Product specifications
Doc ID: 12080006 Rev: A
Page 11
Technical Support: 800-626-6912 Date: 2/19/10
Installation Instructions
The 25th Anniversary Murano Spa installation must comply with all plumbing and electrical codes. A licensed plumber and
licensed electrician must complete the applicable connections of the pedicure spa.
Electrical Service
110V: 110V, 60 Hz, 5.0 Amp GFCI protected grounded circuit must be used to supply power to the pedicure
spa. (220V if ordered in 220V configuration)
220V: 220V, 50/60 Hz, 5.0 Amp GFCI protected grounded circuit must be used to supply power to the
pedicure spa.
Water Supply
• All plumbing connections must conform to local codes.
• Water pressure must be 30 to 80 PSI for the sprayer to operate correctly.
• Maximum operating water temperature should not exceed 105
°
F (41
°
C) and the maximum supply water
temperature should not exceed 120° F (49° C). (In Massachusetts, the maximum supply water temperature
should not exceed 130
°
F (54
°
C)). Adjust the hot water heater accordingly.
• For hot and cold water supply fittings and power drain fittings location, see figure 1 below.
• Carefully connect the incoming water supply lines to the appropriate fittings located on the back of the
pedicure spa. Shut-off valves are recommended.
Drain Facilities
The 25th Anniversary Murano Spa comes equipped with a power drain pump. The discharge hose is located at
the back of the 25th Anniversary Murano Spa. The drain hook-up must meet local plumbing codes.
Location/Positioning
Check your Local & State plumbing codes for additional backflow requirements. Any additional requirements
are the responsibility of the owner of the unit.
Backflow Protection Devices for Faucets with Side Spray: Check valves comply with ANSI/ASME
A112.18.3M, A112.18.1M, and CSA B12.