Installation guide

Installation and Operation Handbook Configuration
2408 and 2404 Controller 6-21
Name Description Values Meaning
CAL
CALCAL
CAL
Calibration
In this mode you can
1. Calibrate the instrument using a mV source -
rcAL
or ref source
cal.
2. Offset the calibration to account for errors in actual sensor
measurement and a ref sensor -
UCAL
or user calibration
3. Return to factory set calibration -
FACT
or factory set calibration.
rcAL
Calibration
point
nonE
No calibration
PV
Calibrate main Process Value input.
PV.2
Calibrate DC input, or PV 2.
1A.Hi
Calibrate DC output high - Module 1
1A.Lo
Calibrate DC output low - Module 1
2A.Hi
Calibrate DC output high - Module 2
2A.Lo
Calibrate DC output low - Module 2
3A.Hi
Calibrate DC output high - Module 3
3A.Lo
Calibrate DC output low - Module 3
INPUT CALIBRATION
ForCAL=PV’, or ‘PV.2’, the following parameters apply.
PV
PV Calibration Value
IdLE
Idle
mv.L
Select 0mV as the calibration point
mv.H
Select 50mV as the calibration point
V 0
Select 0Volt as the calibration point
1. Select calibration value
V 10
Select 10V as the calibration point
2. Apply specified input
CJC
Select 0
o
C CJC calibration point
3. Press
to step to GO rtd
Select 400 as the calibration point
HI 0
High impedance: 0Volt cal’n point
HI 1.0
High impedance: 1.0 Volt cal’n point
See Note below.
FACt
Restore factory calibration
GO
Start calibration
no
Waiting to calibrate PV point
SelectYESwith
or YES
Start calibration
Wait for calibration to
buSy
Busy calibrating
complete.
donE
PV input calibration completed
FAIL
Calibration failed
Note. When a DC input module is installed for the first time, or there is a requirement to change one,
then the microprocessor in the controller needs to read the factory calibration data stored in the module.
Select ‘FACt’ as the calibration value. Step toGO’ and start calibration.
Goto User
calibration table-
See also chapter 7
Go to input
Calibation table
Go to
DC Output
Calibration
table