Direct Vent Gas Fireplace Installation, Operation and Owner’s Manual This manual covers the following appliances for use in North America ONLY: Trisore 95, Trisore 100H, Trisore 140, Bidore 95, Bidore 100H, Bidore 140, Lucius 140, Lucius 140 T, Lucius 140 C 1/3, Lucius 140 C 2/3, Modore 95, Modore 100H, Modore 140, Optica, Bioptica Element4 Gas Fireplaces June 20141 EuropeanHome.
TABLE OF CONTENTS Important Safety Information 3 User Information 7 Specifications and Dimensions 8 Clearances 27 Gas and Electric 33 Venting 34 Enclosing the Fireplace 46 Fire Media 53 Operating the Fireplace 58 Maintenance 61 Warranty 65 Venting System Installation Instructions Appendix One Massachusetts Certification Appendix Two Troubleshooting Flowchart Appendix Three
IMPORTANT SAFETY INFORMATION CAUTION - HOT! HOT! HOT! This appliance is a HEATING appliance and it does become very hot in operation. UNDER ANY CIRCUMSTANCES, DO NOT PLACE any object, furniture, draperies or other item LESS THAN 36”/90 cm) IN FRONT OF THE GLASS OF THE FIREPLACE. HOT SURFACES 36" 36" 90cm 90cm Radiant heat can heat surfaces such as the surround and trims of the fireplace to temperatures that, although approved safe, can be quite uncomfortable to touch particularly for children and pets.
IMPORTANT SAFETY INFORMATION WARNING WARNING: Installation and Service Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition. Installation and Service must be performed by an authorized qualified installer, service agency or gas supplier. Any alteration to the product that causes soot or carbon to form and results in damage is not the responsibility of the manufacturer.
IMPORTANT SAFETY INFORMATION This gas fireplace and vent assembly MUST be vented directly to the outside and MUST NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance MUST BE a separate vent system. Common vent systems are prohibited. TURN OFF the gas before servicing the appliance. It is recommended that a qualified service technician perform an appliance check-up/service once a year.
IMPORTANT SAFETY INFORMATION When enclosing your Element4 fireplace the use of non-combustible building materials is REQUIRED. Please read and understand the following. COMBUSTIBLE MATERIALS Materials that can catch fire and burn are considered combustible. Any material that is made of, or faced with, wood, wood pulp, paper, plastic or any other material that can catch fire and burn is considered combustible.
USER INFORMATION WARMTH AND BEAUTY - HOW IT WORKS The Element4 fireplaces are called direct vent fireplaces and, as such, the intake and exhaust are both handled through the vent pipe. The fireplace also provides convection air to your room. Figure 1 (below) shows one of the unique features of the Element4 fireplaces - its use of convection air flow. Other fireplaces have louvered metal boxes around them to keep temperatures under control.
SPECIFICATIONS and DIMENSIONS APPLIANCE RATINGS Bidore 95 Modore 95 Trisore 95 Bioptica Optica Model Gas Bidore 100H Modore 100H Trisore 100H Bidore 140, Lucius 140, Lucius 140 T, Lucius 140 C 1/3, Lucius 140 C 2/3, Modore 140, Trisore 140 Natural Gas Propane Natural Gas Propane Natural Gas Propane Natural Gas Propane Input Maximum Btu/hr 30,730 26,300 36,200 32,400 34,145 34,145 38,200 34,100 Input Minimum Btu/hr 17,070 8,535 17,050 13,650 15,025 17,075 13,650 11,950 Maxim
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 271/4 692 C 209/16 522 D 211/16 68 E 315/16 100 F 341/16 865 G 391/8 995 H 121/2 318 I 101/2 266 J 391/8 995 K 5/8 15 L 411/16 118 M 8 202 N 121/2 318 O 131/8 333 Element4 Gas Fireplaces TRISORE 95 (GLASS 3 SIDES) 9 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 341/16 865 C 397/16 1001 D 37 949 E 397/16 1001 F 211/16 68 G 8 202 H 121/2 316 I 131/8 333 J 271/4 692 K 245/8 624 L 1611/16 424 M 315/16 100 N 101/2 266 O 121/2 318 P 5/8 15 Q 411/16 118 Element4 Gas Fireplaces BIDORE 95 (RIGHT CORNER SHOWN) 10 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 345/8 878 C 417/16 1052 D 211/16 68 E 371/2 952 F 5/8 15 G 121/2 316 H 281/8 714 I 257/16 646 J 1611/16 424 K 315/16 100 L 81/2 215 M 121/2 318 N 411/16 118 Element4 Gas Fireplaces MODORE 95 11 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 51/16 128 C 33 838 D 383/16 970 E 415/16 1050 F 155/8 398 G 415/16 1050 H 5/8 15 I 411/16 119 J 3511/16 899 K 38 964 L 39 990 M 135/16 337 N 2911/16 754 Element4 Gas Fireplaces TRISORE 100H 12 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 51/16 128 C 33 838 D 383/16 970 E 415/8 1057 F 155/8 398 G 395/8 