PROGRAMMABLE CONTROLLERS FOR SINGLE CIRCUIT, DUAL CIRCUIT AND TRIPLE CIRCUIT COMPRESSOR PACKS UP TO 8/12 COMPRESSORS APPLICATION MANUAL CODE 144RACKMGE04
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Important Please read these instructions carefully prior to installation and use, and follow all the precautions for installation and electrical connections; keep these instructions with the device for future consultation. The device must be disposed of in accordance with local regulations pertaining to the collection of electrical and electronic appliances.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Table of contents 1 2 3 4 5 6 GENERAL INFORMATION ......................................................................................................5 1.1 Description ............................................................................................................................5 APPLICATIONS .........................................................................................................................8 2.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6.4.8 Inverter configuration ..................................................................................................82 6.4.9 Compressors of different nominal power.....................................................................83 6.4.10 Suction line loss of load compensation........................................................................84 6.4.11 Refrigeration power incrementing at high pressures ..................................
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1 GENERAL INFORMATION 1.1 Description This application uses C-PRO MEGA and C-PRO GIGA controllers to manage a compressor packs composed of one, two or three circuits with a maximum number of 8 compressors (if using C-PRO MEGA controllers) or 12 compressors (if using C-PRO GIGA controllers).
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL C-PRO MEGA Page 6
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL C-PRO GIGA Page 7
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2 APPLICATIONS Using the CAN protocol, it is possible to connect an 8 relay (C-PRO EXP MEGA) or 13 relay (C-PRO EXP GIGA) expansion module to the controllers. Management of four different types of control unit is envisaged: 1) Application 1: C-PRO MEGA RACK (for single circuit control units; C-PRO MEGA RACK preset configuration) Total No. of digital outputs = 8 Total No. of digital inputs = 10 Total No. of analogue inputs = 8 Total No.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.1 Application 1: use of the C-PRO MEGA RACK (single circuit control unit) As a preset configuration, the C-PRO MEGA RACK is configured to manage single circuit compressor packs; the services mentioned in the figure below refer specifically to the preset configurations.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.2 Application 2: use of the C-PRO GIGA RACK (dual circuit control unit with separate condensation) The C-PRO GIGA RACK is pre-configured to control dual circuit compressor packs; the services mentioned in the figure below refer precisely to the preset configurations. Compressors 1 and 2 (and related load increments) appertain to circuit 1; compressors 3 and 4 (and related load increments) appertain to circuit 2.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.3 Application 3: use of the C-PRO MEGA RACK with the C-PRO EXP MEGA I/O expansion unit (dual circuit control unit with separate condensation) The C-PRO MEGA RACK is pre-configured to control single circuit compressor packs; the services mentioned in the figure below refer to an example of a dual circuit control unit with separate condensation. Compressors 1, 2 and 3 appertain to circuit 1; compressors 4, 5 and 6 appertain to circuit 2.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.4 Application 4: use of the C-PRO GIGA RACK with the C-PRO EXP GIGA I/O expansion unit (dual circuit control unit with separate condensation) The C-PRO GIGA RACK is factory pre-configured to control dual circuit compressor packs; the services mentioned in the figure below refer to an example of a dual circuit control unit with separate condenser, where the controller is used with an I/O expansion unit.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.5 Controller electrical connections The layout relating to the controllers electrical connections is shown below, with tables listing the meanings of the inputs and outputs. 2.5.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.5.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.5.3 Input and output identification tables Card with 12 VDC + 12 VDC dual power supplies Conn. Abbre Description v. C1-1 C1-2 VCC GND main card power supply input (+13 VDC) main power supply reference JA-1 JA-2 JA-3 VDC AI 1 GND active probe power supply (*1) No.1 universal analogue input (NTC, PTC, 0..5V, 0..10V, 0..20 mA, 4..20 mA) analogue input common ground JB-1 JB-2 JB-3 VDC AI 2 GND active probe power supply (*1) No.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Conn. Abbre Description v. JK-3 JK-4 JK-5 JK-6 COM 4 NO 4 COM 5 NO 5 relay No. 4 common connection relay No. 4 contact normally open relay No. 5 common connection relay No. 5 contact normally open JL-1 JL-2 JL-3 JL-4 JL-5 JL-6 COM 6 NO 6 COM 7 NO 7 COM 8 NO 8 relay No. 6 common connection relay No. 6 contact normally open relay No. 7 common connection relay No. 7 contact normally open relay No. 8 common connection relay No.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Other connectors (not present on the C-PRO MEGA RACK controller) Abbre Description v. Conn. JN-1 JN-2 JN-3 NC 9 COM 9 NO 9 relay No. 9 contact normally closed relay No. 9 common connection relay No. 9 contact normally open JO-1 JO-2 JO-3 NC 10 relay No. 10 contact normally closed COM10 relay No. 10 common connection NO 10 relay No. 10 contact normally open JP-1 JP-2 JP-3 JP-4 JP-5 JP-6 COM11 NO 11 COM12 NO 12 COM13 NO 13 JQ-1 JQ-2 JQ-3 DI11 No.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL JMP3 Jumper not inserted Jumper inserted JMP4 CAN terminator Termination (120?) not inserted Termination (120?) inserted Local CAN serial port baud rate selection A Jumper A inserted Jumper B inserted Baud rate = 20K B A Jumper A inserted Jumper B not inserted Baud rate = 50K B A Jumper A not inserted Jumper B inserted Baud rate = 125K B A Jumper A not inserted Jumper B not inserted Baud rate = 500K B JMP5 Jumper not inserted Jumper inserted
