MODEL 808/847 UNIVERSAL PID PROGRAMMER/CONTROLLER MODEL 809/849 THREE-STATE VALVE POSITIONER PROGRAMMER/CONTROLLER Contents Chapter 1 SAFETY, EMC AND GENERAL INFORMATION Safety..........................1-1 1 Electromagnetic compatibility. . . . . . . . . . . . . 1-l GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . l - l l-l Unpacking and storage . . . . . . . . . . . . . . . . . 1-1 General description . . . . . . . . . . . . . . . . . . . . SERVICE AND REPAIR. . . . . . . . . . . . . . . . .
Resistance thermometer (RTD) Pt1 00, three-wire device. . . . . . . . . . . . . . . . . . . . . . 2-8 Linear input (Option QLS . ...) . . . . . . . . . . . . . . 2-8 Digital communications (option) . . . . . . . . . . . 2-9 Programmer/controller (option QP...), setpoint programming option. . . . . . . . . . . . 2-1 1 Chapter 3 TECHNICAL SPECIFICATION Chapter 4 PRODUCT CODE Chapter 5 OPERATION Operating structure . . . . . . . . . . . . . . . . . . . . 5-1 Operating modes . . . . . . . . . . . . . . .
Chapter 9 SELF-TUNING Self-tuning Self-tuning Self-tuning Self-tuning - General. . . . . . . . . . . . . . . . . . . Activation. . . . . . . . . . . . . . . . . . Operation . . . . . . . . . . . . . . . . . Abort conditions. . . . . . . . . . . . . 9-l 9-2 9-2 9-7 Chapter 10 INSTRUMENT REGISTER Chapter 11 SUPPLEMENTS- Relating to 808/809 valve positioner controllers Valve positioner controller (motor open/close) 1 1 - 1 Additional parameters for valve positioner controller . . , . . . . . . . . . .
General SAFETY, EMC AND GENERAL INFORMATION Please read this section carefully before installing the controller This controller is intended for industrial temperature and process control applications when it will meet the requirements of the European Directives on Safety and EMC. Use in other applications, or failure to observe the installation instructions of this handbook may impair the safety or EMC protection provided by the controller.
General Without change of the hardware the main process variable input of the instrument can be configured to suit various thermocouples and resistance thermometers, (PtlOO). Recalibration is not necessary for this procedure. Signals up to 25V can be accommodated by using input adapters in the linear input option. Linearisation is scaleable within the display range of -999 to 9999, with tenths display resolution. The controller is also equipped with a ramp to setpoint function.
General lNSTALLATlON SAFETY REQUIREMENTS Safety Symbols Various symbols are used on the instrument, they have the following meaning: . Caution, (refer to the accompanying documents) I Functional earth (ground) terminal The functional earth connection is not required for safety purposes but to ground RFI filters.
General Earth leakage current Due to RFI Filtering there is an earth leakage current of less than 0.5mA This may affect the design of an installation of multiple controllers protected by Residual Current Device, (RCD) or Ground Fault Detector, (GFD) type circuit breakers.
General . an external valve or contactor sticking in the heating . the controller setpoint set too high. Where damage or injury is possible, we recommend fitting a tion unit, with an independent temperature sensor, which will Please note that the alarm relays within the controller will not conditions. condition; separate over-temperature protecisolate the heating circuit.
installation INSTALLATION Before installing this product read the safety and EMC information Dimensions and panel mounting The instrument is intended to be mounted into a front panel cut-out. Figure 2.1.1 shows the dimensions of the instrument and of the necessary front panel cut-out with tolerances. Behind the instrument sufficient space should be provided for wiring. +0.60 45mm -o.oo 96mm Front panel cut-out Maximum thickness 6mm Figure 2.1.
installation at least 50mm at least 50mm Figure 2.1.2 Minimum spacings for multiple installation Electrical connections When wiring electrical equipment, please refer to the instructions in Chapter 1, Safety, EMC and General Information and Chapter 3 Technical Specification. Before wiring, verify from the instrument label (on the side) which options have been built into the instrument and how the instrument is configured. The terminals at the rear of the instrument are numbered from 1 to 20.
