C-PRO MEGA PROGRAMMABLE CONTROLLERS HARDWARE MANUAL CODE 114CPRMHWE01
C-PRO MEGA HARDWARE MANUAL Important Please read these instructions carefully prior to installation and use, and follow all the precautions for installation and electrical connections; keep these instructions with the device for future consultation. The device must be disposed of in accordance with local regulations pertaining to the collection of electrical and electronic appliances.
C-PRO MEGA HARDWARE MANUAL Sommario Introduction ........................................................................................................................................................................ 4 1 Components and Accessories network...................................................................................................................... 8 1.1 Built-in version example..........................................................................................................
C-PRO MEGA HARDWARE MANUAL Introduction The C-PRO MEGA f programmable controllers family is the right solution for refrigeration, ventilation and air conditioning applications. Both in terms of controls, regulation and the user interface, the controller application software is fully programmable, in a simple and intuitive way, thanks to the use of the UNI-PRO development environment. The C-PRO MEGA is available in a DIN rail version (see the pictueres below).
C-PRO MEGA HARDWARE MANUAL Attention : With 12 Vdc + 12 Vdc power supply, the following ports and outputs are optoinsulated: • the analogic output • the RS-485 serial standard port • the RS-485 serial (or RS-232) optional port • the wide CAN port In order to ensure the optoinsulation of these outputs, the controller must be supplied with two dc power sources preferably insulated from each other (electrically insulated).
C-PRO MEGA HARDWARE MANUAL C-PRO MEGA built-in version C-PRO MEGA Sealed Case Version Page 6
C-PRO MEGA HARDWARE MANUAL C-PRO MEGA Open case version Page 7
C-PRO MEGA HARDWARE MANUAL 1 Components and Accessories network 1.
C-PRO MEGA HARDWARE MANUAL 1.
C-PRO MEGA HARDWARE MANUAL 2 Technical features 2.1 Connections Power supply: The C-pro MEGA family is available with two different version of power supply : i. No optoinsulated internal switching 24Vac/dc version ii. two separeted inputs 12 Vdc + 12 Vdc version.
C-PRO MEGA HARDWARE MANUAL The maximum length of the connection cables to the remote user interface depends of the CAN port baud rate . Local CAN port: 10 m with 20.000 baud 5 m with 50.000 baud 2 m with 125.000 baud 1 m with 500.000 baud. Wide CAN port: 1.000 m with 20.000 baud 500 m with 50.000 baud 250 m with 125.000 baud 50 m with 500.000 baud. The LocalCAN port baud rate is settable by jumpers (see section wiring layout). The WideCAN port baud rate is settable by parameter.
C-PRO MEGA HARDWARE MANUAL 2.2 C-PRO MEGA wiring layout C-PRO MEGA is available in two different version : the first with 12 VDC + 12 VDC e the second with 24 VAC/DC power supply. The C-PRO MEGA 12 VDC + 12 VDC wiring layout connection is reported here below. C-PRO AL power supplier adoption is recommended . Please, refer to the section “power supply” of capter 3 regarding the utilisation optoinsulation.
C-PRO MEGA HARDWARE MANUAL Following it is reported the C-PRO MEGA 24 VAC/DC version wiring layout connection; C-PRO AL power supplier adoption is recommended Please, refer to the section “power supply” of capter 3 regarding the utilisation optoinsulation.
C-PRO MEGA HARDWARE MANUAL The following table shows the available inputs and outputs on c-pro Mega : Lower board 12 VDC + 12 VDC power supply version Conn. Letter Description code C1-1 C1-2 VCC GND main card power supply (+13Vdc) Main power supply reference JA-1 JA-2 JA-3 VDC AI 1 GND power supply for active sensors (*1) universal analogic input 1 (NTC, PTC, 0..5V, 0..10V, 0..20 mA, 4..
C-PRO MEGA HARDWARE MANUAL Conn. Letter Description code JK-6 NO 5 normally open contact relay no. 5 JL-1 JL-2 JL-3 JL-4 JL-5 JL-6 COM 6 NO 6 COM 7 NO 7 COM 8 NO 8 common relay no. 6 normally open contact relay no. 6 common relay no. 7 normally open contact relay no. 7 common relay no. 8 normally open contact relay no.
C-PRO MEGA HARDWARE MANUAL Conn.
C-PRO MEGA HARDWARE MANUAL Jumpers and LEDs meanings The controller also has some configuration jumpers: JMP1 Jumper not inserted Jumper inserted Selection of analogic AI1 input 0-10V input 0-5V, 0-20mA, 4-20mA, NTC, PTC input Jumper not inserted Jumper inserted Selection of analogic AI2 input 0..
C-PRO MEGA HARDWARE MANUAL There are also some LEDs with diagnostic meaning (note: the L5, L6 LEDs are located inside of the controller case) LED L1 On blinking rapidly On blinking slowly On continuously Off Local CAN communication status OK Warning Bus Error Bus OFF Led L2 On blinking rapidly On blinking slowly On continuously Off Local CAN communication status OK Warning Bus Error Bus OFF Led L3 On blinking rapidly On blinking slowly On continuously Off Real Time Clock status Low_Voltage detected R
C-PRO MEGA HARDWARE MANUAL LED L6 Operating status of main It indicates the operating status of the controller's main program (main): when blinking, it indicates the controller program is properly working. The flashing period indicates the execution time of the main cycle.