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.6 Preset configurations The controller preset configurations are reported below. 2.6.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.6.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.7 I/O expansion unit electrical connections The layout relating to the expansion unit electrical connections is shown below, with tables listing the meanings of the inputs and outputs. 2.7.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.7.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2.7.3 Input and output identification tables Card with 12 VDC power supply Conn. Abbre Description v. C1-1 C1-2 VCC GND card power supply input (+13 V DC) power supply reference JD-1 JD-2 JD-3 JD-4 JD-5 JD-6 VDC AI1 AI2 AI3 AI4 GND active probe power supply (*1) No.1 configurable analogue input (NTC, 0..20 mA, 4..20 mA) No.2 configurable analogue input (NTC, 0..20 mA, 4..20 mA) No.3 configurable analogue input (NTC, 0..20 mA, 4..20 mA) No.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL * VDC=12.5 V Imax = 200 mA (as the sum of the current values for all VDC terminals). Card with 24 V AC/DC power supply Conn. CA-1 CA-2 Abbre Description v. VCC VCC card power supply input (24 VAC/DC) card power supply input (24 VAC/DC) Other connectors (not present on the C-PRO EXP MEGA expansion unit) Conn. Abbre Description v. JN-1 JN-2 JN-3 NC 9 COM 9 NO 9 relay No. 9 contact normally closed relay No. 9 common connection relay No.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL configuration) by simply connecting the network components. For further information please refer to the chapter “CAN connection” in the Hardware Manual.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 3 COMPONENT NETWORK AND ACCESSORIES 3.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 4 USER INTERFACE 4.1 Display and keypad For the application there is an interface integrated with the controller (hereinafter referred to as “built-in”). It has a 4x20 character alphanumeric display, offer a range of keys for navigation/editing pages and several LEDs for viewing certain associated events.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL There are also 3 LEDs: - L0 associated with the K0 key, identifies whether there are any alarms. Off: there are no alarms. Flashing slowly: indicates the presence of new alarms Flashing rapidly: indicates that alarm pages are being viewed. On: all active alarms have been viewed - L2 time bands: associated with the K2 key, identifies the status of the RTC and the Off: no signals. Flashing rapidly: indicates there is an ERTC clock alarm.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Password Each menu (besides the clock menu which is always accessible) is associated with a level which affects accessibility. Each level also has an associated password allowing access to the various functions present in that specific menu. Once the correct password has been entered, the protected functions will be accessible.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL The first page for each circuit: Stato circuito Set Point e Valore delle sonde di pressione Funzioni attive su circuito contains information on the circuit’s current status and active functions: hp: tC: dC: sC: tF dF: sF: refrigeration power increments Compressor time band function Compressor set point variation from a digital input Compressor set point variation by supervisor system Fan time band function Fan set point variation from a digital input F
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL not yet visible on the page itself. In this specific case, once the screen highlight is on the third circuit line, pressing DOWN moves the display to the next screen: Service menu The user menu is a level 2 menu, i.e. it is necessary to insert the service level password, or higher, in order to be able to view/modify the parameters in this branch.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL In the REGULATION menu it is possible to set/view the parameters relating to the side band and neutral zone thermoregulations for compressors, fans and any inverters, for each circuit: ⋅ type of regulation ⋅ setpoints ⋅ differentials ⋅ times ⋅ offsets In the COMPRESSORS and FANS menu it is possible to set the parameters pertaining to device management: ⋅ power of the individual compressors (if used) ⋅ type of rotation ⋅ increment logic ⋅ times ⋅ floating
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL The SYSTEM menu contains a system configuration “Wizard” for configuring a number of circuits, activating unique condensation, the use of inverters, the number of compressors and increments, the number of fans, the number of safety devices to be used and the use of any expansion units. A page summarising the relays and selected digital inputs is presented for configuration purposes, indicating whether an expansion unit should be used, if selected.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 4.3 Conditioned visibility Conditioned visibility allows hiding certain parameters and status information on the basis of the configuration of certain parameters. For example, by setting neutral zone type regulation, the side band regulation parameters will be automatically hidden when viewing the pages, or, even more importantly, by setting a single circuit machine, all the parameters for the second and third circuit will no longer be visible.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 5 CONFIGURATION PARAMETERS All the parameters managed by the application are listed below. For each parameter there is also a brief description, the range of values admissible, the units of measurement, the recommended default value and the menu in which it may be found.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PT71..74 PT81..84 Circuit 1 Fan time band offset (1..4) Circuit 2 Fan time band offset (1..4) Circuit 3 time bands. Circuit 1 Sets the offsets to the fan setpoints in relation to the 4 time bands. Circuit 2 Sets the offsets to the fan setpoints in relation to the 4 time bands. Circuit 3 0.0 PF32 PF33 Bar OR 0.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PUF2 PUF5 SPF3 PUF3 PUF6 PSd1 Fan secondary setpoint offset Circuit 2 Fan sup. secondary setpoint offset Circuit 2 Sets the offset value for use of secondary setpoint from fan digital input 0.0 -20.0 20.0 Bar UT Visible if PG01 > 1 and PG30 = 0 Sets the offset value for use of secondary setpoint from fan supervisor 0.0 -20.0 20.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PM21..30 Compressor forcing (1..10) PM33 PM34 Enable compressor (11-12) PM35 PM36 Compressor forcing (11-12) PM37 Comp. inverter forcing Circuit 1 PM38 Comp. inverter forcing Circuit 2 PM39 Comp. inverter forcing Circuit 3 PM51..60 Enable fan (1..10) PM61..70 Fan forcing (1..
