2132 and 2116 PID Temperature Controllers Thank you for choosing the 2132 or 2116 Temperature Controller. Supplied in 1/32 and 1/16 DIN panel sizes they are designed for accurate, stable control of ovens, chillers, sterilisers and other heating and cooling processes. Two outputs are configurable for heating, cooling and alarms. The controller is supplied configured according to the order code given in section 5. Check this on the side labels to determine the configuration of your particular controller. 1.
1.1 To Install the Controller Please read the safety information in sections 7 before proceeding. 1. Prepare the panel cut-out to the size shown 2. Insert the controller through the cut-out. 3. Spring the panel retaining clips into place. Secure the controller in position by holding it level and pushing both retaining clips forward. 4. Peel off the protective cover from the display 1.
2. Electrical Connections Solid State Relay (SSR) Logic I/O 1B T/C Pt100 OR 1B 1A 24 20-29 Vac/dc Low voltage supply Model 2116 L N Model 2132 1A A V- V+ AB - + Output 2 N Relay 2.49Ω mA Sensor Inputs 2.1 24 External Relay Module (Operated by the logic output) Wire Sizes L Line 85-264Vac 50/60Hz Neutral 24 24 20-29 Vac/dc Low voltage supply The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22AWG).
2.2 Typical Wiring Diagram Heater fuse Line Circuit Breaker Controller fuse 2A type T Solid State Relay (e.g. TE10) 1B 1A V- V+ A Model 2132 A L N Heater Neutral + Thermocouple Snubber* Cooling or alarm relay Safety requirements for permanently connected equipment state: Relay output fuse 2A type T * When switching inductive loads such as contactors or solenoid valves, wire the 22nF/100Ω ‘snubber’ supplied across relay terminals AA & AB.
3. Operation 3.1 Switch on the controller. Following a 3 second selftest sequence, you will see the display shown below. It is called the HOME display. Press and release quickly the or button. The setpoint will be displayed for 2 seconds. Output 1 Output 2 OP1 OP2 20 Actual Temperature (or Process Value ‘PV’) OP1 illuminates when the logic output is ON (normally heating).
3.2 To View The Display Units Press and release quickly the or display units will be flashed for 0.5 sec. 0.5 sec o C 20 button. The C Deg Centigrade F Deg Fahrenheit * K Deg Kelvin Linear inputs - no units displayed * * and together will If you get lost, pressing always return you to the HOME display. If, at any time, no key is pressed within 45 seconds, the display will always return to the HOME display. To Acknowledge a New Alarm Press and together.
3.5 To View The Output Power Do this if you want to see how much heating or cooling energy is being demanded by the controller. Note: This is not a measure of actual power. HOME display 20.0 Press twice quickly Warning! * C OP 100.0 Press or Controller is demanding 100% heat In manual standby mode (see ‘To Use The Timer’) the output power can be adjusted by the operator, causing heating or cooling to be permanently applied.
3.6 To Select or Change Other Parameters Parameters are settings in the controller which you can change to suit the process. They are found under list headings. button to step through the list headings Press the as shown below. Turn to paragraph 3.8 to see all of the list headings. These lists are used to: • Change alarm setpoints • Tune the controller to the process • Manually select PID values • Change setpoint limits and access the in-built timer • Change input and output limits HOME display 20.
3.7 Press To Adjust The Alarm Setpoints (Trip Levels) Press or displays List indicating a list heading 2 secs twice to choose the AL list. 0.5 sec * 20 C 2nd press There are three Alarms. The setpoint for each alarm is found under the AL list. If an alarm has been disabled, it will not appear in this list. Note: The other parameters listed in section 3.8 are accessed and adjusted in exactly the same way as this example.
3.8 Parameter Lists Home List X2 Alarm List 20.0 AL OP 1---(1) w.SP 2--- m A 3---(1) diSP (1) Autotune List Atun PID List(2) Pid Setpoint List Input List SP Access List Output List(2) On/Off List iP oP On.Of ACCS tunE Pb SP L FiLt OP.Lo HYS.H codE AdC ti SP H CJCO OP.Hi Hys.C Goto td SPrr mV CYC.H HC.db Conf rES tm.OP OFS CYC.C Lcb tmr CAL.P Ont.H Hcb dwel CAL Ont.C rEL.C StAt Pnt.
3.8.1 Summary 1. Press to step across list headings. 2. Press to step down parameters 3. Press to view the value of a parameter. Keep pressing to decrease the value. 4. Press to view the value of a parameter. Keep pressing to increase the value Part Number HA026270 Issue 5.
