Installation guide

Installation and Operation Handbook Access Levels
2408 and 2404 Controller 3-3
Level selection
The Goto display allows you to select the required
access level.
Use
and to select from the following display
codes: OPEr: Operator level
FuLL: Full level
Edit: Edit level
conF: Configuration level
Press
If you selected either OPEr, FuLL or Edit level
you will be returned to the ACCS list header in the level
that you chose. If you selected conF, you will get a
display showing ConF in the upper readout (see below).
Configuration password
When the ConF display appears, you must enter the
Configuration password in order to gain access to this
level. Do this by repeating the password entry procedure
described in the previous section.
The configuration password is set to 2 when the
controller is shipped from the factory. If you need to
change the configuration password, see Chapter 6,
Configuration.
Press
Configuration level
The first display of configuration is shown. See Chapter
6, Configuration, for details of the configuration
parameters.
For instructions on leaving configuration level, see
Chapter 6, Configuration.
Returning to Operator Level
To return to operator level from either FuLL or Edit level, repeat entry of the password
and select OPEr on the Goto display.
In Edit level, the controller will automatically return to operator level if no button is
pressed for 45 seconds.