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Suction probe 3 calibration Supply probe 1 calibration Circuit 3 suction probe calibration Circuit 1 supply probe calibration PM85 Supply probe 2 calibration PM86 PM83 PM84 PM87 PM88 0.0 -9.9 9.9 Bar MA-IO 0.0 -9.9 9.9 Bar MA-IO Circuit 2 supply probe calibration 0.0 -9.9 9.9 Bar MA-IO Supply probe 3 calibration Circuit 3 supply probe calibration 0.0 -9.9 9.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PC26 PC27 PC28 PC32 PC33 PC34 PC36 PC37 offset. Circuit 1 Inverter comp. min. Circuit 1 Inverter comp. speedup Circuit 1 PC44 PC45 PC46 PC47 PC48 % IS-RC Visible if PG12 =1 0 0 999 Sec IS-RC Visible if PG12 =1 10 0 999 Sec IS-RC Visible if PG12 =1 0.1 PH01 SPC2 Bar IS-RC Visible if PG01 >1 2.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Circuit 2 PC52 PC53 PC54 PC56 PC57 Compressor min. setpoint Circuit 3 Compressor max. setpoint Circuit 3 Compressor regulation Circuit 3 Compressor integral time Circuit 3 Compressor proportional band. Circuit 3 PC58 Comp. zone Circuit 3 PC59 Comp. zone differential Circuit 3 the minimum value to the maximum value ( circuit 2 neutral zone reg.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Compressor TOnMin Circuit 3 Compressor TOnMax Circuit 3 Compressor TOffMin Circuit 3 Compressor TOffMax Circuit 3 Comp. inverter diff. Circuit 3 Compressor inverter SP offset. Circuit 3 Minimum insertion time for subsequent compressor step ( circuit 3 neutral zone reg.) Maximum insertion time for subsequent compressor step ( circuit 3 neutral zone reg.) Minimum release time for subsequent compressor step ( circuit 3 neutral zone reg.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PC04 TMinOn PC05 TMinOff PC06 TOnOn PC07 TOnOther PC08 TOffOther PC09 TOnParz PC10 TOffParz PC11 Comp. probe error Circuit 1 PC31 Comp. probe error Circuit 2 PC51 Comp.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PC73 PC74 PC75 PC76 PC78 HP prevention C3 limit SP HP prevention differential HP prevention hold time HP prevention percentage Side band step overlap Set compressor increment pressure (circuit 3) Comp. increment pressure differential Minimum comp. increment hold time 22.0 PH03 PH04 Bar IS-C 4.0 0.1 10.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PF13 Fan max, setpoint Circuit 1 PF14 Fan regulation Circuit 1 PF16 Fan integral time Circuit 1 PF17 Fan proportional band. Circuit 1 PF18 Fan zone Circuit 1 PF20 Fan TOn/TOff Circuit 1 PF24 PF25 PF26 PF27 Fan inverter differential Circuit 1 Fan inverter SP offset.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PF38 Fan zone Circuit 2 Zone value for neutral zone regulation of circuit 2 fans 1.0 0 20.0 Bar IS-RF PF40 Fan TOn/TOff Circuit 2 Next fan insertion/release time ( circuit 2 neutral zone reg.) 10 0 999 Sec IS-RF PF44 Fan inverter differential Circuit 2 Differential for fan regulation with circuit 2 inverter 0.5 0.0 20.0 Bar IS-RF PF45 Fan inverter SP offset.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PF64 Fan inverter minimum Circuit 3 Differential for fan regulation with circuit 3 inverter 0.5 0.0 20.0 Bar IS-RF PF65 Fan inverter SP offset. Circuit 3 Suction setpoint offset for circuit 3 inverter regulation of the fan. 0.0 -20.0 20.0 Bar IS-RF PF66 Fan inverter minimum Circuit 3 Minimum fan value with circuit 3 inverter 0.0 0.0 100.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PF72 PF73 PF74 PF78 PH01 PH02 PH03 PH04 Floating condensation offset Set floating condensation min. Set floating condensation max.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PH12 Modbus baud rate PH13 Modbus parity PH14 Modbus stop bit PH15 Restore default parameters PH20 Compressors inverter consent logic PH21 Fans inverter consent logic PH23 Enable environment temp. probe PH24 Enable external temp.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL compensation line (neutral zone) 0: NO 1: YES Page 50
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PH36 Suction load compensation offset PH40 Measurement unit PH43 AI1 probe type PH44 PH45 PH47 PH53 PSd3 AI2 probe type AI3_4 probe type AI5_6 probe type Buzzer enable Installer PSd Load loss compensation factor Sets the display for temperature or pressure 0: Pressure 1: Temperature Sets the type of AI01 analogue input: 2: NTC 3: 0-20mA 4: 4-20mA Sets the type of AI02 analogue input: 2: NTC 3: 0-20mA 4: 4-20mA Sets analogue input type for AI
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PA01 PA02 Enable compressor operation time alarm Enable fan operation time alarm Enables the alarm pertaining to compressor operation times NO NO (0) YES (1) IS-S Enables the alarm pertaining to fan operation times NO NO (0) YES (1) IS-S PA03 HP suction alarm delay Sets the suction high pressure alarm activation delay 30 0 999 Sec IS-S PA04 ExPro alarm delay Sets the expansion unit alarm activation delay 1 0 999 Sec IS-S Flui
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL alarm diff. Circuit 2 suction HP alarm setpoint . C2 suction HP alarm diff. pressure alarm differential PA29 >1 Circuit 2 suction probe high pressure alarm setpoint 4.0 PA25 PH02 Bar IS-S Circuit 2 suction probe high pressure alarm differential 0.5 0.0 20.0 Bar IS-S C2 supply LP alarm setpoint Circuit 2 supply probe low pressure alarm setpoint 2.0 PH03 PA31 Bar IS-S PA30 C2 supply LP alarm diff.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PA39 C3 supply LP alarm setpoint Circuit 3 supply probe low pressure alarm setpoint 2.0 PH03 PA41 Bar IS-S PA40 C3 supply LP alarm diff. Circuit 3 supply probe low pressure alarm differential 0.5 0.0 20.0 Bar IS-S PA41 C3 supply HP alarm setpoint Circuit 3 supply probe high pressure alarm setpoint 20.0 PA39 PH04 Bar IS-S PA42 C3 supply HP alarm diff. Circuit 3 supply probe high pressure alarm differential 1.0 0.0 20.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL PG22 PG30 Circuit 3 inverter comp.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL C1 comp.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL HC04 Compressor C4 DO position Sets the position of the digital output for compressor 4 Or compressor inverter consent position 7 0 13 (26) CO-Hw HC14 C4 increment 1 DO position Sets the position of the increment 1 digital output for compressor 4 8 0 13 (26) CO-Hw HC24 C4 increment 2 DO position Sets the position of the increment 2 digital output for compressor 4 0 0 13 (26) CO-Hw HC34 C4 increment 3 DO position Sets the position o
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL for compressor 7 HC27 C7 increment 2 DO position Sets the position of the increment 2 digital output for compressor 7 0 0 13 (26) CO-Hw HC37 C7 increment 3 DO position Sets the position of the increment 3 digital output for compressor 7 0 0 13 (26) CO-Hw HC08 Compressor C8 DO position Sets the position of the digital output for compressor 8 Or compressor inverter consent position HC18 C8 increment 1 DO position Sets the position of th
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL CO-Hw Max = 8(16) on C-PRO MEGA RACK; Visibility *¹ CO-Hw Max = 8(16) on C-PRO MEGA RACK; Visibility *¹ C10 increment 3 DO position Sets the position of the increment 3 digital output for compressor 11 HC50 Compressor C11 DO position Sets the position of the digital output for compressor 11 Or compressor inverter consent position HC51 C11 increment 1 DO position Sets the position of the increment 1 digital output for compressor 11 0 0 13 (2