1005 H 5/8 15 I 411/16 119 J 3511/16 899 K 38 964 L 39 990 M 135/16 337 N 2911/16 754 BIDORE 100H (RIGHT CORNER SHOWN) Element4 Gas Fireplaces 13 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 51/16 128 C 33 838 D 393/8 1000 E 431/2 1104 F 155/8 398 G 393/8 1000 H 5/8 15 I 411/16 119 J 3511/16 899 K 38 964 L 39 990 M 135/16 337 N 2911/16 754 MODORE 100H Element4 Gas Fireplaces 14 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 503/4 1288 C 5711/16 1464 D 5/8 15 E 131/8 333 F 121/2 318 G 271/4 692 H 245/8 624 I 165/8 422 J 315/16 100 K 107/8 275 L 211/16 68 M 121/2 318 N 101/2 266 O 411/16 118 Element4 Gas Fireplaces TRISORE 140 (GLASS 3 SIDES) 15 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 503/4 1288 C 5715/16 1471 D 211/16 68 E 557/8 1419 F 5715/16 1471 G 5/8 15 H 101/2 266 I 121/2 318 J 411/16 118 K 165/8 422 L 245/8 624 M 271/4 692 N 315/16 100 O 107/8 275 P 121/2 318 Q 131/8 333 Element4 Gas Fireplaces BIDORE 140 (LEFT CORNER SHOWN) 16 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Inches Millimeters A 77/8 200 B 143/8 364 C 3213/16 834 D 5411/16 1389 E 607/16 1534 F 5515/16 1420 G 5711/16 1464 H 147/16 366 I 36 915 J 213/16 70 K 4 102 L 165/8 422 M 2411/16 626 N 277/16 696 O 71/16 180 P 5/8 15 Element4 Gas Fireplaces Letter LUCIUS 140 17 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 143/8 364 C 143/8 364 D 221/2 570 E 201/2 520 F 577/8 1470 G 5515/16 1420 H 5/8 15 I 213/16 70 J 3213/16 834 K 5411/16 1389 L 607/16 1534 M 371/2 953 N 4 102 O 165/8 422 P 2411/16 626 Q 277/16 696 R 71/8 180 Element4 Gas Fireplaces LUCIUS 140 C 1/3 (RIGHT CORNER SHOWN) 18 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 143/8 364 C 143/8 364 D 393/8 1000 E 377/16 950 F 577/8 1470 G 5515/16 1420 H 5/8 15 I 213/16 70 J 3213/16 834 K 5411/16 1389 L 607/16 1534 M 371/2 953 N 4 102 O 165/8 422 P 2411/16 626 Q 277/16 696 R 71/8 180 Element4 Gas Fireplaces LUCIUS 140 C 2/3 (RIGHT CORNER SHOWN) 19 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 143/8 364 C 143/8 364 D 597/16 1509 E 551/2 1409 F 597/16 1509 G 551/2 1409 H 5/8 15 I 213/16 70 J 3213/16 834 K 5315/16 1370 L 613/16 1554 M 371/2 953 N 4 102 O 165/8 422 P 2411/16 626 Q 277/16 696 R 71/8 180 Element4 Gas Fireplaces LUCIUS 140 T 20 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 77/8 200 B 345/8 1288 C 5913/16 1518 D 211/16 68 E 557/8 1418 F 5/8 15 G 121/2 316 H 281/8 714 I 257/16 646 J 1611/16 424 K 315/16 100 L 107/8 275 M 121/2 318 N 411/16 118 Element4 Gas Fireplaces MODORE 140 21 EuropeanHome.
SPECIFICATIONS and DIMENSIONS Letter Inches Millimeters A 515/16 150 B 341/4 869 C 4211/16 1084 D 213/16 71 E 321/16 814 F 5/8 15 115/8 321⁄16"/ 814 3713/16 mm 295 961 I 35 889 J 261/2 672 K 313/16 96 L 87/8 224 M 1111/16 297 N 57/16 138 Element4 Gas Fireplaces 42 ⁄16"/ 1084 mm 8"/ 203 mm 11 OPTICA 22 8 mm G H 1111⁄16"/ 297 mm mm 101⁄16"/ 255 mm 90 ° 393⁄8"/ 1000 57⁄16" 65⁄16" 127.5 mm 160 mm ???7⁄16" EuropeanHome.
SPECIFICATIONS and DIMENSIONS Millimeters A 515/16 150 B 341/4 869 mm mm C 4211/16 1084 D 213/16 71 E 321/16 814 129⁄16"/ 319 Letter F 5/8 15 G 115/8 319 mm 3713/16 961 321⁄16"/ 814 H I 35 889 J 261/2 672 K 313/16 96 L 87/8 224 M 129/16 319 N 65/16 160 Element4 Gas Fireplaces 4211⁄16"/ 1084 mm BIOPTICA 23 mm Inches 101⁄16"/ 255 57⁄16" 65⁄16" 160 mm EuropeanHome.
SPECIFICATIONS and DIMENSIONS DO NOT REMOVE NE PAS RETIRER DIRECT VENT GAS FIREPLACE - Not for use with solid fuel. FOYER GAZ À AÉRATION DIRECTE - Ne pas utiliser avec un combustible solide This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home where not prohibited by local codes. See owner’s manual for details.
SPECIFICATIONS and DIMENSIONS PARTS OF THE FIREPLACE The various parts of the Lucius 140 fireplace are shown in Figures 4, 5 and 6. These parts are typical of any Element4 fireplace. 11 9 1 8 2 6 3 7 8 5 4 1 10 8 Figure 4 3 8 1 5 4 Figure 5 shows two Glass Clamps, 10 after some of the Finish Trim 8 is removed. 1 10 Element4 Gas Fireplaces 25 Figure 5 EuropeanHome.
SPECIFICATIONS and DIMENSIONS 10 2 1 13 14 12 3 Figure 6 Figure 6 shows a Lucius 140 from below.
CLEARANCES MINIMUM CLEARANCE TO COMBUSTIBLES The beauty of the Element4 fireplaces is due largely to the fact that they are NOT zero-clearance fireplaces. All clearances to combustible AND non-combustible materials MUST be maintained as described in this manual. • The appliance is approved with a minimum clearance to combustible materials on all sides of 11”/280 mm. Any spacer or framing used closer than this dimension must be noncombustible (e.g. metal).
