C-PRO KILO AHU APPLICATION MANUAL
Pag. 88
1=FixedOpen
1593
PS02_SetWinterMinLimit_AirExternalShutter 14.0 -15.0 158.0 R/W
1594
PS03_SetSummerMaxLimit_AirExternalShutter 28.0 -15.0 158.0 R/W
1595
PS04_Diff_AirExternalShutter 8.0 0.0 86.0 R/W
1596
PS05_MinRegulationValue_AirExternalShutter 0.00 0.00 100.00 R/W
1597
PS06_MaxRegulationValue_AirExternalShutter 100.00 0.00 100.00 R/W
1598
PS07_RunningTime_AirExternalShutter 120 0 3600 Sec R/W
1599
PS08_EndRunMaximumSignalTime_AirExternalShutte
r
5 0 600 R/W
1600
PS09_MinVariation_AirExternalShutter 0.00 0.00 90.00 % R/W
1601
PS10_FixRegulationValue_AirExternalShutter 50.00 0.00 100.00 R/W
1602
PS11_DiffHeating_AirExternalShutter 2.0 0.0 86.0 R/W
1603
PP01_PumpRegulation 0 0 1 R/W
1604
PP02_SetON_Pump 5.00 1.00 90.00 R/W
1605
PP03_SetOFF_Pump 2.00 1.00 90.00 R/W
1606
PP04_TimeOFF_Pump 10 1 99 Minute R/W
1607
PU02_TypeRegulation_Humidifier 0 0 1 0=DO, 1=AO R/W
1608
PU03_Humidifier_Diff 10 0 100 R/W
1609
PU10_tSupply_EnableHumidifier_Enable 1 0 1 R/W
1610
PU11_tSupply_EnableHumidifier_Set 22.0 -15.0 158.0 R/W
1611
PU12_tSupply_EnableHumidifier_Diff 3.0 0.0 68.0 R/W
1612
PA01_En_Alarm_HourFan 1 0 1 R/W
1613
PA02_En_Alarm_HourPump 0 0 1 R/W
1614
PA03_AlarmHours_alarmDO 1 0 1 R/W
1615
PA04_AlarmProbe_Delay 10 0 240 R/W
1616
PA05_AlarmProbe_alarmDO 1 0 1 R/W
1617
PA08_AlarmSupplyFan_alarmDO 1 0 1 R/W
1618
PA09_AlarmReturnFan_alarmDO 1 0 1 R/W
1619
PA10_ThermalFan_Delay 2 0 999 R/W
1620
PA11_InverterAlarmFan_Delay 2 0 999 R/W
1621
PA15_ThermalPump_Delay 2 0 999 R/W
1622
PA16_AlarmPump_alarmDO 1 0 1 R/W
1623
PA24_ResetType_AlarmAirFilterSwitch 1 0 1 R/W
1624
PA25_AlarmAirFilterSwitch_Delay 30 0 999 R/W