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL HF04 Fan 4 DO position HF05 Fan 5 DO position HF06 Fan 6 DO position HF07 Fan 7 DO position HF08 Fan 8 DO position HF09 Fan 9 DO position HF10 Fan 10 DO position HF11 Fan 11 DO position HF12 Fan 12 DO position HA01 Global alarm DO position HA11 Sets the position of the digital output for fan 4 Or fan inverter consent position 13 0 13 (26) CO-Hw 0 0 13 (26) CO-Hw 0 0 13 (26) CO-Hw 0 0 13 (26) CO-Hw 0 0 13 (26) CO-H
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL SYSTEM BUILDER MENU PARAMETERS – Other hardware digital input/output positions Sets the position of the system global on/off digital input Sets the position for compressor management secondary setpoint digital input Sets the position for fan management secondary setpoint digital input 0 0 12 (22) CO-Hw Max =10(18) on C-PRO MEGA RACK 0 0 12 (22) CO-Hw Max =10(18) on C-PRO MEGA RACK 0 0 12 (22) CO-Hw Sets the position of the circuit 1 on/off
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Hd24 C2 supply HP alarm DI pos. Hd25 C2 comp. oil diff. alarm DI pos. Hd26 Sets the position of the circuit 2 supply pressureswitch high pressure alarm digital input 12 0 12 (22) CO-Hw Sets the position of the circuit 2 compressor oil differential alarm digital input 0 0 12 (22) CO-Hw C2 comp. fan thermal alarm DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Hd42 Hd43 Hd44 Hd45 Hd46 Hd47 Hd48 Comp. 2 thermal DI pos. Comp. 3 thermal DI pos. Comp. 4 thermal DI pos. Comp. 5 thermal DI pos. Comp. 6 thermal DI pos. Comp. 7 thermal DI pos. Comp. 8 thermal DI pos. Hd49 Comp. 9 thermal DI pos. Hd50 Comp. 10 thermal DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL alarm digital input Hd51 Comp. 11 thermal DI pos. Hd52 Comp. 12 thermal DI pos. Hd61 Compressor 1 pressure-switch DI pos. Hd62 Hd63 Compressor 2 pressure-switch DI pos. Compressor 3 pressure-switch DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Hd64 Hd65 Compressor 4 pressure-switch DI pos. Compressor 5 pressure-switch DI pos. Sets the position of the compressor 4 pressureswitch alarm digital input 0 0 12 (22) CO-Hw 0 0 12 (22) CO-Hw 0 0 12 (22) CO-Hw Sets the position of the compressor 5 pressureswitch alarm digital input Sets the position of the compressor 6 pressureswitch alarm digital input Hd66 Compressor 6 pressure-switch DI pos. Hd71 Compressor 1 oil diff. DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL input C-PRO MEGA RACK; Visibility *¹ Hd81 Fan 1 thermal DI pos. Sets the position of the fan 1 thermal alarm digital input 0 0 12 (22) CO-Hw Hd82 Fan 2 thermal DI pos. Sets the position of the fan 2 thermal alarm digital input 0 0 12 (22) CO-Hw Hd83 Fan 3 thermal DI pos. Sets the position of the fan 3 thermal alarm digital input 0 0 12 (22) CO-Hw Hd84 Fan 4 thermal DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Hd86 Hd87 Hd88 Hd89 Hd90 Hd91 Hd92 Max =10(18) on C-PRO 0 0 12 (22) CO-Hw MEGA RACK; Visibility *² Max =10(18) on C-PRO Fan 7 thermal DI Sets the position of the fan 7 0 0 12 (22) CO-Hw MEGA RACK; pos. thermal alarm digital input Visibility *² Max =10(18) on C-PRO Fan 8 thermal DI Sets the position of the fan 8 0 0 12 (22) CO-Hw MEGA RACK; pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6 REGULATIONS 6.1 Machine configuration A Wizard (System builder menu) allows assisted configuration of the machine. The first choice refers to the number of circuits (1, 2 or 3) by means of parameter PG01; in the case of dual and triple circuit machines, the selection of the type of condensation, single or separate, (PG30) and the presence, or otherwise, of an expansion unit (PG02) are also important.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL The same wizard also sets the number of compressors and fans for each circuit, the presence of an inverter, compressors and fans, the number of increments and compressor safety devices and enables fan safety devices.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL ⋅ be switched to the ON state if fulfilling the “OFF by supervisor” conditions, and the “OFF by digital input” condition is not met. The machine On/Off key is the ESC key, pressed for approx. 2 seconds. The remote On/Off inputs (if present) are configured by means of the relevant parameters.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6.3 Compressor regulation Control of compressor suction pressure envisages the management of the latter in order to reach and maintain a defined working pressure value: depending on the type of control (side band or neutral zone) and the use, or otherwise, of inverters for fine adjustment, four types of regulation are envisaged. 6.3.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL The PC78 Sideband step overlap parameter allows improvements in the behaviour of this type of regulation, which requires broad proportional bands in order to be stable, thus modifying the subdivision of the regulation band between steps: 100 - PC78 % Steps Release Max Steps Insertion Suction PC78 % SP SP + BP The insertion of steps occurs at PC78% of the proportional band, while release occurs at 100 – PC78% of the band; if for example PC78 = 60%, s
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL the zone, the on and off requests for the various steps must be timed. The relevant parameters are as follows: ⋅ Minimum switch-on time (NZ_TOnMin) ⋅ Maximum switch-on time (NZ_TOnMax) ⋅ Minimum switch-off time (NZ_TOffMin) ⋅ Maximum switch-off time (NZ_TOffMax) On the basis of the suction pressure value approaching the reference value, the times will vary proportionally according to the values set.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL The range of values the inverter output may assume is comprised of between 0 and 100 percentage points, with two decimal places. By enabling the inverter, for a given number of compressors, one step is lost, which will be replaced by regulation with inverter on the first compressor. Below is given an example of how to change regulation with the presence of an inverter.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Example: 4 compressors w/o inverter Example: 4 compressors with 1 inverter Steps 3 2 Steps 1 4 3 Pressure 2 Inverter 1 100.00 % Pressure Out of range. Switching on Pressure Out of range. Switching on In the neutral zone, the inverter undergoes no changes and the compressors are neither switched on or off. In the on zone: ⋅ the inverter is activated as soon as requested. ⋅ the inverter value varies according to the time TI set by the parameter.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL digital inputs and digital outputs for switching on/off and any increment devices, may be associated with each compressor. The compressors are managed by means of a setPoint and differential that can be set by means of a parameter, and by reading a pressure value from the suction probe. Switching on/off is guaranteed by a thermoregulation device and by certain times settings, protecting the various startup operations. 