3.9 Parameter Tables Home List Adjustable Range Op Output Power -100% = max cooling, 100.0% = max heating. w.SP Working Setpoint Only appears when setpoint rate limit enabled Manual/ Auto mAn m-A Auto Select disp Home Display Options Automatic control selected OP Displays the output power - for use as a manual station. (Only applies to software version 1.4) the AL.SP pv.
AL Alarm List (See section 3.
Atun Automatic Tuning List (See section 4.3) tunE Automatic Tune Enable OFF or on Off Adc Automatic Manual reset calculation (when P+D control) man or caLc man Adjustable Range Default Setting PID List (See section 4.3) Adjustable Range Pb Proportional Band 1 to 999.9 display units ti Integral Time OFF to 9999 seconds 360 td Derivative Time OFF to 9999 seconds 60 rES Manual Reset Value -100 to 100.0 % 0.
SP Setpoint List (See also ‘To Use the Timer’ section 3.11) Adjustable Range SP L Setpoint Low Limit -1999 to 999.9 As per order SP H Setpoint High Limit -1999 to 999.9 As per order sprr Setpoint Rate Limit 0FF to 999.9 display units per minute tm.OP Timer Operating Mode Opt.1 to Opt.5 tmr Time Remaining 0 to 9999 minutes dwEl Dwell Time 0FF to 9999 minutes OFF StAt Timer Status OFF or on OFF Part Number HA026270 Issue 5.0 Aug 07 Default Setting Customer setting Off OPt.
iP Input List (See also ‘User Calibration’ section 4.2) Adjustable Range FiLt Input Filter Time Constant 0FF to 999.9 seconds CJC* Cold Junction Temperature measured at rear terminals Read only Millivolt Input measured at the rear terminals Read only mV Default Setting -1999 to 9999 display units OFS Process value Offset CAL.P Calibration Password 0 to 9999 CAL User Calibration Enable FACt Re-instates factory calibration Customer setting 1.
oP Output List Adjustable Range OP.Lo Low Output Power Limit -100 to 100.0 % OP.Hi High Output Power Limit -100 to 100.0 % 100.0 CYC.H Heating Output Cycle Time 0.2 to 999.9 seconds 1.0 Lgc 20 Rly CYC.C Cooling Output Cycle Time 0.2 to 999.9 seconds 5.0 Lgc 20 Rly ont.H Heating Output Minimum On Time Auto to 999.9 seconds (Auto = 50ms) Auto ont.C Cooling Output Minimum On Time Auto to 999.9 seconds (Auto = 50ms) auto onOF On Off Output List Adjustable Range Default Setting hYS.
3.10 To Hide, Reveal and Promote Parameters ACCS Press PASS codE Press Edit Goto Press reached. until the Access List Heading is Press or to enter the password. The factory default is 1. ‘PASS’ will be displayed when the correct password has been entered. or to select ‘Edit’ level. Press Other options are: OPEr Operator level - shows selected parameters FuLL Reveals the ‘FULL’ set of parameters ConF Gives access to configuration level. Example: HidE 2FSH High alarm 2 has been selected.
3.10.1 The Pro (Promote) option 3.10.2 Returning to Operator level Up to twelve commonly used parameters can be ‘promoted’ into the HOME list. This will give the operator quick access to them by simply pressing the Repeat the above procedure for all the parameters you wish to hide, promote, or make read-only then return to operator level: button. This feature, used in combination with ‘hide’ and ‘ read only’, allows you to organise the way in which you want your controller formatted.
3.11 In reset To Use The Timer Press until you reach the SP list • Press until you reach the tM.OP parameter • or to select the timer operating Press mode, Opt.1 to Opt.5 as follows: • In reset, you can switch between automatic control and standby mode, using the parameter m-A in the HOME list. The controller is supplied with the m-A parameter hidden. You must first reveal it. See ‘To Hide, Reveal and Promote Parameters’. 3.11.1 Opt.
‘Automatic control’ means control at setpoint, with heating (and cooling) being applied. ‘Standby mode’ means: the controller is in manual with zero output power. See ‘Warning!’ in section 3.5. During Running The controller will always switch to automatic control. Heating (or cooling) will be applied and the temperature will rise (or cool) to the setpoint. When the temperature is within 1oC of setpoint, the timer will start counting down.
3.11.3 Opt.3 - Mode 3, Time from Cold and Switch Off Temperature 3.11.4 Opt.4 Mode 4, Time from Cold No Switch Off Temperature Setpoint Standby mode Setpoint Indefinite dwell at setpoint End flashes End flashes Reset Timing End This is the same as mode 1 except that the timer will start counting down immediately without waiting for the temperature to reach setpoint.
