Manual

C-PRO KILO AHU APPLICATION MANUAL
Pag. 32
activate
PM80 Calibration of the ambient air temperature probe 0.0 -10.0 10.0 °C MA-IO
PM81 Calibration of the delivery air temperature probe
0.0 -10.0 10.0 °C MA-IO
PM82 Calibration of the external air temperature probe 0.0 -10.0 10.0 °C MA-IO
PM83 Calibration of the ambient humidity probe 0 -10 10 °C MA-IO
PM84
Calibration of the air temperature expulsion
probe
0.0 -10.0 10.0 °C MA-IO
PM85 Calibration of the anti-freeze temperature probe 0.0 -10.0 10.0 °C MA-IO
PM87
Calibration of the pre-heating air temperature
probe
0.0 -10.0 10.0 °C MA-IO
PM88 Calibration of the air quality probe (CO2/VOC) 0 -100 100 ppm MA-IO
PM89 Calibration of the external air humity probe 0 -10 10 % MA-IO
PSd2 Password Maintenance Operator Level (2) 0 -999 9999 - MA
Level
3
INSTALLATION OPERATOR MENU
REGULATION
PC01 Enable compensation Set Point summer NO (0) NO (0) YES (1) - IS-R
PC02 Set Point maximum for summer compensation 28.0 SEtC PH04 °C IS-R
PC03
Set Point (on external t.) from begining
compensation
26.0 PH03 PH04 °C IS-R
PC04
Differential for the summer compensation of Set
Point
4.0 0.0 20.0 °C IS-R
PC05
Enable cycles for air quality sensors for ambient
temperature (when probe is restarting)
NO (0) NO (0) YES (1) - IS-R
PC06
Wait time prior to fan activation for air quality
sensors
6 1 99 Min IS-R
PC07 Fan activation time for air quality sensors 2 1 30 Min IS-R
PC08
Activate both fans for air quality sensors
0 : NO – Only activate pickup fan
1 : YES – Activate both fans
NO (0) NO (0) YES (1) - IS-R
Only with
PG05=1
FANS
PF01
Types of regulations for fans:
0: Continuous Regulation
1: On/Off Regulation
2: Module Regulation
3: Module Regulation with steps to enable
On/Off
1
Continuo
us (0)
Inverter+
OnOff
(3)
- IS-F
PF02 Differentials for fan regulation 5.0 0.0 30.0 °C IS-F
PF03
Minimum speed for the regulation of fan
modules
0.0 0.0 PF04 % IS-F
PF04
Maximum speed for the regulation of fan
modules
100.0 PF03 100.0 % IS-F
PF05
Minimum time between the startup of pickup
and delivery fans.
20 0 999 Sec IS-F
PF08
Differentials of On/Off steps on ramp of
regulation of fan modules
8.0 PF03 60.0 % IS-F
Only if
PF01=3
PF09
Wait time (on and off) of On/Off steps on ramp
of regulation of fan modules
10 0 999 Sec IS-F
Only if
PF01=3
PF10
Pickup and delivery fan speed in ambient probe
alarm
30.0 0.0 100.0 % IS-F
If fans
On/Off set
PF10 > 0 to
activate in
probe error
COILS
Pb01
Proportional band for regulation of valves
(cooling/heating)
10.0 0.0 20.0 °C IS-B
Pb02
Integral time for regulation of valves
(cooling/heating)
0 0 999 Sec IS-B
If Pb02=0
integral action