6.4.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 5. Alarm: the compressor is off and in the alarm state. In this state, the user interface displays the message “ALL”. 6. Manual: the compressor is in manual operational mode. In this state, the user interface displays the message “MAN”. In any case, a manually functioning compressor is sensitive to any alarms, in this case, the status will be that of Alarm. 6.4.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Switch off : C12 . … C4 . C3 . C2 . C1 3) FIFO + time of operation This type of rotation functions by considering the number of operating hours for each compressor. Startup will switch on the compressor with the least operating hours, while shut down will switch off the compressor with the most operating hours.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Increment number By means of the appropriate parameter (PG04), it is possible to select one, two or three equal powered increments for each of the configured compressors. Each compressor will have the same number of available increments. Possible configurations for the number of increments per compressor depend on what hardware is being used, and the presence, or otherwise, of an expansion unit.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Switch off : ppCppCppC. The program favours the complete switching off of individual compressors prior to moving to the following compressor. With CCCpppppp type switching on and ppppppCCC type switching off, the individual step switch on/off logic follows this example (example for 3 compressors): Compressor switch on : C1 . C2 . C3 Increment switch on : p1C1 . p1C2 .p1C3 / p2C1 . p2C2 . p2C3 / p3C1 . p3C2 . p3C3 Increment switch off : p3C3 . p3C2 .
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL SpeedUp time. If regulation by means of inverter is set, then this parameter, if other than zero, keeps the inverter output at maximum value (100.0%) with each new step switch on request. 6.4.6 Startup delay from reset By means of the parameter PC69 – TRestart in the Installer ->Compressors menu, it is possible to delay compressor startup each time the controller is reset; for example, following a black-out caused by a power cut. 6.4.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL The “compressor high/low pressure pressure-switch” safety device manages up to a maximum of 6 compressors and is enabled by setting two parameters as follows: Safety device number: 2 / 3 Safety device type: 2 / 4 To enable the alarms associated with these safety devices, besides setting the above-described parameters, it is also essential to set the positions where the digital inputs relating to the various alarm types will be connected from within the S
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 3) N°2 circuit (PG01=2), n°1 circuit 1 compressor, n°2 circuit 2 compressors (PG11=1, PG15=3), only circuit 2 inverter enabled (PG12=0, PG16=1).
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL ⋅ ⋅ In the neutral zone: the combination remains unchanged. In the on zone: the combination of compressors is recalculated in order to guarantee power greater than that provided by the previous combination. ⋅ In the off zone: the combination of compressors is recalculated in order to guarantee power less than that provided by the previous combination.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6.4.11 Refrigeration power incrementing at high pressures In order to avoid tripping the condensation high pressure pressure-switch, with consequent blocking of cold production, it is possible to reduce the refrigeration power and consequently the power to be exchanged by the condenser, thus reducing condensation pressure.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6.5 Condensation regulation Condensation management envisages control of the supply pressure using the fans: depending on the type of control (side band or neutral zone) and the use, or otherwise, of inverters for fine adjustment, four types of regulation are envisaged. 6.5.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL ⋅ Side band suction SetPoint (SP) Outwith said neutral zone, device on or off requests for the configured fans will follow this logic: ⋅ Switch on: when the supply pressure exceeds the setPoint + Neutral Zone threshold ⋅ Switch off: when the pressure drops below the setPoint In this type of regulation, the neutral zone is displaced to the right of the setPoint.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL If the value measured by the probe is between the value of SP + OFSI and the value of SP + OFSI + ID, the regulator output will assume a value proportional to the supply probe value. In the case where the supply probe assumes a value greater than or equal to the value of SP + OFSI + ID, the inverter output will assume the maximum value.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL ⋅ when the inverter reaches the maximum value one of the other fans is requested. In the case where the on zone remains ongoing one or all the fans are switched on and the inverter value remains at maximum. In the off zone: ⋅ as soon as requested, the inverter output is adjusted, according to TI, to the minimum value.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6.6 Fan management The program is capable of managing up to a maximum of 12 fans (8 if using C-PRO MEGA) divided according to circuit. A digital input for safety devices and a digital output for switching on/off may be associated with each fan. The number of fans that can be used is further limited by the number of compressors (and stepped compressors), i.e. the number of free digital outputs remaining after the compressors have been configured.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 4. On: the fan is on. In this state, the user interface displays the message “ON”. 5. Awaiting switch on: the fan is about to be switched on, and is currently waiting protective device waiting times. In this state, the user interface flashes the message “WON”. 6. Alarm: the fan is off and in the alarm state. In this state, the user interface displays the message “ALL”. 7. Manual: the fan is in manual operational mode.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2) LIFO This follows “Last In First Out” logic, i.e. the last fan switched on will be the first to be switched off. Example. Switch on : F1 . F2 . F3 . F4 … . F12 Switch off : F12 . … F4 . F3 . F2 . F1 3) FIFO + time of operation This type of rotation functions by considering the number of operating hours for each fan. Startup will switch on the fan with the least operating hours, while shut down will switch off the fan with the most operating hours.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Neutral zone timings These parameters are used to time the switching on and off requests for the various condensation devices. Minimum switch on/off request time - TOn/Off For these parameters, please refer to the description given in section 2.5.2. Protective device timings These times are required to protect the fans from the various startup operations to which they are subjected. TOnOther – Minimum different fan switch on time (PF07).