3.11.5 Opt.5 Mode 5, Delayed Switch On Temperature Setpoint Reset Indefinite dwell at setpoint Timing Reset This mode applies a time delay before turning on the heating (or cooling). When the timer is started, the controller will always switch to standby mode and start counting down. When the timer has timed out, the controller will switch into automatic control, apply heating (or cooling) and control indefinitely at the setpoint. Part Number HA026270 Issue 5.0 Aug 07 3.11.
3.12 To Start And Reset The Timer There are two methods: TIP: Promote tmr to the HOME list for quick access, as described in ‘To Hide, Revealing and Promote Parameters. Method 1. This is the simplest method to control the timer. until you reach the SP list • Press • Press until you reach the tMr parameter (time remaining). 1234 Tmr Press or to enter Press the required timing period in minutes. (0 to 9999). to return to the HOME display As soon as a value is entered into tmr timing will commence.
Method 2. Use this method if you want to set a fixed time and use the stat parameter to start and stop the timer. Press sp to reach the SP List heading. Press until you reach dwel 1234 dwel The stat parameter can also be switched between Off and run by configuring the logic I/O as a Off/run contact closure input. Open the external contact to select run. This is an edge triggered action. Close the contact to select Off. Off is forced whenever the contact is closed.
4. Configuring the Controller Select configuration level to change: •The type of control •The display units •The input sensor type• The scaling of linear inputs •The alarm configuration • The passwords. 4.1 ACCS To select configuration level Press to reach the Access List Heading. Press codE Press to step across the configuration list headings. inSt PASS Press or to enter the password. The factory default is 1. PASS will be displayed when the correct password has been entered.
4.1.1 Instrument Configuration inst unit Instr Conf Display units dEC.P Decimal places in display CtrL Control type Act Control action Options *C *F *K nonE nnnn nnn.n nn.nn Pid On.OF AL rEv dir Part Number HA026270 Issue 5.0 Description Centigrade Fahrenheit Kelvin None None One Two PID Control On/off Control Convert to an alarm unit Reverse (normal action for temperature control) Direct (output decreases as PV falls below SP) Aug 07 Inst Pd.
4.1.2 Input Configuration iP Sensor Input Options Meaning inPt Input type j.tc k.tc L.tc r.tc b.tc n.tc t.tc S.tc PL 2 rtd mV C.tc J thermocouple K thermocouple L thermocouple R thermocouple B thermocouple N thermocouple T thermocouple S thermocouple Platinell II CJC (TC only) 28 Cold junction compen sation 100Ω PRT Linear mV Custom input C=default Auto Automatic 0*C 0°C external ref. 45*C 45°C external ref. 50*C 50°C external ref. Linear input scaling (Range -12 to +80mV) InP.
4.1.3 Alarm Configuration The AL list configures the three internal ‘soft’ alarms and causes the appropriate alarm message to be flashed in the HOME display. At this stage the alarm is indication only (known as a ‘soft alarm’). To make the alarms operate the relay or logic outputs, follow the instructions under “Relay and Logic input/output Configuration.
4.1.4 Relay and Logic input/output Configuration Aa 1a The logic I/O can be configured as an output or a contact closure input for alarm acknowledge, keylock, or timer run/reset. Aa 1a id Relay Logic I/O Identity of output Func Function These functions only appear for the logic I/O diG.
Note 1: The last three letters will correspond to the alarm type configured in the AL list. If the alarm is disabled, AL1 or AL2 or AL3 will be shown. 5. Note 2: If tmg.3 and tmG.4 are selected, they illuminate the logic or relay output beacons, OP1 and OP2, without operating the actual output. They are used to indicate that timing is in progress while leaving the actual outputs to be operated by the other digital functions such as the END condition which can be used to operate an external klaxen. 6.
4.1.8 4.1.9 Passwords PASS Passwords Range Default ACC.P Full and Edit level password 0-9999 1 CnF.P Configuration level password 0-9999 2 CAL.P User calibration password 0-9999 3 32 Press To leave Configuration level to reach the ‘exit’ display Exit YES Press or to select ‘YES’ After 2 secs the display will blink and return to the HOME display in Operator level. Part Number HA026270 Issue 5.
4.1.10 Diagnostic Alarms In addition to the normal process alarms, the following diagnostics alarm messages are provided. Message Meaning and (Action) Message Meaning and (Action) EE.Er Electrically Erasable Memory Error: Err3 Error 3: Watchdog fail. (Return for repair) A parameter value has been corrupted. Contact Eurotherm Controls. HW.