A VENT OPENING 800cm² (124In²) TOTAL MINIMUM CLEARANCES CTION A-A MANTELS The graph in Figure 7 shows a range of allowable depths and heights for a combustible mantel installation. INCHES 20 18 16 14 12 10 8 6 4 2 0 20 Mantel Depth Depth Mantel 18 (12) 300 12”/300 mm 16 C 14 12 8 6 4 2 A B MantelHeight Height Mantel 13”/330 mm (13) 330 10 The maximum mantel depth is 12”/300 mm at a minimum height above the fireplace opening of 13”/330 mm.
1” 1" 25 (25) mm 2” 2" 50 (50) mm CLEARANCES COMBUSTIBLE MATERIAL NON-COMBUSTIBLE LINING WITHIN COMBUSTIBLE AND NON-COMBUSTIBLE WALLS Figures 9 through 11 show clearances to Combustible Material combustible and non-combustible walls. with a Non-Combustible Lining Figure 9 shows a typical method for protecting combustible walls while maintaining close installation dimensions.
CLEARANCES A WARMOPENING AIR OUTLET VENT 800cm² (124In²) REQUIRED TOTAL MINIMUM Figure 12 C B B SECTION A-A A (36") 36” 900 mm 900 SECTION B-B 2”/50 (2")mm 50 (36") 36” 900900 mm KEEP THIS AREA FREE OF COMBUSTIBLE FURNISHINGS MATERIALS COMBUSTIBLE NOT PERMITTED IN FRONT 36” (36") 900 mm 900 OF GLASS CONSTRUCTION BEAMS COMBUSTIBLE A typical chase enclosing a Trisore fireplace (as an example) is(TYPICAL) shown in Figure 12.
(36") 900 CLEARANCES CONSTRUCTION NON-COMBUSTIBLE BEAMS COMBUSTIBLE FRAMING (TYPICAL) (TYPICAL) CONSTRUCTION NON-COMBUSTIBLE BEAMS NONFRAMING COMBUSTIBLE (TYPICAL) (TYPICAL) (2")2” 50 mm 50 (11") 280 NON COMBUSTIBLE MATERIAL A DETAIL “C” DETAIL C TOP OF FIREPLACE OPENING VENT OPENING 800cm² (124In²) TOTAL MINIMUM GLASS CONVECTION GAP NON-COMBUSTIBLE WALL (TYPICAL) DETAIL “C”C B B SECTION A-A 2” (2")mm 50 50 A (36") (36") Figure 13 COMBUSTIBLE MATERIALS NOT PERMITTED IN FRONT OF GLASS (36
CLEARANCES TYPICAL CLEARANCE DIAGRAMS The total area of the convection air outlet(s) depends on the fireplace model. (See Table 7 on page 47.) The location of the outlet(s) must allow for the free movement of air and must not allow excessive convection air to build up within the chase. The top of the outlet(s) must be at least 1”/25 mm down from the ceiling and we recommend no more than 6”/152 mm down. The minimum distance from the bottom of the appliance to the room ceiling is 72”/1830 mm. See Table 3.
GAS and ELECTRIC INSTALLING THE GAS LINE Correctly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed as per requirements outlined in the latest edition of the National Fuel Gas Code, NFPA 54 (USA) or CAN/CSA-B149.1 (Canada). Never use galvanized or plastic pipe unless specified specifically for use with gas. Refer to the table below for proper sizing of the supply gas line.
VENTING CONFIGURING THE VENTING The fireplaces in this manual are direct vent fireplaces that uses a co-axial or “pipe within a pipe” venting system. The outer “pipe” or vent conducts fresh, outside air into the fireplace and the inner vent carries the exhaust outside. This technology, which can run either horizontally through a side wall or vertically through the roof, produces an efficient system because conditioned building air is not used for combustion.
VENTING rise run Figure 15 APPROVED MANUFACTURERS and COMPONENTS Manufacturer All Bidore, Lucius, Modore, Trisore Optica, Bioptica M&G DuraVent, Inc.* only DirectVent Pro 5” x 8” components only DirectVent Pro 4” x 65/8” components Table 5 * Appendix One contains venting installation instructions. Element4 Gas Fireplaces 35 EuropeanHome.
VENTING HORIZONTAL TERMINATION DIAGRAM FOR BIDORE, LUCIUS, MODORE AND TRISORE ONLY V H Distance “H” = 0.5-5m (min - max) Distance “V” = 0.5-3m (min - max) Note - for E4-10 & 11 Elbow can go on to fire, thus “V” min = 200mm Note2 - For E4-5, use a 50mm flue Restrictor Figure 16 Dimension “H” can vary between 19”/500 mm minimum to 16’4”/5.0 m maximum depending on Dimension “V”. See Graph 1. Dimension “V” can vary between 19”/500 mm minimum to 9’10”/3.0 m maximum depending on Dimension “H”. See Graph 1.
VENTING HORIZONTAL TERMINATION GRAPH FOR BIDORE, LUCIUS, MODORE AND TRISORE ONLY Vertical Rise V (METRES) 9’10” 3.0 2.5 2.0 1.5 1.0 0.5 3.0 m 8’2” 2.5 m 6’6” 2.0 m 4’11” 1.5 m 3’3” 1.0 m 1’7” 0.5 m Maximum pipe extension, for outside wall. Use shaded area to calculate maximum alowable length (H) for the corresponding pipe rise (V). 0”/0 mm H Horizontal Run 0 (METRES) 1’7” 0.5 m 0.5 3’3” 1.0 m 1.0 4’11” 1.5 m 1.5 6’6” 2.0 m 8’2” 2.5 m 2.0 2.5 Graph 1.
VENTING HORIZONTAL TERMINATION DIAGRAM FOR OPTICA AND BIOPTICA ONLY V H Distance “H” = 0.5-5m (min - max) Distance “V” = 0.5-3m (min - max) Note - for E4-10 & 11 Elbow can go on to fire, thus “V” min = 200mm Note2 - For E4-5, use a 50mm flue Restrictor Figure 17 Dimension “H” can vary between 19”/500 mm minimum to 16’4”/5.0 m maximum depending on Dimension “V”. See Graph 2. Dimension “V” can vary between 3’3”/1.0 m minimum to 9’10”/3.0 m maximum depending on Dimension “H”. See Graph 2.