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6.7 Miscellaneous controls 6.7.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL is not possible. To correctly configure this feature, simply enable at least one compressor/fan inverter, depending on the type enabled, the other type will be automatically excluded from the analogue outputs. The only case where it is possible to use both compressor inverters and fan inverters is when the parameter unique condensation (PG30) is set; in this case, the last analogue output (AO04) may be used as the sole fan inverter. Note 1.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Band start 02:00:00 07:15:00 07:15:00 07:15:00 Offset +0.3 +0.1 0 0 Setpoint 1.3 bar 1.1 bar 1.0 bar 1.0 bar Description From 02:00:00 to 07:15:00 From 07:15:00 to 02:00:00 - During an ERTC alarm (clock alarm), the time band function is automatically disabled and LED L2 on the display stays on, until the alarm is reset. When the clock is within a time band, i.e.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL ⋅ ⋅ ⋅ Flashes slowly if only one of the compressor and fan setpoints is altered. Remains on if both setpoints are altered by the time bands. Remains off if there is no condition. To enter time band management, press and hold display key K2 for approx. 2 seconds. 6.7.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL To restore the compressor to normal use, it is necessary to reset the parameter compressor enable to the value “A” (Automatic), otherwise, the compressor in question will continue to operate in manual mode, not fulfilling the switch on and/or off requests calculated by the selected regulation.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 6.7.8 Temperature probes The application is capable of managing up to two auxiliary temperature probes: environment probe and external probe.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 7 DIAGNOSTICS The application is capable of managing a series of alarms relating to the system compressors, fans, circuits and functions. Based on the various alarm types, it is possible to configure resets (manual or automatic), possible signalling delays and the actions to be executed in specific cases. When several alarms are active, display LED L0 flashes (even with the machine off) and the buzzer sounds if the machine is switched on.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL At this point, if there are no other alarms, a page will appear indicating “No active alarms”, LED L0 will be switched off and the machine will return to normal operation, or the page relating to the subsequent active alarm will be displayed. The consequences derived from an active manual alarm remain valid until the user cancels the alarm message. To silence the buzzer simply press the K0 key. 7.1.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL Settable Settable Settable Settable Settable Settable Settable Settable Settable Settable Settable Settable (if enabled) - Num. comp. ON configurable - Inverter forced to 100% (if requested and if only comp. on circuit) - Num. fan. ON configurable - Inverter forced to 100% (if requested and if only fan on circuit) - OFF Step circuit 3 HP (if enabled) Comp. 1 OFF 1 Comp. 2 OFF Comp. 3 OFF Comp. 4 OFF Comp. 5 OFF Comp. 6 OFF Comp. 7 OFF Comp. 8 OFF Comp.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL AC09 Compressor 9 operating time AC10 Compressor 10 operating time AC11 Compressor 11 operating time AC12 Compressor 12 operating time AF21 AF22 AF23 AF24 AF25 AF26 AF27 AF28 AF29 AF30 AF31 AF32 Fan 1 thermal Fan 2 thermal Fan 3 thermal Fan 4 thermal Fan 5 thermal Fan 6 thermal Fan 7 thermal Fan 8 thermal Fan 9 thermal Fan 10 thermal Fan 11 thermal Fan 12 thermal AF01 Fan 1 operating time AF02 Fan 2 operating time AF03 Fan 3 operating time
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL ACC1 AFC1 AL32 AL37 C1 common oil differential C1 common fan thermal C2 supply pressure high C2 suction pressure high AL42 Settable Manual Auto Auto Display Display All fans ON All comp. ON C2 supply pressure low Auto All fans OFF AL47 C2 suction pressure low Auto All comp. OFF AL12 C2 supply high pressure pressure-switch Settable All comp. OFF AL22 C2 suction low pressure pressure-switch Auto All comp.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL By means of the relevant parameter (PH18) it is possible to establish the polarity (NO, or NC) of the various alarm digital outputs.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 8 LIST OF MODBUS VARIABLES It is possible to control the application by means of a supervisor module, using the Modbus protocol. Communication uses an RS485 serial interface, already built in to the controller. The various parameters exported by the application are reported below 8.1.1 Modbus export table (C-PRO GIGA) REGISTER VARS LIST id Name Value Min Max Description Mode 257 PackedDI1_16 0 0 65535 Bit1=DI01, Bit2=DI02 ...
