10”
3.0 m
13’1”
4.0 m
16’4”
5.0 m
19’8”
6.0 m
23’
7.0 m
Horizontal
Run