VENTING HORIZONTAL TERMINATION GRAPH FOR OPTICA AND BIOPTICA ONLY Vertical Rise V (METRES) 9’10” 3.0 2.5 2.0 1.5 1.0 3.0 m 8’2” 2.5 m 6’6” 2.0 m 4’11” 1.5 m 3’3” 1.0 m 3’3” 1.0 m 4’11” 1.5 m Maximum pipe extension, for outside wall. Use shaded area to calculate maximum alowable length (H) for the corresponding 6’6” 8’2” 9’10” 11’5” 13’1” 14’9” 16’4” risem(V).3.0 m 2.0 mpipe 2.5 3.5 m 4.0 m 4.5 m 5.0 m 1.0 1.5 2.0 0.5 1’7” 0.5 m 0”/0 mm Horizontal (METRES) Run 0 H (METRES) 0 0.5 2.5 3.0 3.
VENTING HORIZONTAL VENT TERMINATION CLEARANCES AND REQUIREMENTS Element4 Gas Fireplaces 40 EuropeanHome.
VENTING V 12”/304 mm 150 min minimum 12”/304 mm minimum 150 min VERTICAL VENT TERMINATIONS FOR ALL MODELS When installing vertical venting with no elbows, dimension “V” must be at least 3’3”/1.0 m minimum and no more than 36’/11.0 m maximum. Distance "V" 1m - 11m (min - max) Note: Configurations with vertical terminations may need a restrictor. See the INSTALLING A RESTRICTOR section. Figure 18. Vertical Terminations with NO elbows Element4 Gas Fireplaces 41 EuropeanHome.
VENTING V2 VERTICAL VENT TERMINATIONS WITH 90° ELBOWS (FOR ALL MODELS) V H V1 Distance “H” = 0”/0.0 m minimum to 9’10”/3.0 m maximum Distance “V1” = 19”/500 mm minimum to 33’10”/10.0 m maximum Distance “V2” = 19”/500 mm minimum to 33’10”/10.0 m maximum Distance “V” (V1+V2) = 3’3”/1.0 m minimum to 36’/11.0 m maximum Distance “V” must be greater than twice the distance of “H” Distance "H" =m0of- maximum 3m (min -height max) for every 90° elbow up to a maximum Subtract 3’3”/1.
VENTING V2 V V3 VERTICAL VENT TERMINATIONS WITH 45° ELBOWS (FOR ALL MODELS) H V1 Distance “H” = 0”/0.0 m minimum to 9’10”/3.0 m maximum Distance “V1” = 19”/500 mm minimum to 33’10”/10.0 m maximum Distance “V2” = 8”/200 mm minimum to 33’10”/10.0 m maximum Distance “V” (V1+V2+V3) = 3’11”/1.2 m minimum to 36’/11.
VENTING VERTICAL VENT TERMINATION CLEARANCES AND REQUIREMENTS Important Note for Roof Terminations These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI Z223.1 in the USA) or the current standard of CAN/CSA-B149.1 in Canada. Chart 1. Termination Heights A second termination may be no closer than 12”/305 mm. See Figure 36. Figure 21.
VENTING INSTALLING A RESTRICTOR As previously noted, restrictors must be fitted in some configurations. Use the table below to determine which restrictor may be needed with your venting configuration. The restrictors are shown in Figure 24.
ENCLOSING the FIREPLACE THE FRAMING A safe installation of your Element4 fireplace requires that four things be clearly understood. 1. Most important, these fireplaces are NOT zero-clearance fireplaces. Unlike most others, there is not a metal box around the Element4 fireplaces. With no metal box there are no louvers to distract your view of the fire. We do, however, want the cooling advantage of a metal box. 2.
ENCLOSING the FIREPLACE DO NOT ALLOW THE FIREPLACE TO BEAR ANY WEIGHT Dimension B Dimension A and Dimension B, shown in Figure 28, must be equal throughout the installation, no matter the model. The wall framing must be at least 2”/50 mm (NON-combustible framing ONLY) from the fireplace and the entire weight of the non-combustible wallboard (see page 6) is carried by the framing.
ENCLOSING the FIREPLACE Rough Opening Dimensions for NON-COMBUSTIBLE Framing A B C Bioptica Model Figure 30 463/4”/1184 mm 129/16”/319 mm 39”/986 mm Lucius 140 T 30 65”/1652 mm 143/8”/364 mm 391/2”/1002 mm Modore 95 30 451/2”/1152 mm 141/2”/368 mm 291/4”/742 mm Modore 140 30 633/4”/1618 mm 141/2”/368 mm 291/4”/742 mm Modore 100H 30 477/16”/1204 mm 1711/16”/448 mm 4011/16”/1032 mm Optica 30 463/4”/1184 mm 131/2”/337 mm Table 8 39”/986 mm C B A Figure 30 Rough Opening Dimen
ENCLOSING the FIREPLACE Rough Opening Dimensions for NON-COMBUSTIBLE Framing I J Lucius 140 1/3 Model Figure 32 621/4”/1582 mm 201/2”/519 mm G H 185/16”/464 mm 391/2”/1002 mm Lucius 140 2/3 32 621/4”/1582 mm 371/2”/949 mm Table 10 185/16”/464 mm 391/2”/1002 mm H J I G Figure 32 M K Rough Opening Dimensions for NON-COMBUSTIBLE Framing Model Figure Lucius 140 R L Figure 33 Element4 Gas Fireplaces 49 33 K L M 185/16”/464 mm 621/4”/1582 mm 391/2”/1002 mm Table 11 EuropeanHome.
