Owner`s manual
47
ENCLOSING the FIREPLACE
Element4 Gas Fireplaces EuropeanHome.com
Dimension A and Dimension B, shown in Figure 28, must be equal
throughout the installation, no matter the model.
The wall framing must be at least 2”/50 mm (NON-combustible framing
ONLY) from the replace and the entire weight of the non-combustible
wallboard (see page 6) is carried by the framing. Since most Element4
replaces have two or three sides of glass, the upper wall framing is
usually hung from the ceiling or often cantilevered. See Figure 29.
Figure 28
Dimension A
Dimension B
DO NOT ALLOW THE FIREPLACE
TO BEAR ANY WEIGHT
Figure 29
NON-combustible Wallboard
Metal Framing
Fireplace (typical)
2”/50 mm Clearance Between
NON-combustible Framing
and Fireplace
Convection Air Outlet Area by Model
Model
Square
Inches
Square
Centimeters
Bidore 95
Modore 95
Trisore 95
Bidore 100H
Modore 100H
Trisore 100H
50 322
Bidore 140 77 477
Bioptica 75 484
Lucius 140 119 768
Lucius 140 C 1/3 77 497
Lucius 140 C 2/3 77 497
Lucius 140 T 112 722
Modore 140 60 387
Optica 40 258
Trisore 140 70 452
A convection air outlet is always required and the area of the
convection air outlet varies by replace model. Table 7 shows the
minimum total area required for the various Element4 models. This
table assumes an enclosed chase with a top or ‘ceiling’ and with the
convection air outlet(s) on the wall(s) of the chase.
However, if the chase takes the form of a ‘half-wall’ and there is no
top on the half-wall then convection air will escape out of the ‘top’
of the half-wall. In this case, outlets on the walls are not required.
Table 7.