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 772 773 774 775 776 PackedAlarmW4 PackedAlarmW5 PackedAlarmW6 PackedAlarmW7 PackedAlarmW8 0 0 0 0 0 0 0 0 0 0 65535 Bit1=AC41, Bit2=AC42, Bit3=AC43, Bit4=AC44, Bit5=AC45, Bit6=AC46, Bit9=AC51, Bit10=AC52, Bit11=AC53, Bit12=AC54, Bit13=AC55, Bit14=AC56 R/W 65535 Bit1=AC01, Bit2=AC02, Bit3=AC03, Bit4=AC04, Bit5=AC05, Bit6=AC06, Bit7=AC07, Bit8=AC08, Bit9=AC09, Bit10=AC10, Bit11=AC11, Bit12=AC12 R/W 65535 Bit1=AF01, Bit2=AF02, Bit
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1287 CmpInv_actualSet_Circuit1 0.0 -145.0 625.5 R/W 1288 FanInv_actualSet_Circuit1 0.0 -145.0 625.5 R/W 1289 PowerRequested_Circuit1 0 0 100 R/W 1290 PowerSupplied_Circuit1 0 0 100 R/W 1291 StatusCircuit2 0 0 5 R/W 1292 Cmp_actualSetPoint_Circuit2 0.0 -145.0 625.5 R/W 1293 Fan_actualSetPoint_Circuit2 0.0 -145.0 625.5 R/W 1294 CmpInv_actualSet_Circuit2 0.0 -145.0 625.5 R/W 1295 FanInv_actualSet_Circuit2 0.0 -145.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1557 PT34_Cmp_TBOffset4_Circuit3 0.0 -290.0 290.0 R/W 1558 PT50_Fan_EnableTimeBands 0 0 1 R/W 1559 PT51_Fan_startTB1 ( Low ) 0 0 86399 R/W 0 0 86399 R/W 0 0 86399 R/W 0 0 86399 R/W 1567 PT61_Fan_TBOffset1_Circuit1 0.0 -290.0 290.0 R/W 1568 PT62_Fan_TBOffset2_Circuit1 0.0 -290.0 290.0 R/W 1569 PT63_Fan_TBOffset3_Circuit1 0.0 -290.0 290.0 R/W 1570 PT64_Fan_TBOffset4_Circuit1 0.0 -290.0 290.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1595 PUF3_Fan_SecSPOffset_ByDI_Circuit3 0.0 -290.0 290.0 R/W 1596 PUF6_Fan_SecSPOffset_BySup_Circuit3 0.0 -290.0 290.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1633 PM11a20_33_34_En_Manual_Comp[10] 0 0 1 R/W 1634 PM11a20_33_34_En_Manual_Comp[11] 0 0 1 R/W 1635 PM21a30_35_36_ForzCmp[0] 0 0 4 R/W 1636 PM21a30_35_36_ForzCmp[1] 0 0 4 R/W 1637 PM21a30_35_36_ForzCmp[2] 0 0 4 R/W 1638 PM21a30_35_36_ForzCmp[3] 0 0 4 R/W 1639 PM21a30_35_36_ForzCmp[4] 0 0 4 R/W 1640 PM21a30_35_36_ForzCmp[5] 0 0 4 R/W 1641 PM21a30_35_36_ForzCmp[6] 0 0 4 R/W 1642 PM21a30_35_36_ForzCmp[7] 0 0
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1671 PM41a50_71_72_V_HoursFan[9] ( High ) 1672 PM41a50_71_72_V_HoursFan[10] ( Low ) 0 0 500000 R/W 0 0 500000 R/W 1676 PM51a60_73_74_En_Manual_Fan[0] 0 0 1 R/W 1677 PM51a60_73_74_En_Manual_Fan[1] 0 0 1 R/W 1678 PM51a60_73_74_En_Manual_Fan[2] 0 0 1 R/W 1679 PM51a60_73_74_En_Manual_Fan[3] 0 0 1 R/W 1680 PM51a60_73_74_En_Manual_Fan[4] 0 0 1 R/W 1681 PM51a60_73_74_En_Manual_Fan[5] 0 0 1 R/W 1682 PM51a60_73_74_En_Manual_
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1709 PM87_Taratura_AI07 0.0 -19.0 19.0 R/W 1710 PM88_Taratura_AI08 0.0 -19.0 19.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1744 PC36_Cmp_PI_Ti_Circuit2 600 0 999 R/W 1745 PC37_Cmp_PI_Diff_Circuit2 0.5 0.0 290.0 R/W 1746 PC38_Cmp_NZ_Zone_Circuit2 0.5 0.0 290.0 R/W 1747 PC39_Cmp_NZ_DiffOutZone_Circuit2 0.5 0.0 290.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1781 PC76_PartLimit 50 0 100 % R/W 1782 PC78_OverloadSteps_Cmp 0 0 100 % R/W 1783 PC81a92_PowerCmp[0] 1 0 5000 kW R/W 1784 PC81a92_PowerCmp[1] 1 0 5000 kW R/W 1785 PC81a92_PowerCmp[2] 1 0 5000 kW R/W 1786 PC81a92_PowerCmp[3] 1 0 5000 kW R/W 1787 PC81a92_PowerCmp[4] 1 0 5000 kW R/W 1788 PC81a92_PowerCmp[5] 1 0 5000 kW R/W 1789 PC81a92_PowerCmp[6] 1 0 5000 kW R/W 1790 PC81a92_PowerCmp[7] 1 0 5000 kW