ENCLOSING the FIREPLACE COLD CLIMATE INSULATION For cold climate installations, it is especially important to insulate outside the chase cavity, between studs and under the floor on which appliance rests, if floor is above ground level. Gas line holes and other openings should be filled with approved firestop. If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or a raised platform can be placed underneath to prevent cold transferring to the fireplace and into the room.
ENCLOSING the FIREPLACE One of the tie wraps which secure the line set. Figure 34. Figure 35. Tighten bolt through mounting bosses (at arrows) Fit tab into bracket on BDLE4 Figure 36. Figure 37 Element4 Gas Fireplaces 51 EuropeanHome.
ENCLOSING the FIREPLACE Figure 38 Figure 39 Element4 Gas Fireplaces 52 EuropeanHome.
FIRE MEDIA LOG ARRANGEMENTS (TRISORE 95, BIDORE 95, MODORE 95, OPTICA, BIOPTICA) Ensure that the hearth panel is sitting firmly in the base of the fire box, with the long slot in the center of the panel aligning with the center slots on the burner tube. The pilot flame must be visible through the panel and the cut-out in the pilot shield. Scatter the embers over the panel, as shown in Figure 40.
FIRE MEDIA LOG ARRANGEMENTS (TRISORE 140, BIDORE 140, MODORE 140) Ensure that the hearth panel is sitting firmly in the base of the fire box with the long slot in the center of the panel aligning with the top of the burner. The pilot flame must be visible through the hearth panel. Place the coals as shown in Figure 44. Ensure that the area near the pilot (circled) is left clear. Figure 44 Pine Cones Figure 45 Position the coals and pine cones as shown in Figure 45.
FIRE MEDIA LOG ARRANGEMENTS (ALL LUCIUS MODELS) Ensure that the hearth panel is sitting firmly in the base of the fire box with the long slot in the center of the panel aligning with the top of the burner. The pilot flame must be visible through the panel and the cut-out in the pilot shield. Place the six coals and two cones as shown in Figure 48. Ensure that the area near the pilot flame is left clear. Figure 48 Position the embers, coals and fir cones as shown in Figure 49.
FIRE MEDIA LOG ARRANGEMENTS (BIDORE 100H, MODORE 100H AND TRISORE 100H) Ensure that the hearth panel is sitting firmly in the base of the fire box with the long slot in the center of the panel aligning with the top of the burner. The pilot flame must be visible through the panel and the cut-out in the pilot shield. Place the six coals and two cones as shown in Figure 52. Place the logs in the order shown in Figures 52 through 61. Ensure that the area inside the ember shield is left clear.
FIRE MEDIA CARRARA PEBBLES ARRANGEMENTS (ALL MODELS) Ensure that the grate is sitting firmly in the base of the fire box with the long slot in the center of the grate aligning with the center slots on the burner tube. The pilot flame must be visible through the grate and the cut-out in the pilot shield. Scatter evenly the contents of the bags of pebbles over the top of the grate and burner. Ensure that none of the pebbles enters the pilot enclosure. The arrangement of the pebbles is now complete.
OPERATING the FIREPLACE BEFORE THE FIRST FIRE 1. 2. 3. 4. 5. 6. Make sure all construction materials have been removed from inside and around the fireplace. Confirm the proper placement of the burner media. Confirm that the controls are properly connected. Check the gas supply for leaks. Close and properly clamp the glass panels. Check that the venting is unobstructed and in proper working condition.
OPERATING the FIREPLACE Man - Manual Flame Height Adjustment. You are now able to use the remote control. To increase the flame, theÇbutton should be depressed. Pressing theÈbutton on the handset will reduce the flame. The main flame may be lowered all the way down until it is off, leaving only the pilot ignited. Fully Extinguishing the Appliance From any heat setting, press the OFF button for a few seconds. This will cause the burner to fully extinguish.
OPERATING the FIREPLACE Automatic Turndown. 1. In Manual/Temperature/Timer modes, the valve will turn to pilot flame if there is no change in flame height for a six hour period. In Temperature or Timer mode, if the ambient room temperature changes, the flame height will adjust automatically to maintain set temperature and the fire will continue to function normally. The valve will turn to pilot flame if the set temperature and the ambient room temperature remain the same over a six hour period. 2.
MAINTENANCE REMOVING AND CLEANING THE GLASS OVERVIEW The glass panels on this fireplace are held in place by a number of retaining bolts and gasketed clamps. These instructions will show you how to remove and install the clamps and glass panels. Side Trim Please read these instructions completely before proceeding. 1 TOOLS REQUIRED • No.
MAINTENANCE Step 3. Attach the vacuum glass clamp (if available) to the center of the glass and lift the glass up into the clearance notch. See Figure 73. When the glass panel is raised into the clearance notch there is enough clearance to swing the lower edge of the glass panel over the standoff frame. See Figure 74. When the glass panel is outside of the standoff frame then lower the glass panel out of the clearance notch and carefully, and securely, set the panel aside. Step 4.
MAINTENANCE BURNER MAINTENANCE WARNING Installation and maintenance must be performed by an authorized qualified installer, service agency or gas supplier. The flames from the burner should be visually checked. The flame should have a blue base and yellow tops and be candle-like in appearance. TURN OFF THE GAS before servicing the appliance. It is recommended that a qualified service technician perform an appliance check-up/service once a year.
MAINTENANCE THERMOCOUPLE MAINTENANCE The Element4 fireplaces have two thermocouples; one next to the pilot flame and one opposite the pilot burner on the other side of the main burner. The completeness and operation of both must be checked. A qualified installer must confirm that the thermocouple is in place and not cracked or damaged. Figure 76 shows a typical pilot flame engulfing the first thermocouple (shown on a Trisore 95.
