6. Error Codes
The error codes are depicted by a number of flashes by the error light in a sequence every
four seconds.
Code
Reason / Solution
ERR1 or ERR2 (On Display
instead on temperature)
Faulty temperature probe
- Please call Evakool for closest service centre.
1 Flash Low Voltage
- Please check the source voltage to ensure it is above
the cut out. Try lowering the voltage cut out setting to
LO.
- The vehicle cabling may be inadequate or unsuitable,
please refer to cable specifications table for correct
cable thickness.
- Try the refrigerator on a different power source.
2 Flashes Fan or compressor running issue
- Fan is drawing too many Amps (Over 1 Amp) –
Replace Fan.
- The compressor is drawing too many amps (Over 12
Amps)
- Possible Electronic Box or compressor fault – contact
Evakool or Service Agent
3 Flashes The compressor speed is too low
- Reduce products / items inside unit
- Move unit to a lower ambient temperature
- Clean vents / ensure clear air flow over compressor
4 Flashes Ambient Temperature too high
- Clean vents / ensure clear air flow
- Fan Fault – Replace fan