Instruction Manual

C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
17
Other connectors (not present on the C-PRO MEGA RACK controller)
Conn.
Abbre
v.
Description
JN-1
NC 9
relay No. 9 contact normally closed
JN-2
COM 9
relay No. 9 common connection
JN-3
NO 9
relay No. 9 contact normally open
JO-1
NC 10
relay No. 10 contact normally closed
JO-2
COM10
relay No. 10 common connection
JO-3
NO 10
relay No. 10 contact normally open
JP-1
COM11
relay No. 11 common connection
JP-2
NO 11
relay No. 11 contact normally open
JP-3
COM12
relay No. 12 common connection
JP-4
NO 12
relay No. 12 contact normally open
JP-5
COM13
relay No. 13 common connection
JP-6
NO 13
relay No. 13 contact normally open
JQ-1
DI11
No. 11 digital input 230 VAC
JQ-2
DI12
No. 12 digital input 230 VAC
JQ-3
CONHV
digital input common connection 230 VAC
Second RS-485 port (on request)
Conn.
Abbre
v.
Description
YE-1
RS485-
RS 485 - connector for connecting to supervision system
YE-2
RS485+
RS 485 + connector for connecting to supervisor system
YE-3
GND
GND connector for connecting to supervision system, via RS485
RS-232 port (available on request, as an alternative to the second RS-485 port)
Conn.
Abbre
v.
Description
YF-1
5Vdc
RS 232 9 pole connector -
YF-2
Tx
RS 232 9 pole connector - Transmission Signal
YF-3
Rx
RS 232 9 pole connector - Reception Signal
YF-4
DTR/D
SR
RS 232 9 pole connector -
YF-5
GND
RS 232 9 pole connector -
YF-6
DTR/D
SR
RS 232 9 pole connector -
YF-7
RTS
RS 232 9 pole connector -
YF-8
CTS
RS 232 9 pole connector -
Jumper and LED meanings
JMP1 AI1 analogue input selection
Jumper not inserted 0 – 10 V input
Jumper inserted 0 – 5 V, 0 – 20 mA, 4 – 20 mA, NTC, PTC input
JMP2 AI2 analogue input selection
Jumper not inserted 0..10 V input
Jumper inserted 0 – 5 V, 0 – 20 mA, 4 – 20 mA, NTC, PTC input