WARRANTY PRODUCT INSTALLATION RECORD Installer: Please complete this form. Customer: Please retain this information. Purchased From Date of Purchase Installed By Date of Installation Fireplace Serial Number Fuel Type Element4 Gas Fireplaces 65 EuropeanHome.
APPENDIX ONE 9HQWLQJ 6\VWHP )RU 'LUHFW 9HQW *DV 6WRYHV DQG )LUHSODFHV Element4 Gas Fireplaces 66 DirectVent Pro VENTING SYSTEMInstructions INSTALLATION INSTRUCTIONS Installation EuropeanHome.
APPENDIX ONE $ 0$-25 &$86( 2) 9(17 5(/$7(' ),5(6 ,6 )$,/85( 72 0$,17$,1 5(48,5(' &/($5$1&(6 $,5 63$&(6 72 &20%867,%/( 0$7(5,$/6 ,7 ,6 2) 7+( 870267 ,03257$1&( 7+$7 '28%/( :$// ',5(&79(17 352 %( ,167$//(' 21/< ,1 $&&25'$1&( :,7+ 7+(6( ,16758&7,216 ,03257$17 5HDG WKURXJK DOO RI WKHVH LQVWUXFWLRQV EHIRUH EHJLQQLQJ \RXU LQVWDOODWLRQ )DLOXUH WR LQVWDOO WKLV SURGXFW DV GHVFULEHG LQ WKHVH LQVWUXFWLRQV ZLOO YRLG WKH PDQXIDFWXUHU·V ZDUUDQW\ PD\ FUHDWH D ÀUH RU RWKHU VDIHW\ KD]DUG DQG PD\ DIIHFW \RX
APPENDIX ONE )RU WKH PRVW XS WR GDWH LQVWDOODWLRQ LQVWUXFWLRQV VHH ZZZ GXUDYHQW FRP &217(176 DirectVent Pro VENTING SYSTEM FOR DIRECT VENT GAS STOVES AND FIREPLACES Application | Warning | Safety ,QVWDOODWLRQ 3UHFDXWLRQV & Installation Precautions 65 $SSOLFDWLRQ _ :DUQLQJ _ 6DIHW\ Options | Planning Your Installation 66 2SWLRQV _ 3ODQQLQJ
APPENDIX ONE $33/,&$7,21 QHDUE\ FRPEXVWLEOH VXUIDFHV %H VXUH WR FKHFN WKH YHQW WHUPLQDWLRQ FOHDUDQFH UHTXLUHPHQWV IURP GHFNV ZLQGRZV VRI¿WV JDV UHJXODWRUV DLU VXSSO\ LQOHWV DQG SXEOLF ZDONZD\V DV VSHFL¿HG LQ WKHVH LQVWDOODWLRQ LQVWUXFWLRQV DQG ORFDO EXLOGLQJ FRGHV 7KH JDV DSSOLDQFH DQG YHQW V\VWHP PXVW EH YHQWHG GLUHFWO\ WR WKH RXWVLGH RI WKH EXLOGLQJ DQG QHYHU EH DWWDFKHG WR D FKLPQH\ VHUYLQJ D VHSDUDWH VROLG IXHO RU JDV EXUQLQJ DSSOLDQFH (DFK GLUHFW YHQW JDV DSSOLDQFH PXVW XVH LW
APPENDIX ONE E\ 0 * 'XUD9HQW RU WKH DSSOLDQFH PDQXIDFWXUHU ,QVWDOODWLRQ RWKHU WKDQ DV LQVWUXFWHG E\ 0 * 'XUD9HQW RU WKH DSSOLDQFH PDQXIDFWXUHU ROUND HORIZONTAL TERMINATION CAP SHOWN PIPE SECTION &RQVXOW \RXU ORFDO EXLOGLQJ FRGHV EHIRUH EHJLQQLQJ WKH LQVWDOODWLRQ 237,216 7KH 0 * 'XUD9HQW 'LUHFW9HQW 3UR RIIHUV D FRPSOHWH OLQH RI FRPSRQHQW SDUWV IRU ERWK KRUL]RQWDO DQG YHUWLFDO LQVWDOODWLRQV 0DQ\ LWHPV DUH RIIHUHG LQ GHFRUDWLYH EODFN DV ZHOO DV JDOYDQL]HG ¿QLVK 7KH JDOYDQL]HG SLSH DQG ¿WWL
APPENDIX ONE VERTICAL HIGH WIND TERMINATION CAP SHOWN STORM COLLAR ROOF FLASHING CEILING FIRESTOP ROUND CEILING SUPPORT/WALL THIMBLE COVER CATHEDRAL CEILING SUPPORT BOX PIPE SECTION LPSRUWDQW WR QRWH WKH ZDOO WKLFNQHVV 6HOHFW WKH DPRXQW RI YHUWLFDO ULVH GHVLUHG RU UHTXLUHG IRU ³YHUWLFDO WR KRUL]RQWDO´ LQVWDOODWLRQV YHULI\ WKDW LW LV ZLWKLQ WKH DSSOLDQFH PDQXIDFWXUHU¶V PLQLPXP DQG PD[LPXP OLPLWV 7R GHWHUPLQH WKH OHQJWK RI YHQW SLSH UHTXLUHG IRU YHUWLFDO LQVWDOODWLRQV PHDVXUH WKH GLVWDQF
APPENDIX ONE 1RWHV 7ZLVW ORFN SURFHGXUH /LQH XS ORFNLQJ OXJV RQ PDOH DQG IHPDOH HQGV RI SLSH VHFWLRQV ,QVHUW WKH PDOH HQG RI SLSH LQWR WKH IHPDOH HQG XQWLO WKH ORFNLQJ OXJV DUH FRYHUHG 7ZLVW WKH IHPDOH HQG FORFNZLVH DQ HLJKWK RI D WXUQ WR ORFN VHFWLRQV WRJHWKHU )LJ 6FUHZV DUH QRW UHTXLUHG WR VHFXUH WKH MRLQW EXW DUH DFFHSWDEOH SURYLGHG WKH\ GR QRW SHQHWUDWH WKH LQQHU ZDOO RI WKH YHQW SLSH +RUL]RQWDO UXQV RI YHQW SLSH PXVW EH VXSSRUWHG WR SUHYHQW DQ\ GRZQZDUG VDJV +RUL]R
APPENDIX ONE 7$%/( ',5(&79(17 352 )5$0,1* 25 &87287 ',0(16,216 672&. 180%(5 '9$ :7 '9$ :76 '9$ :78 '9$ &6 '9$ )6 '9$ :)6 '9$ 966 '9$ &) '9$ &). '9$ &).6 '9$ 96. '9$ 96.6 '9$ ,6 '9$ :7 '9$ :76 '9$ :78 '9$ &6 '9$ )6 '9$ :)6 '9$ 966 '9$ 96. '9$ &) '9$ &).