Installation will read the line voltage even though the output is off. This does not indicate that the output is faulty. Such a test should only be carried out when the output is loaded appropriately.
Installation output 1 Output 1 can be fitted with four output module types: triac (Tl), relay (Rl), logic (Ll) or DC (Dl). Check the relevant code on the instrument label. The external connections depend on the type of output module installed. If output 1 is configured as time proportioned with power feedback, the mains supply of the instrument must be connected to the same Live as the load supply.
Installation Function External Connections Terminals Internal Device Triac (T1) Triac c o n d u c t s d u r i n g ON Phase ( y e l l o w OP1 l a m p ON) To mains 80 - 264V AC 50/60Hz Relay (R1) Relay c o n t a c t i s c l o s e d luring ON phase (yellow OP1 l a m p O N ) Logic (L1) Logic output = +18V Wing ON phase of Output c y c l e ( y e l l o w OP1 amp ON) ov (-) Logic signal (+) +18V, m a x 1 10mA DC (D1) DC signal (+) 4-20mA / 0-20mA Not Isolated from thermo Figure 2.3.
Installation Function External Connections Terminals Internal Device Tr (T1) riac Cool c h a n n e l o n l y iac conducts during Oh phase ( y e l l o w O P 2 l a m p ON) To mains , ted elay channel elay contact is closed during O N p h a s e ( y e l l o w (OP2 l a m p O N ) larm Output Contacts e n e r g i s e d during a l a r m c o n d i t i o n (OP2 l a m p O N ) 2A To mains 80 264V AC I I Logic Cool channel Logic output = +1 ON phase of output c y c l e ( y e l l o w O P 2 w output output = a
Installation Output 3, Alarm This alarm channel can be fitted with relay (Rl) or logic (Ll) output module types. Check the relevant code on the instrument label. The external connections depend on the type of output module installed. When in the alarm condition, the alarm relay is de-energised. The alarm circuit connected should be fused and designed to operate in a failsafe manner, even in the event of a blown fuse. In the alarm condition an appropriate annunciation appears on the LED display.
installation Resistance thermometer (RTD) Ptl 00, three-wire device Connect the single wire of the sensor to terminal 19 and the double wire to terminals 18 20. The length and gauge of all three wires must be equal. The cable resistance is compensated for by the three-wire device. Sensor break display is shown only if two wires break Sensor External Connections Terminals no connection Figure 2.3.
Installation Process Signal (Option QLS only ) Voltage Adapter -10 . . . +50mV NONE - 4 0 +200mV IAV2 -200 . . +1000mV IA1V -1 . . . +5V IA5V - 2 +10V 1A10V IA25V -5 . . +25V External Connections Ground Input Adapter Terminals Adapter T YP IA... Controller Terminals O I V. in t Current -4 .. .+20mA Adapter IAA02 Figure 2.3.6 Linear input, Terminals 18, 19 & 20 Digital communications (option) Verify on the instrument label if an EIA232 or an EIA422 interface is installed.
Installation If the instrument is configured as a programmer controller, terminals 16 17 no longer serve as a lock-out override, but instead take on functions associated with the programming option, see following sections. The digital communications output is isolated from the thermocouple input. Figure 2.3.7 shows terminal allocation for in-built digital communications.
Installation Programmer controller (Option QLPS), programming option If the instrument is configured as a programmer controller (see instrument label), the RUN 17. Figure 2.3.8 shows and HOLD states of a given program are controlled via terminals 16 possible connections. The function of the programmer controller is described in later sections HOLD/RESET Model to start program (restart after HOLD/RESET) reset to beginning of program and hold Option A. Switch 6. logic with opto-coupler C.
