Maximum pipe extension, for outside wall.
Use shaded area to calculate maximum
alowable length (H) for the corresponding
pipe rise (V).
37
VENTING
Element4 Gas Fireplaces EuropeanHome.com
1’7”
0.5 m
3’3”
1.0 m
Vertical
Rise
0”/0 mm
HORIZONTAL TERMINATION GRAPH FOR BIDORE, LUCIUS, MODORE AND TRISORE ONLY
Graph 1 shows the maximum horizontal vent run (to the outside wall) for a certain vertical vent rise on all models EXCEPT Optica
and Bioptica. The allowable venting conguration MUST be within the shaded area.
• When using a wall-mounted termination a maximum of 2 horizontally-mounted elbows (45° or 90°) may be used.
- For each 45° elbow, 20”/500 mm must be subtracted from the horizontal length allowance.
- For each 90° elbow, 40”/1000 mm must be subtracted from the horizontal length allowance.
• Between 19”/500 mm and 4’11”/1.5 m of rise, every increase of 1”/25 mm allows an increased run of 4”/100 mm.
Example A: With a total rise of 60”/1.52 m and one horizontal 90° elbow, a total run of 13’1”/4.0 m is allowed
Example B: If the rise is 3’10”/1168 mm then the run can be no longer than 12’/3.67 m.
Example C: If the run is 5’ 6”/1.68 m then the rise must be at least 2’2”/670 mm.
Graph 1. Horizontal Terminations on Bidore, Lucius, Modore and Trisore models ONLY