APPENDIX ONE H &OHDUDQFH WR DQ RXWVLGH FRUQHU DV WHVWHG E\ DSSOLDQFH PDQXIDFWXUHU I &OHDUDQFH WR DQ LQVLGH FRUQHU DV WHVWHG E\ DSSOLDQFH PDQXIDFWXUHU J 1RW WR EH LQVWDOOHG DERYH D PHWHU UHJXODWRU DVVHPEO\ ZLWKLQ IHHW KRUL]RQWDOO\ IURP WKH FHQWHUOLQH RI WKH UHJXODWRU K &OHDUDQFH WR D VHUYLFH UHJXODWRU YHQW RXWOHW IHHW PLQLPXP L &OHDUDQFH WR QRQ PHFKDQLFDO DLU VXSSO\ LQOHW WR D EXLOGLQJ RU WKH FRPEXVWLRQ DLU LQOHW WR DQ\ RWKHU DSSOLDQFH LQFKHV PLQLPXP M &OHDUDQFH WR D
APPENDIX ONE 6125.
APPENDIX ONE SNORKEL OPTIONAL DVA-WTU ADJUST AND SECURE TELESCOPING THIMBLE SLEEVES WITH SCREWS 12" MINIMUM )LJXUH SNORKEL WALL THIMBLE COVER 12" MINIMUM ADEQUATE DRAINAGE )LJXUH Element4 Gas Fireplaces 76 EuropeanHome.
APPENDIX ONE VINYL SIDING, STUCCO OR OTHER SIDING MATERIAL 9,1
APPENDIX ONE FORFNZLVH SODFH WKH OHIW VLGH WKH ERWWRP VLGH DQG WKHQ WKH ULJKW VLGH DURXQG WKH RSHQLQJ LQ WKH VLGLQJ 5HIHU WR )LJXUH :LWK WKH SLHFHV LQ SODFH VHFXUH WKH SLHFHV WRJHWKHU XVLQJ WKH SUH GULOOHG KROHV DQG WKH VFUHZV SURYLGHG 6HDO DURXQG WKH LQVLGH FRUQHUV RI WKH 9LQ\O 6LGLQJ 6WDQGRII WR KHOS HQVXUH D ZHDWKHU WLJKW LQVWDOODWLRQ $WWDFK WKH +RUL]RQWDO &DS WR WKH 9LQ\O 6LGLQJ 6WDQGRII /LQH XS WKH KROHV LQ WKH FDS ZLWK WKH KROHV LQ WKH 9LQ\O 6LGLQJ 6WDQGRII DQG VHFXUH ZLW
APPENDIX ONE FR CEILING JOISTS MARK LOCATION 1 1/2" WOOD SCRE MARK AND DRILL FRAMING PLUMB BOB CEILING JOISTS DEC CE SU C CUT AND FRAME DECORATIVE CEILING SUPPORT COVER CUT AND FRAME 1 1/2" WOOD SCREWS )LJXUH )LJXUH 6WHS &KHFN WKH DSSOLDQFH PDQXIDFWXUHU¶V LQVWDOODWLRQ LQVWUXFWLRQV IRU UHTXLUHG FOHDUDQFHV DLU VSDFHV WR FRPEXVWLEOHV ZKHQ SDVVLQJ WKURXJK FHLOLQJV ZDOOV URRIV HQFORVXUHV DWWLF UDIWHUV RU RWKHU QHDUE\ FRPEXVWLEOH VXUIDFHV 'R QRW SDFN DLU VSDFHV ZLWK LQVXO
APPENDIX ONE )LJ 'HWHUPLQH LI FHLOLQJ MRLVWV URRI UDIWHUV IUDPLQJ RU RWKHU PDWHULDOV ZLOO REVWUXFW WKH YHQWLQJ V\VWHP
APPENDIX ONE 7$%/( 522) 3,7&+ 0,1,080 +(,*+70LQLP )ODW WR 2YHU WR 2YHU WR 2YHU WR 2YHU WR 2YHU WR 2YHU WR 2YHU WR 2YHU WR 2YHU WR 2YHU WR )HHW 0HWHUV DIMENSION "H" OBTAINED FROM TABLE 2 )LJXUH :KHUHYHU SRVVLEOH XVH (OERZV LQVWHDG RI (OERZV 7KH (OERZ RIIHUV OHVV UHVWULFWLRQ WR
APPENDIX ONE HIGH WIND VERTICAL TERMINATION OPTIONAL LOW PROFILE TERMINATION CAP SECURE FLASHING WITH NON-HARDENING SEALANT AND ROOFING NAILS STORM COLLAR ROOF FLASHING )LJXUH WKH YHQW SLSH DQG WKH FRPEXVWLEOH VXUIDFHV RI WKH HQFORVXUH 'R QRW ¿OO UHTXLUHG DLU VSDFHV ZLWK LQVXODWLRQ ,I YHQWLQJ V\VWHP SDVVHV WKURXJK DQ DWWLF VSDFH WKH $WWLF ,QVXODWLRQ 6KLHOG RU D FKDVH HQFORVXUH PXVW EH LQVWDOOHG WR SUHYHQW FRQWDFW EHWZHHQ 3LSH 6HFWLRQV DQG WKH LQVXODWLRQ RU RWKHU GHEULV )RU WKH $WWLF ,QVX
APPENDIX ONE LEVEL 2' MIN BELOW FINISHED CEILING CATHEDRAL CEILING SUPPORT BOX CUT HOLE 1/8" LARGER THAN SUPPORT BOX )LJXUH )LJXUH OVERLAP CEILING TRIM CATHEDRAL CEILING SUPPORT BOX SCREWS )LJXUH &$7+('5$/ &(,/,1* ,167$//$7,21 6WHS )ROORZ LQVWDOODWLRQ 6WHSV DQG XQGHU 9HUWLFDO 7HUPLQDWLRQV 6WHS 8VLQJ WKH SOXPE ERE PDUN WKH FHQWHUOLQH RI WKH YHQWLQJ V\VWHP RQ WKH FHLOLQJ DQG GULOO D VPDOO KROH WKURXJK WKH FHLOLQJ DQG URRI DW WKLV SRLQW )URP WKH URRI ORFDWH WKH GUL