Technical Specification TECHNICAL SPECIFICATION Environmental ratings Instruments are intended to be panel mounted. The rating of panel sealing is IP54, (EN 60529), or NEMA 3 when used with the optional gasket kit, part number LA 022339. 0 to 50°C. Ensure the enclosure provides adequate ventilation. 5 to 95%, non condensing. The instrument is not suitable for use above 2000m or in explosive or corrosive atmospheres.
Technical Specification Linearisation accuracy: RTD linearisation: Linearisation accuracy: Maximum lead resistance: DIN 43760; BS 1904 Electrical safety Standards: Installation category II: Pollution degree 2: Isolation: EN 61010, Installation category II, pollution degree 2. CSA C22.2 Voltage transients on any mains power connected to the instrument must not exceed Conductive pollution must be excluded from the cabinet in which the instrument is mounted.
Product Self-tuning: Auto/manual behaviour: Code Automatic adjustment of control parameters in start-up phase or when required. Bumpless transfer to manual operation, adjustable -99.9 to 100.0%. Programmer/controller Programs/segments: Program parameters: Holdback: Baud rate/character format: One program with four segments, consisting of ramp l/dwell period l/ramp 2/dwell period 2. 0.01 to 99.
Product Code PRODUCT CODE Basic instrument 808, vertical instrument 847, horizontal instrument 809, vertical instrument 849, horizontal instrument Output modules, Output 1 / 2 & alarm Output 1, heat No output Relay, 2A /264 V AC Logic, 18 V I 20mA Triac, /1A / 264 V AC DC, 0 to 20mA I 4 to /20mA max.
Product Code Linear, with appropriate input adapter, see calibration code X Measurement range B N E J L K P R S T Z Code . A -250 to +250 . . . -100 to +l00 B . . . . -100 to +400 C . . . . -75.0 to +400.0 D . . . . . . . . . . 0 to +100 E . . . . . . . . . . F 0 to +200 0 to +300 . . . . . . . . . 0 to + 4 0 0 H 0 to 1-600 . . . . . . 0 to +800 K . . . . . . 0 to +1000 L . . . . . 0 to +1200 M . .
Product Code Code Output 3, alarm 0 No alarm 4 Full-scale low alarm 5 Full-scale high alarm 6 Deviation band alarm Alarms non-latching (standard), relay de-energised in alarm condition. Alarm latching configurable. Operating instructions, a manual is enclosed in the packaging GDR German ENG English FRA French (only 808 / 847) NED Dutch (only 808 / 847) Basic Instrument 8081847 Output Modules Output 1 Output 2 Output 3 Measurement Linearisation Range Units Comms.
Operating structure The operation of the instrument is structured on two access levels. Within these levels, three operating modes and four control algorithms with their parameters may be selected. Operator level: The operator level is intended for normal, everyday operation of the controller at the plant, The modifiable parameters on this level are fixed by the commissioning engineer in the ACCESS menu. Configuration level: The configuration level is intended for commissioning the instrument.
Operation Operating modes The controller can function in three different operating modes. In automatic or closed loop, the output of the controller is determined by the control algorithm. In the base condition, the process value and the setpoint appear on the LED display. The setpoint is modified by the raise and lower buttons. Changeover to manual is through the A/M button (if not locked out, see section 5.4).
Oaeration Front panel identification The instrument is operated and also configured by means of four pushbuttons and displays on the front fascia (Figure 5.4.1). Displays: The upper display indicates the measured value when in the base condition. On selecting a parameter, the appropriate parameter abbreviation appears. If one of the configured alarm conditions occurs, the display flashes. The lower display indicates the setpoint when in the automatic mode and the output level set when in the manual mode.
Operation A. B C. D E F G. H. I. J. K. L. Communications in progress Ramp-to-setpoint in progress Manual operating mode Upper LED display Lower LED display Output 1 energised beacon Output 2 energised beacon Parameter/Scroll alarm acknowledge pushbuttons Raise parameter value pushbutton lower parameter value pushbutton Auto/manual operation selection pushbutton Jacking screw Figure 5.4.
