Important parameters:
MCPS: Installer menu General parameters Aux1 Circuit
MCPS: Installer Menu General parameters pumps alarm CFG AUX1 pump
MCPS: Maintenance Menu Aux1 Management Setpoint
MCPS: Maintenance Menu Aux1 Management Hysteresis
MCPS: Maintenance Menu Aux1 Management Probe offset
MCPS: Maintenance Menu Aux1 Management Mode
9.5.5 Control of the high and low temperature of the auxiliary circuit AUX1
(MCPS module)
Whenever the temperature of the AUX1 auxiliary circuit water exceeds or drops below the
minimum and maximum temperature values accepted for the system of the hysteresis value, then
the c-pro micro MCPS solar panels regulator will start special management cycles for these
emergencies:
- High temperature protection: the high temperature protection intervention will trigger a
simple signal to the maintenance staff.
- Low temperature protection: the low temperature protection will trigger the activation of the
circulation pump of the auxiliary circuit in order to ease heating of the circuit water. The
pump will remain on until the minimum temperature conditions are recovered.
Important parameters:
MCPS: Maintenance Menu Aux1 Management HT setpoint
MCPS: Maintenance Menu Aux1 Management HT hyst.
MCPS: Maintenance Menu Aux1 Management LT setpoint
MCPS: Maintenance Menu Aux1 Management LT hyst.
9.5.6 Management and setting of the periodic antilegionella cycle for the DHW
tank (MCPS module)
In order to disinfect the DHW tank from the proliferation of legionella bacteria due to the deposit of
DHW, the c-pro CLIMA system envisions the periodic management of anti-legionella cycles.
Depending on the type of system, it is possible to select daily, weekly or monthly antilegionella
cycles.
An anti-legionella cycle consists in taking, the temperature of the DHW tank to a temperature such
to destroy bacteria (standard to 70°C, but which can be set from parameter) for a long enough
period of time (standard at 60 minutes, but can be set from parameter) by activation of the boiler
and the DHW circulation pump.
These periodic cycles will help with respect to the Standards in force on the subject.
Important parameters:
MCPS: Maintenance Menu General parameters Antilegionella Enable
MCPS: Maintenance Menu General parameters Antilegionella Mode
MCPS: Maintenance Menu General parameters Antilegionella Start hour
MCPS: Maintenance Menu General parameters Antilegionella Day week
MCPS: Maintenance Menu General parameters Antilegionella Day month
MCPS: Maintenance Menu General parameters Antilegionella Setpoint
MCPS: Maintenance Menu General parameters Antilegionella Duration