APPENDIX ONE 6WHS 3ODFH WKH 6XSSRUW &ODPS SURYLGHG ZLWK WKH 6XSSRUW %R[ LQVLGH WKH 6XSSRUW %R[ DW WKH ERWWRP DQG VHFXUH WR WKH 3LSH 6HFWLRQ 7KH &ODPS DOORZV WKH 6XSSRUW %R[ WR VXSSRUW WKH ZHLJKW RI WKH 3LSH 6HFWLRQV &RQWLQXH WR DGG 3LSH 6HFWLRQV XQWLO \RX DUH DERYH WKH URRÀLQH 6WHS )ROORZ 6WHSV WKURXJK SDJH RI WKH 9HUWLFDO ,QVWDOODWLRQ ,QVWUXFWLRQV 6WHS ,QVWDOO WKH EODFN 7ULP &ROODU DURXQG WKH RXWVLGH RI WKH &DWKHGUDO &HLOLQJ 6XSSRUW %R[ 7KH WZR SLHFHV RI
APPENDIX ONE *(1(5$/ 0$,17(1$1&( GENERAL MAINTENANCE &RQGXFW DQ LQVSHFWLRQ RI WKH YHQWLQJ Conduct an inspection of the venting V\VWHP DQQXDOO\ 5HFRPPHQGHG system every six months.
APPENDIX ONE ROUND, SCONCE OR SQUARE HORIZONTAL TERMINATION CAP DECORATIVE CEILING SUPPORT/WALL THIMBLE COVER 2 PIECE WALL THIMBLE APPLIANCE ADAPTOR PIPE SECTION )LJXUH ROUND, SCONCE OR SQUARE HORIZONTAL TERMINATION CAP DECORATIVE CEILING SUPPORT/WALL THIMBLE COVER 2 PIECE WALL THIMBLE 90° ELBOW 6833/(0(17$/ &$1$',$1 ,16758&7,216 :KHQ LQVWDOOLQJ 'LUHFW9HQW 3UR RQ DSSOLDQFHV LQ &DQDGD D SLHFH :DOO 7KLPEOH LV UHTXLUHG LQ RUGHU WR FRPSO\ ZLWK ,5 )LJ DQG )LJ &XW DQG IUDPH DQ RSHQLQ
APPENDIX ONE VERTICAL HIGH WIND OR LOW PROFILE TERMINATION CAP STORM COLLAR ROOF FLASHING CEILING FIRESTOP ROUND CEILING SUPPORT/WALL THIMBLE COVER CATHEDRAL CEILING SUPPORT BOX PIPE SECTION PIPE SECTION APPLIANCE ADAPTOR )LJXUH Element4 Gas Fireplaces 87 EuropeanHome.
APPENDIX ONE M&G DURAVENT LIMITED LIFETIME WARRANTY M&G DuraVent, Inc. (“DuraVent”) provides this limited lifetime warranty for all of its products with the exception of Ventinox® (lifetime), and PolyPro® (ten years). Subject to the limitations set forth below, DuraVent warrants that its products will be free from defects in material or manufacturing, if properly installed, maintained and used. DuraVent products are fully warranted if installed only by a professional installer.
APPENDIX TWO MASSACHUSETTS CERTIFICATION This appliance is approved for installation in the Commonwealth of Massachusetts. The Board of State Examiners of Plumbers and Gas Fitters has issued approval number G1-1212-217 for this appliance.
APPENDIX THREE FUNCTION POSSIBLE CAUSE 1. Press UP and OFF buttons to start ignition sequence. Beep will occur each second. No Yes 2. Magnet unit is energized thus producing an obvious latching sound. Transmitter batteries low. Replace transmitter batteries. Quality 9V alkaline recommended. Receiver batteries low. Replace transmitter batteries. Quality 1.5V AA alkaline recommended. Check that transmitter and receiver are synchronized.
APPENDIX THREE FUNCTION 4. Pilot lit. POSSIBLE CAUSE No Yes REMEDY TC- and SW-cable reversed. Check cable connection between receiver and interrupter block. Magnet unit not operating properly. Replace gas valve. Short between interrupter and SW cable. Check interrupter block connection. No gas (magnet unit drops after 30 second Check gas supply. audible count.) Spark not lighting the pilot. 5. Sparking stops after pilot is lit. No Check spark is crossing pilot orifice.