Operation operating mode to the manual mode. Depressing the button again returns the controller to automatic. The changeover is bumpless, the output level at the time of the changeover is transferred into the required operating mode. If the instrument is configured as an ON/OFF controller, the output level can only assume one of two values (0 or 100%). This button can be locked out in the configuration level, so that the instrument remains in the operating mode chosen before lockout.
Operation Original setpoinr trajectory Setpoint Modified setpoint trajectory Target setpoint e target setpoint B. Change in target setpoint: ramping leads to new target setpoint Original setpoint target Original setpoint trajectory Setpoint Modified target Change in target setpoint target setpoint C . Change in target setpoint new setpoint already exceded Time by ramp Figure 5.5.
Operation Alarms Two alarm outputs may be installed in the controller. Three different types of alarm can be set up with these alarm outputs by configuration: . Full-scale high alarm (H AO) . Full-scale low alarm (L AO) . Deviation band alarm (d AO) In the alarm condition, the alarm outputs fitted and configured with the appropriate modules are energised. Alarm output 1 and alarm output 2 possess different characteristics.
Operation Alarm output 1 (fitted with the appropriate module) operates as the collective alarm for all configured alarm types, i.e. it operates if at least one of the configured alarm conditions occurs. The function of the alarm output can be configured for each type of alarm as ‘latching’ (LAt), ‘non-latching’ (nLAt) or as ‘not active’ (OFF). If the appropriate alarm type is configured as non-latching, it is then a ‘soft-alarm’ in the instrument.
Operation the nearest EUROTHERM branch for inspection. Under no circumstances should the faulty instrument be used.
Configuration CONFIGURATION LEVEL, OPERATOR LEVEL Configuration link/switch There are over 30 parameters maintained in the non-volatile memory of the instrument. These parameters are pre-set according to the product code and corresponding standard values, but can, however, be modified at any time by commissioning staff allowing for the available and externally connected hardware.
Configuration R Configuration Link open = operator level M Link closed = configuration level OP1 OP2 Figure 6.1.1 Configuration link/switch Hardware configuration It is important to note in the configuration of the instrument that the configuration parameters possible for an output (OP 1, OP 2 or AL 1) depend on the output module installed. Depending on the output module, only certain configuration values may be selected. Figure 612.
Configuration Parameter list All parameters available in the instrument are listed on the following pages. The sequence of parameters corresponds to the sequence in the instrument, as it appears after pressing the PAR button. Some parameters influence the appearance, and similarly the disappearance (HidE), of other parameters, e.g. the cool cycle time is hidden if no cool output channel is configured. Other parameters depend on the firmware options of the instrument.
Mnemonic Parameter Adjustable range Factory setting Comments LOWER SP LEVEL Setpoint Upper limit: ‘SP H’ Lower limit: ‘SP L’ No n e Output level -99.9 to + 100.0% (heat/cool) 0.0 to 100.0% (heat only) C or F Display units (plus active program segment) Display only PROGRAMMER/CONTROlLER (Option QLPS...
PROGRAMMER/CONTROLLER (Option QLPS...)continued Hb* Holdback 1 to (without tenth’s precision) These parameters appear only f ‘Ctrl’ is configured as ‘Prog’ 100” or units Only appears if ‘Ctrl’ is configured as ‘Prog’ or 100.0” or units Tenths’ precision if measured range is so configured 1 to 3600°F 1 to 9999 units Holdback (with tenths’ precision) 0.1 to 0.1 to 0.1 to 999.
Mnemonic CONTROL c c.t H cb cb Parameter Adjustable range Factory setting Comments (continued) Cool cycle time 0.3 to 80.0s High cutback start-up optimisation 1 to 2000 1 to 3600 1 to 9999 units (without tenths’ precision) High cutback start-up optimisation with tenths’ precision Low cutback SETPOINT LIMITS SP H Setpoint high limit SP I.