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1817 PF37_Fan_PI_Diff_Circuit2 0.5 0.0 290.0 R/W 1818 PF38_Fan_NZ_Zone_Circuit2 0.5 0.0 290.0 R/W 1819 PF40_Fan_NZ_TOnOff_Circuit2 10 0 999 R/W 1820 PF44_Fan_Inverter_Diff_Circuit2 0.5 0.0 290.0 R/W 1821 PF45_Fan_Inverter_OffsetSP_Circuit2 0.0 -290.0 290.0 R/W 1822 PF46_Fan_Min_Inverter_Circuit2 0.00 0.00 100.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1854 PA12_ThermalCmp_ResetType 1 0 1 R/W 1855 PA13_PressSwitchCmp_ResetType 1 0 1 R/W 1856 PA14_OilDiffCmp_ResetType 1 0 1 R/W 1857 PA15_SetPoint_LP_Suction_C1 0.5 -145.0 625.5 R/W 1858 PA16_Diff_LP_Suction_C1 0.5 0.0 290.0 R/W 1859 PA17_SetPoint_HP_Suction_C1 4.0 -145.0 625.5 R/W 1860 PA18_Diff_HP_Suction_C1 0.5 0.0 290.0 R/W 1861 PA19_SetPoint_LP_Supply_C1 2.0 -145.0 625.5 R/W 1862 PA20_Diff_LP_Supply_C1 0.5 0.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1892 PH11_Modbus_Address 1 1 247 R/W 1893 PH12_Modbus_Baud 3 0 4 R/W 1894 PH13_Modbus_Parity 2 0 2 R/W 1895 PH14_Modbus_StopBit 0 0 1 R/W 1896 PH15_SetDefault_Par 0 0 1 R/W 1897 PH16_Cmp_SecuritiesType 1 0 4 R/W 1898 PH17_Logic_DI_Alarm 0 0 1 R/W 1899 PH18_Logic_DO_Alarm 0 0 1 R/W 1900 PH19_Logic_DI_Other 1 0 1 R/W 1901 PH20_LogicCmdInverter_Comp 0 0 1 PH20=0: 0=0, 1=1; PH20=1: 0=1, 1=0; R/W 1902 PH21_Lo
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1928 PG16_EnCmpInverter_Circuit2 0 0 1 R/W 1929 PG21_CmpNumber_Circuit3 0 0 12 R/W 1930 PG22_EnCmpInverter_Circuit3 0 0 1 R/W 1931 PG30_En_UniqueCondenser 0 0 1 R/W 1932 PG32_Fan_EnSecurities 0 0 1 R/W 1933 PG41_FansNumber_Circuit1 2 0 12 1934 PG42_EnFanInverter_Circuit1 0 0 1 1935 PG45_FansNumber_Circuit2 2 0 12 1936 PG46_EnFanInverter_Circuit2 0 0 1 R/W 1937 PG51_FansNumber_Circuit3 0 0 12 R/W 1938 PG52_En
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1963 HC21a30_52_62_PosDO_LS2[0] 0 0 26 Max=16 on C-PRO MEGA R/W 1964 HC21a30_52_62_PosDO_LS2[1] 0 0 26 Max=16 on C-PRO MEGA R/W 1965 HC21a30_52_62_PosDO_LS2[2] 0 0 26 Max=16 on C-PRO MEGA R/W 1966 HC21a30_52_62_PosDO_LS2[3] 0 0 26 Max=16 on C-PRO MEGA R/W 1967 HC21a30_52_62_PosDO_LS2[4] 0 0 26 Max=16 on C-PRO MEGA R/W 1968 HC21a30_52_62_PosDO_LS2[5] 0 0 26 Max=16 on C-PRO MEGA R/W 1969 HC21a30_52_62_PosDO_LS2[6] 0 0
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 1999 HA01_11_21_31_PosDO_Alarms[0] 9 0 26 Value=2, Max=16 on C-PRO MEGA R/W 2000 HA01_11_21_31_PosDO_Alarms[1] 0 0 26 Max=16 on C-PRO MEGA R/W 2001 HA01_11_21_31_PosDO_Alarms[2] 0 0 26 Max=16 on C-PRO MEGA R/W 2002 HA01_11_21_31_PosDO_Alarms[3] 0 0 26 Max=16 on C-PRO MEGA R/W 2003 Hd01_Pos_DI_Remote_OnOff 0 0 22 Max=18 on C-PRO MEGA R/W 2004 Hd02_Pos_DI_CmpSecSP 0 0 22 Max=18 on C-PRO MEGA R/W 2005 Hd03_Pos_DI_FanSecSP
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL 2031 Hd41_52_PosDI_ThermalOverloadCmp[7] 0 0 22 Max=18 on C-PRO MEGA R/W 2032 Hd41_52_PosDI_ThermalOverloadCmp[8] 0 0 22 Max=18 on C-PRO MEGA R/W 2033 Hd41_52_PosDI_ThermalOverloadCmp[9] 0 0 22 Max=18 on C-PRO MEGA R/W 2034 Hd41_52_PosDI_ThermalOverloadCmp[10] 0 0 22 Max=18 on C-PRO MEGA R/W 2035 Hd41_52_PosDI_ThermalOverloadCmp[11] 0 0 22 Max=18 on C-PRO MEGA R/W 2036 Hd61_66_PosDI_PressureSwitchCmp[0] 0 0 22 Max=18 on
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL C-PRO MEGA RACK and C-PRO GIGA RACK application manual. Version 1.04, March 2011. Code 144RACKMGE04 File 144RACKMGE04.pdf. This document is the exclusive property of Evco, whereby any reproduction or distribution is strictly forbidden, unless expressly directly authorised by Evco. Evco assume no responsibility in relation to the characteristics, technical data and any possible errors reported in this document or deriving from the use of the same.
HEAD OFFICE Evco Via Mezzaterra 6, 32036 Sedico Belluno ITALY Tel. 0437-852468 Fax 0437-83648 info@evco.it www.evco.it OVERSEAS OFFICES Control France 155 Rue Roger Salengro, 92370 Chaville Paris FRANCE Tel. 0033-1-41159740 Fax 0033-1-41159739 control.france@wanadoo.fr Evco Latina Larrea, 390 San Isidoro, 1609 Buenos Aires ARGENTINA Tel. 0054-11-47351031 Fax 0054-11-47351031 evcolatina@anykasrl.com.ar Evco Pacific 59 Premier Drive Campbellfield, 3061, Victoria Melbourne, AUSTRALIA Tel.