Installation guide
Installation and Operation Handbook Configuration
2408 and 2404 Controller 6-25
Node Address is set up in Operator or Full Access level. Select either of these levels, then:-
8. Press
as many
times as necessary to
select ‘cms’
9. Press
to read
‘Addr’
10. Press
and to
select the address
Valid addresses are from 0 -
63
11. Press
to read
‘nw.St’
Indicates the network status:-
‘run’ = network connected
and operational
‘rdy’ = network connected
but not operational
‘OFF.L’ = network not
connected
cms
List
Addr
5
nw.St
run