MEASURED VALUE INPUT OFst Input/calibration offset CF unit selection Sn DIGITAL Addr bAud Linearisation COMMUNICATIONS These parameters appear only -9.99 to 99.99 Degrees Centigrade Degrees Fahrenheit thermocouple K thermocouple PL2 thermocouple R thermocouple S thermocouple T thermocouple J th’couple O’s prec) Ptl 00, 3-wire L thermocouple L th’couple O’s prec) Linear input Linear input (l/l O’s prec) BOARD Instrument address 0.0 to 9.
Mnemonic Parameter GENERAL OP 1 output 1 (hardware Adjustable range configuration) Time-proportioned O-20mA Time-proportioned with power feedback Off output 2 (hardware configuration) Cooling algorithm Output 2 alarm Fan cooling, linear Parameter is output module dependent O-20 4-20 PFb Feedback of mains fluctuations: connect controller & load to same Live Parameter is output module dependent Min. 500ms unit ‘Min. 35ms unit Condensing water cooling (35ms unit) Min. 5% of C c.
Proportional band scale to 999.9 I Set to I measurment ranae 90.0 to 999.9 0.1 to 999.9 units Enabled Cb * Cutback function LINEAR INPUT (Option QLS) Act Control action Hi L o I. Fil Proc ACCS CAL Measurement upper limit ranae break) Measurement range lower limit (sensor break) Input filter Process scaling (straight line equation] Disabled YES no Automatic value (3x Pb) Adjustable parameter HAnd Automatic vReverse Direct rEv dir Automatic Reverse (PV below SP heat) -999 to 9999 -99.
Configuration Pre-configuration, parameter setting A large number of parameters are installation-dependent, and as such only need setting once before commissioning. This setting should take place before connecting the instrument to the plant, e.g. at a bench. In addition, these parameters should, for security reasons, be removed from the operator’s ACCESS menu (HidE). WARNING Never configure the instrument while it is controlling a process.
Configuration To adjust cutback, both parameters are set in the first instance to match the proportional band. Thus cutback is cancelled (switched off). The data is always in display units and must therefore be recalculated in percentage for proportional band: Hcb=Lcb=Pb for Pb in units: H cb = L cb = Pb(%) x measurement range/100 for Pb in %: Now the process is started up with a large control deviation and the degree of over- and undershoot is registered.
Calibration Parameter access protection This menu defines the parameters which are modifiable at the operator level. The menu is only available when the configuration link/switch is closed. Here, each parameter is defined as to whether at the operator level it is: . ‘readable and alterable’ (Altr) ‘readable only, not alterable’ (rEAd) . ‘hidden’ (HidE). With the configuration link/switch closed, scroll down to the mnemonic ACCS using the PAR button.
Calibration BUTTON DISPLAY: OPERATION: 1. Instrument configuration switch in ‘CONFIG’ position. 2. Depress PAR button until display shows: 3. Depress ‘raise’ button, first paramete appears: r A 4. Depress ‘lower’ button until desired access appears 5. Depress ‘raise’ button to advance to next parameter Assign access for all parameters Figure 7.1 .
Calibration Factory calibration is stored in the non-volatile memory of the instrument, and can be retrieved at any time without the aid of calibration sources. For factory calibration, follow the instructions given in Figure 7.2.1, the instrument must be set to configuration mode by closing the configuration link/switch. Factory calibration must not be attempted while the instrument is controlling a process. Field calibration of the instrument should only be performed by trained and qualified personnel.
Calibration Depending on the measurement range, different reference voltages must be calibrated in the instrument. The necessary references are listed in Figure 7.2.2 and must be calibrated in the sequence given in the table. REFERENCE 1. 2 0 . 0 0 m V 2. 5 0 , 0 0 0 m V 3. CJC 4. Pt100 # MNEMONIC 20.0 50.0 CJC All MEASUREMENT RANGE INPUT thermocouples RTD Linear input . # ! . . . . . rtd = required calibration NOTE: Calibration must be performed in the order given in the table Figure 7.2.
