6.2.5 Unit with 2 coils without dehumidification (PG00=5)
The MOdE parameter starts while set by default on WINTER.
This unit provides the utilization of the expansion (PG02=1).
The regulation of the fans starts while on its default setting on the inverter with On/Off
(PF01=3).
The number of coils is PG01=2; the post-heating is managed by the resistance PG14=3.
The dehumidification is disabled PG12=0.
The regulation of the shutter is enabled for free-cooling/free-heating (PG07=1, PS01=1).
The recuperator utilized is that which is at cross flow PG13=1.
PIN ANALOGUE INPUTS
AI1 Ambient air temperature probe (NTC)
AI2 Delivery air temperature probe (NTC)
AI3 External air temperature (NTC)
AI4 Ambient humidity probe (4..20 mA)
AI5 Expulsion air temperature probe (NTC)
AI6 Anti-freeze temperature probe (NTC)
AI7 Not utilized
AI8 Preheating air temperature probe (NTC)
AI9 Air quality probe CO2/VOC (4..20 mA)
AI10 External humidity probe (4..20 mA)
PIN DIGITIAL INPUTS
DI1 On/Off remote
DI2 Summer/winter remote commutation
DI3 Thermal delivery fans
DI4 Dirty pressure switch recuperator
DI5 Pressure switch air filter
DI6 Airflow meter
DI7 Thermal pickup fan
DI8 Humidifier alarm
DI9 Inverter delivery fan alarm
DI10 Inverter pickup fan alarm
DI11 Heating pump alarm
DI12 Cooling pump alarm
DI13 Fire/smoke alarm
DI14 Not utilized
PIN ANALOGUE OUTPUTS
AO 1 Not utilized
AO 2 Heating valve command (0-10V)
AO 3 Cooling valve command (0-10V)
AO 4 Not utilized
AO 5 Fans inverter command (0-10V)
AO 6 Modulating humidifier command (0-10V)