Installation guide

Load Current Monitoring and Diagnostics Installation and Operation Handbook
D-8
2408 and 2404 Controller
Press to show
VAL.H)
Press or
to show 100.0
Press
to show
OUT.L
Press or
to show 0.0
Press
to show
OUT.H
Press or
to show 100.0
Press
to show
SEnS
Press or
to show nor
This is the upper
PID demand level
To set the maximum
PID signal to 100%
This is the minimum
output power
To set the min
output power to 0
This is the maximum
output power
To set the max
output power to 100
This sets the output
signal to normal for
heating control
VAL.H
100.0
SenS
nor
OUT.L
0.0
OUT.H
100.0
Warning! If OUT.L is set to
any figure other than 0 the
minimum output power will be
limited to this level. You must
ensure that this does not
p
resent an unsafe condition for