Calibration BUTTON OPERATION: DISPLAY: 1. Instrument switch in CONFIG position Connect calibration, source and set to appropriate value. 2. Depress PAR button until display shows: 3. Depress ‘raise’ or ‘lower’ button until appropriate reference appears: 4. Depress PAR button once:: 5. Depress ‘raise’ or ‘lower’ button: 6. Acknowledge with the PAR button: 7. After about 5 seconds the calibrator procedure is completed. Select next reference to be calibrated and repeat procedure.
Calibration linear input option With option QLS, linear input signals (mV and process signals with an appropriate input adapter) can be connected to the input and conditioned according to a linear equation. 2. Set-up point (example) (example) 20 10 30 40 Input signal (mV) Figure 7.3.
Programmer/Controller PROGRAMMER/CONTROLLER Programmer/controller - Function Models 808 and 847 with option QLPS contain an in-built setpoint generator in addition to the controller function. This setpoint generator can produce a temperature/time profile with four segments. When the program is running, the current setpoint from the setpoint generator is fed to the control algorithm. The current setpoint is continuously shown on the lower display.
Programer/Controller the ramping rate in units per minute (0.01 to 99.99), parameters L1 and L2 the appropriate target setpoint in display units (adjustable over the configured measurement range, but not restricted by SP H and SP L). The starting setpoint for ramp 1 is always the current measured value (servo). Even during a program repeat, the starting setpoint is always set equal to the current measured value at the moment of reset.
the program on the current setpoint. From the Hold state, the program can be continued (run) or reset (IdlE). Setpoint Setooint >I Figure 8.2.1 Programmer/controller states Programmer/controller - Holdback The holdback state (Hb) is a special case of Hold. It is activated of its own accord by the programmer/controller and cannot be selected by the user. The Hb parameter allows the user to set the difference tolerated between the current setpoint and the actual value while the program is running.
Programmer/Controller Setpoint/actual value Process value Time Process value oscillates during dwell period: HOLDBACK stops the time base when process value outside holdback band Figure 8.3.1 Holdback Programmer/controller - Setpoint programming The state of the programmer can be modified in three ways. All three have the same priority and the last action from any of them is acted upon: .
Programmer/Controller Programmer/controller - Annunciators The LED beacon R in the upper section of the display panel indicates the current state of the programmer/controller: . LED off IdlE . LED on *run Hold or Holdback . LED flashing Programmer/controller - Parameter modification Modifications to the parameters specific to a particular program are differently interpreted according to the state of the programmer/controller.
Programmer/Controller Ending a program At the end of a program, the programmer/controller returns to the IdlE state and switches back to the normal control setpoint (SP). According to the target setpoint of ramp 2 and the normal control setpoint, different conditions ensue. The setpoint can be modified as in normal closedloop operation whilst the program is running and influences the end of the program. Figure 8.5.1 shows a combination of all possibilities.
Programmer/Controller Program recovery following loss of power All the instrument parameters are stored in non-volatile memory. When power is lost, the current point in the program is also stored in the memory. When power is restored, the programmer/controller resumes the program in the appropriate segment at the point reached at the moment of interruption, as soon as the process value re-enters the holdback band. Setpoint/actual value Process value Time Power failure A.
Self-tuning SELF-TUNING Self-tuning - General 808 and 847 controllers have in-built self-tuning as a standard feature, which can be activated by the user on demand. According to a special procedure, the instrument examines the process reaction curve and calculates by means of a complex computer algorithm the optimum control parameters, using the data measured during the procedure. The parameters thereby obtained after successful tuning are automatically set into the instrument.