4.2 User Calibration Your controller has been calibrated for life against known reference sources. User calibration allows you to apply offsets to compensate for sensor and other system errors. The parameter OFS in the IP list applies a fixed offset over the whole display range. You may also apply a 2-point calibration as follows: • Press until you reach the iP list • Press until you reach the CAL.P parameter • or to enter the password. The Press factory default is 3.
4.3 Automatic Tuning In PID control, the output from the controller is the sum of three terms: Proportional, Integral and Derivative. These three terms deliver just the right amount of power to hold the temperature at setpoint without oscillation. For stable control, the PID values must be ‘tuned’ to the characteristics of the process being controlled. In the 2132 and 2116 this is done automatically using advanced tuning techniques.
If the process cannot tolerate 100% heating or cooling during tuning, the power can be restricted by the heating and cooling limits in the Output list. However, the measured value must oscillate to some degree for the tuner to determine values. Tuning is normally performed only once during the initial commissioning of the process. However, if the process under control subsequently becomes unstable (because its characteristics have changed), you can retune again at any time.
4.3.3 Typical automatic tuning cycle Temperature 1. 2. 3. 4. Time 4.3.4 Calculation of the cutback values When low cutback or high cutback is set to ‘AuTo’ their values will be fixed at three times the proportional band, and will not be altered during automatic tuning. If set to any other value, they will be calculated as part of the tuning process. 4.4 Manual Tuning If for any reason automatic tuning gives unsatisfactory results, you can manually tune the controller. Proceed as follows: 5.
4.4.1 Setting the cutback values Temperature The above procedure sets up the parameters for optimum steady state control. If unacceptable levels of overshoot or undershoot occur during start-up or for large step changes in temperature, then manually set the cutback parameters Lcb and Hcb. Proceed as follows: 1. Set the low and high cutback settings to 3 x the proportional band (that is to say, Lcb = Hcb = 3 x PB). 2.
5. Ordering Code The controller is supplied configured according to the ordering code shown below. Model number Function Model Number 2132 1/16 DIN 2116 1/8 DIN CC NF TC TN VH VL Function PID controller On/Off controller PID controller + timer On/Off controller + timer XXX ENG FRA GER NED SPA SWE ITA Supply voltage Manual None English French German Dutch Spanish Swedish Italian Supply voltage 85-264Vac 20 -29Vdc or ac Part Number HA026270 Issue 5.
Sensor input Sensor input Setpoint min Display range and Setpoint min & max limits Thermocouples J Type J K Type K T Type T °C -210 to 1200 -200 to 1372 -200 to 400 L Type L -200 to 900 N Type N -200 to 1300 -50 to 1768 -50 to 1768 0 to 1820 0 to 1369 R S B P Type R Type S Type B Platinell II Resistance thermometer Z Pt100 -200 to 850 40 °F -340 to 2192 -325 to 2500 -325 to 750 -325 to 1650 -325 to 2370 58 to 3200 -58 to 3200 32 to 3308 32 to 2496 -325 to 1562 Setpoint max Units Ext re
6. Technical Specification Panel sealing IP65 (EN 60529), or 4X (NEMA 250) Operating ambient 0 to 55oC. Ensure that the enclosure is adequately ventilated. 5 to 95%RH, non condensing Storage temperature -30oC to +75oC. (Protect from humidity and dust) Atmosphere Not suitable for use above 2000m or in explosive or corrosive atmospheres Power supply High voltage unit: 100 to 240Vac -15%, +10%, 48-62Hz, 5Watts maximum consumption Low voltage unit: 24Vdc/ac +/- 20%.
7. Safety and EMC Information This controller is intended for industrial temperature and process control applications when it will meet the requirements of the European Directives on Safety and EMC. Use in other applications, or failure to observe the installation instructions of this handbook may impair safety or EMC. The installer must ensure the safety and EMC of any particular installation.
precaution may damage the indicator or cause some discomfort to the user. Electrostatic discharge precautions When the controller is removed from its sleeve, it is vulnerable to damage by electrostatic discharge from someone handling the controller. To avoid this, before handling the unplugged controller discharge yourself to ground. Cleaning Do not use water or water based products to clean labels or they will become illegible. Isopropyl alcohol may be used to clean labels.
IEE wiring regulations (BS7671) and in USA use NEC Class 1 wiring methods. Power Isolation The installation must include a power isolating switch or circuit breaker. This device should be in close proximity to the controller, within easy reach of the operator and marked as the disconnecting device for the instrument.
Reasons why the heating might remain constantly on include: • the temperature sensor becoming detached from the process • thermocouple wiring becoming short circuit; • the controller failing with its heating output constantly on • an external valve or contactor sticking in the heating condition • The controller setpoint too high Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit, with an independent temperature sensor, which will isolate the heating circuit.
8.