VENTING
Element4 Gas Fireplaces EuropeanHome.com
V2 V3V1
V
H
Distance "H" = 0 - 3m (min - max)
Distance "V1" = 500mm - 10m (min - max)
Distance "V2" = 200mm - 10m (min - max)
Distance "V3" = 500mm - 10m (min - max)
Distance "V" (= V1+V2+V3) = 1.2m - 11m
(min - max)
Distance "V" =2x "H" (min)
Distance “H” = 0”/0.0 m minimum to 9’10”/3.0 m maximum
Distance “V1” = 19”/500 mm minimum to 33’10”/10.0 m maximum
Distance “V2” = 8”/200 mm minimum to 33’10”/10.0 m maximum
Distance “V” (V1+V2+V3) = 3’11”/1.2 m minimum to 36’/11.0 m maximum
Distance “V” must be greater than twice the distance of “H”
Subtract 19”/500 mm of maximum height for every 45° elbow up to a maximum of
eight (8) 45° elbows.
Figure 24. Vertical Terminations with 45° elbows
VERTICAL VENT TERMINATIONS WITH 45° ELBOWS