Self-tuning band for the cool channel. Here, too, a correct setting of rEL.C is necessary before activating self-tune. Self-tuning - Activation Self-tuning can be activated under the following conditions: Operator level (not in configuration level) . Automatic operating mode (closed loop) . PID control algorithm (Pid, r SP, or Prog) In the following circumstances, self-tuning is halted or overridden: Tuning is halted when the controller is switched over from automatic to manual.
Self-tuning Tune from ambient: The desired setpoint for tuning can be adjusted with the raise or lower buttons for about one minute. During this time the output level is reset to zero. Also at this time the influence of adjacent zones on the specific zone is observed and compensated for in the algorithm. After this the actual tuning operation begins, the instrument commands heat (if setpoint is greater than actual value) or cool (if setpoint is smaller than actual value) with maximum output strength.
Self-tuning Process value Process reaction curve output Tune from ambient - cool down Figure 9.3.
Self-tunina Tune from setpoint: After initiating a self-tune from setpoint, the output power is fixed for one minute at the original value. If during this time a new setpoint is set, the instrument automatically switches to tuning from ambient. Again at this time, the influence of adjacent zones on the specific zone is observed and compensated for in the algorithm. After this, both outputs are switched off for a short while and the process reaction curve is observed.
Self-tuning Process value CP I...................., -Setpoint- fictitious Setp PV4 output 100% 0% Tune from Setpoint - endothermic process Figure 9.3.
Self-tuning Self-tuning - Abort conditions In some cases, the self-tune routine aborts spontaneously due to external influences in the process being tuned for by the instrument. In a heat-only controller, this is the case when, for example, through the influence of an adjacent zone, the process is heated up to the setpoint without its own heat source. The tuning algorithm recognises such a case and aborts the tune of its own accord after a time (depending on the process reaction).
Self-tuning Process value -Setpoint Cl fictii Tune from ambient heat/cool, abort Figure 9.4.
Register INSTRUMENT REGISTER On the following pages is an instrument register for models 808 and 847 digital controllers. Record data here for each individual instrument. In the parameter tables, up to three different parameter adjustments can be recorded. Instrument Basic Instrument output 1 Month Output modules output 2 output 3 Linearisation Measurement Display Range Units Type u Year Serial No.
Register Parameter Mnemonic LOWER PARAMETER LEVEL none Output level (Manual only) C or F Display units (Display only) OUTPUT POWER LIMITS H PL Max. power output Sensor break power output I Measured value input Calibration offset unit selection Sensor linearisation select C F Sn DIGITAL COMMUNICATIONS Addr Instrument address Baud rate I I Alarms Hi Al Lo Al d Al Full-scale high alarm Full-scale low alarm Deviation alarm CONTROL PARAMETERS band I t H c.t c c.
Register Mnemonic Parameter CONTROL PARAMETERS SETPOINT LIMITS SPH Setpoint high limit Setpoint low limit SPL ALARM 1 OUTPUT HA0 LAO dA0 Full-scale high alarm Full-scale low alarm Deviation band alarm INSTRUMENT CONFIGURATION Identification number Control algorithm Setpoint ramp rate idno Ctrl SPrr OPl output 1 (Hardware configuration) OP2 output 2 (Hardware configuration) AH Automatic/manual enable Cold junction compensation CJC Pb d PH-L Proportional band display Proportional band scale
Supplements SUPPLEMENTS RELATING TO 809/849 VALVE POSITIONER CONTROLLERS The dimensions, technical data, operation etc. are equivalent to the 808/847 controller series and can be taken from the appropriate chapters of this manual. Further information is contained in the 809/849 series.
Supplements Additional parameters for valve positioner controller You will find general parameters for the 809 in Chapter 6.3, parameter list. In addition, the following control parameters (see Figure 6.3.2) may be accessed and modified: Display mnemonic tt TT TM ct inrt blSh TN BK Parameter Motor travel time Cycle time Adjustable range Function 0.1 to 240s Motor travel time 0.1 to 240s Output cycle frequency (periods for ON and OFF) Motor inertia time 0.000 to 1 .