Manual
C-PRO KILO AHU APPLICATION MANUAL
Pag. 86
1293
Status_AirExtShutter 0 0 6
0=Disabilitato,
1=OFF,
2=Opening,
3=ON,
4=Closing,
5=ALL,
6=Allineamento
R/W
1294
Position_AirShutter 0.00 0.00 100.00 0% -100.00% R/W
1537
PT01_Start_NightTB ( Low ) 0 0 86399 R/W
1538
PT01_Start_NightTB ( High )
1539
PT02_End_NightTB ( Low ) 0 0 86399 R/W
1540
PT02_End_NightTB ( High )
1541
PT03_OffsetSetPoint_Night 0.0 -20.0 68.0 R/W
1542
MOdE_SummerWinterMode 1 0 1
0=Estate
(Cooling),
1=Inverno
(Heating)
R/W
1543
SEtC_SummerSetPoint 24.0 -15.0 158.0 R/W
1544
SEtH_WinterSetPoint 20.0 -15.0 158.0
Winter Set Point
or Set Point
unique(if selected
by PH27)
R/W
1545
PU01_Humidifier_SetPoint 55 0 100 R/W
1546
OS01_OffsetSetPoint_DI 0.0 -20.0 68.0 R/W
1547
OS02_OffsetSetPoint_SUP 0.0 -20.0 68.0 R/W
1548
PM00_Limit_HourFan ( Low ) 20000 0 100000 ore x 10 R/W
1549
PM00_Limit_HourFan ( High )
1550
PM01_SupplyFan_Hours ( Low ) 0 0 100000 R/W
1551
PM01_SupplyFan_Hours ( High )
1552
PM02_ReturnFan_Hours ( Low ) 0 0 100000 R/W
1553
PM02_ReturnFan_Hours ( High )
1554
PM10_Limit_HourPump ( Low ) 20000 0 100000 ore x 10 R/W
1555
PM10_Limit_HourPump ( High )
1556
PM11_Pump_Hours ( Low ) 0 0 100000 R/W
1557
PM11_Pump_Hours ( High )
1558
PM20_EnManual_SupplyFan 0 0 1 R/W
1559
PM21_ForceSuppyFan 0.00 0.00 100.00 R/W
1560
PM23_EnManual_ReturnFan 0 0 1 R/W
1561
PM24_ForceReturnFan 0.00 0.00 100.00 R/W