Manual

C-PRO KILO AHU APPLICATION MANUAL
Pag. 87
1562
PM26_EnManualHumidifier 0 0 1 R/W
1563
PM27_ForceHumidifier 0 0 100 R/W
1564
PM80_Calibration_EnvironmentProbe 0.0 -9.9 50.0 R/W
1565
PM81_Calibration_AirSupplyProbe 0.0 -9.9 50.0 R/W
1566
PM82_Calibration_AirExternalProbe 0.0 -9.9 50.0 R/W
1567
PM83_Calibration_HumidityEnvironment_Probe 0 -9 9 R/W
1568
PM84_Calibration_AirSupplyPressure_Probe 0.0 -14.5 14.5 R/W
1569
PM90_LastMaintainDATE ( Low ) 252460801
2524608
01
214748364
7
R/W
1570
PM90_LastMaintainDATE ( High )
1571
PC01_EnableSetPointCompensation 0 0 1 R/W
1572
PC02_MaxSetPoint_Compensation 28.0 -15.0 158.0 R/W
1573
PC03_SetPointExternal_StartCompensation 26.0 -15.0 158.0 R/W
1574
PC04_OffsetSetPointExternal_Compensation 4.0 0.0 68.0 R/W
1575
PC05_Enable_SniffingMode 0 0 1 R/W
1576
PC06_WaitTime_SniffingCycle 6 1 99 Minute R/W
1577
PC07_ActiveTime_SniffingCycle 2 1 30 Minute R/W
1578
PC08_EnableBothFans_onSniffing 0 0 1 R/W
1579
PF01_FanRegulationType 1 0 3
0=Continue,
1=On/Off,
2=Inverter,
3=Inverter+On/O
ff
R/W
1580
PF02_FanRegulation_Diff 5.0 0.0 86.0 R/W
1581
PF03_MinSpeedFan 0.00 0.00 100.00 R/W
1582
PF04_MaxSpeedFan 100.00 0.00 100.00 R/W
1583
PF05_Fan_TonOther 20 0 999 R/W
1584
PF08_FanRegulation_InverterOnOff_Diff 2.00 0.00 60.00 R/W
1585
PF09_FanRegulation_InverterOnOff_Time 10 0 999 R/W
1586
PF10_ForceOnErrorProbe 30.00 0.00 100.00 R/W
1587
PV01_Valve_BP 10.0 0.0 86.0 R/W
1588
PV02_Valve_Ti 0 0 999 R/W
1589
PV05_Offset_ValveSupplySetPoint 0.0 0.0 50.0 R/W
1590
PV06_Diff_ValveSupplySetPoint 5.0 0.0 68.0 R/W
1591
PV10_ForceValve_OnErrorProbe 30.00 0.00 100.00 R/W
1592
PS01_TypeRegulation_AirExternalShutter 0 0 1 0=Moduling, R/W