C-PRO KILO AHU APPLICATION MANUAL
Pag. 90
1658
PH28_EnableNightTimeBand 0 0 1 R/W
1659
PH32_TemperatureUM 0 0 1 R/W
1660
PH33_Press_UM 0 0 1 0=Bar, 1=psi R/W
1661
PH40_EnableExternalProbe 0 0 1 R/W
1662
PH41_EnableHumidityEnvironmentProbe 0 0 1 R/W
1663
PH42_EnableAirPressureSupplyProbe 0 0 1 R/W
1664
PH50_Logic_DI_OnOff_SP_Mode_Remote 0 0 1 R/W
1665
PH51_Logic_DI_Alarm 0 0 1 R/W
1666
PH52_Logic_DI_AlarmAirflow 1 0 1 R/W
1667
PH53_Logic_DI_AlarmFire 1 0 1 R/W
1668
PH60_Logic_DO_Alarm 0 0 1 R/W
1669
PG00_UnitType 1 1 3
1=Only Heat,
2=Only Cool,
3=Heat/Cool +
Humidity
R/W
1670
PG03_EnableRTC 1 0 1 R/W
1671
PG04_PrimaryRegulation 1 0 1 0=Fan, 1=Valve R/W
1672
PG05_RegProbe_Return 0 0 1 R/W
1673
PG06_EnableHumidifier 0 0 1 R/W
1674
PG07_EnableAirExternalShutter 1 0 1 R/W
1675
PG08_EnableSupplyFan 1 0 1 R/W
1676
PG09_EnableReturnFan 1 0 1 R/W
1677
PG10_EnablePump 0 0 1 R/W
1678
Hd01_PosDI_OnOffRemote 1 0 7 R/W
1679
Hd02_PosDI_ChangeModeRemote 0 0 7 R/W
1680
Hd03_PosDI_SetPointRemote 0 0 7 R/W
1681
Hd05_PosDI_ThermalSupplyFan 3 0 7 R/W
1682
Hd06_PosDI_AlarmInverterSupplyFan 0 0 7 R/W
1683
Hd07_PosDI_ThermalReturnFan 0 0 7 R/W
1684
Hd08_PosDI_AlarmInverterReturnFan 0 0 7 R/W
1685
Hd10_PosDI_ThermalPump 0 0 7 R/W
1686
Hd15_PosDI_AlarmHumidifier 0 0 7 R/W
1687
Hd16_PosDI_AlarmAirflowSwitch 6 0 7 R/W
1688
Hd17_PosDI_AntiFreeze 5 0 7 R/W
1689
Hd18_PosDI_AlarmAirFilterSwitch 4 0 7 R/W