C-PRO MEGA HARDWARE MANUAL 2.3 C-PRO MEGA Dimensions / Installations C-PRO GIGA dimensions are reported here below; all dimensions are to be meant in millimeters (inc). Built-in version Sealed version Open version Cautions for the installation: - ensure that the operating conditions (operating temperature, humidity, etc.) are within the limits indicated in the technical data sheets - do not install the device near to, any heat sources (heating elements, hot air conduits, etc.
C-PRO MEGA HARDWARE MANUAL - in compliance with safety regulations, the device must be correctly installed, and protected against any contact with electrical parts; all safety devices must be safely fixed in order to be removed only by means of proper tools.
C-PRO MEGA HARDWARE MANUAL To install the C-PRO MEGA, proceed as indicated in figures 1 and 2. To remove the C-PRO MEGA, use a screw driver and proceed as indicated in figures 3 and 4.
C-PRO MEGA HARDWARE MANUAL 3 C-PRO MEGA technical features 3.
C-PRO MEGA HARDWARE MANUAL 3.2 General features C-PRO MEGA open CPU Microprocessor Oscillator frequency Flash program memory RAM data storage memory A/D converter Number type Physical layer WideCAN communication bus (optional) Baud rate (max. length = 1000 m) Baud rate (max. length = 400 m) Baud rate (max. length = 250 m) Baud rate (max.
C-PRO MEGA HARDWARE MANUAL 3.3 Electrical features Internal Switching Power supply External Power supply Main Input Note: in this case the I/O and the serial ports of the controller are not insulated Main Input 24Vac +/- 15%, 20-60Vdc, max 1A 13Vdc, 0.6A (both inputs) +0.2A if a user interface has to be fed +0.6A if an expansion board has to be feed (double inputs) Secondary input 15Vdc, 0.
C-PRO MEGA HARDWARE MANUAL Note: The commons (COM) terminals are connected together Analog outputs Digital outputs Internal CAN communication bus Number type 4 voltage or current (selectable by dip-switch), optoinsulated Jumper inserted Current range Current output accuracy Current output resolution Maximum load of current output Current output settling time Current 0 - 20 mA ±1 mA 0.
C-PRO MEGA HARDWARE MANUAL Note: 1) baud rate selectable by two jumpers 2) The CAN connection consists of a cable with twisted pair (both shielded and not shielded). The first and the last elements of the system must have the bus terminating resistor connected (impedance is 120Ω). A second twisted pair is used for the feed and the ground Number type Physical layer Baud rate (max. length 1000 m) Connector RS485 serial communication (UART1) type Physical layer Baud rate (max.
C-PRO MEGA HARDWARE MANUAL 3.4 C-PRO MEGA built-in user interface The C-PRO MEGA built-in versions has a 4x20 alphanumerical backlit LCD display and a keyboard with 9 buttons and 6 LEDs. Some buttons and LEDs are predefined; this means that their function has been set by the firmware. Other buttons and LEDs are programmable; this means that they may be used freely within the UNIPRO development system.
C-PRO MEGA HARDWARE MANUAL Programmable Controller parameter configuration command 2nd level programming command + + 3rd level programming command + The following table shows the LEDs’ functions: LED LS L0 L1 LP L2 LM LS LP L0 L1 L2 FUNCTION Predefined (blinks during controller parameters configuration ) Programmable Programmable Programmable Programmable Programmable Page 29
C-PRO MEGA HARDWARE MANUAL 4 C-PRO EXP MEGA I/O expansion C-PRO EXP MEGA I/O expansion allows to expand the I/O of the controller. The expansion has the following inputs and outputs: • 4 analogic inputs for NTC / 0-20 mA /4-20 mA , probes • 8 low voltage digital inputs (12-24 VAC/DC) • 8 digital outputs (relays) : • 6 with 8 A res. @ 250 VAC (4 N.O./N.C. + 7 N.O.) • 2 with 5 A res. @ 250 VAC (2 N.O.).
C-PRO MEGA HARDWARE MANUAL 4.1 C-PRO EXP MEGA wiring layout The length of the connecting cables reported on chapter 3 is valid also for the I/O expansion. The C-PRO EXP MEGA wiring layout is here below reported showing the tables of the meaning of inputs and outputs . C-PRO EXP MEGA wiring layout The controller and C-PRO EXP MEGA power supplies have to be electrically insulated one from the other.
C-PRO MEGA HARDWARE MANUAL Lower board 12 VDC + 12 VDC power supply version Conn. Letter Description code C1-1 C1-2 VCC GND main card power supply (+13Vdc) Main power supply reference JD-1 JD-2 JD-3 JD-4 JD-5 JD-6 VDC AI 5 AI 6 AI 7 AI 8 GND power supply for active sensors (*1) analogic input 5, configurable (NTC, 0..20 mA, 4..20 mA) analogic input 6, configurable (NTC, 0..20 mA, 4..20 mA) analogic input 7, configurable (NTC, 0..20 mA, 4..20 mA) analogic input 8, configurable (NTC, 0..20 mA, 4..
C-PRO MEGA HARDWARE MANUAL Lower board 24 VAC/DC power supply version with built-in switching feeder Conn.
C-PRO MEGA HARDWARE MANUAL 5. C-PRO EXP MEGA Dimensions / Installations The C-PRO EXP MEGA dimensions are reported here below; all dimensions are in millimeters (inc). Sealed case version Open case version The open case version is available with fixed screw terminals only.
C-PRO MEGA HARDWARE MANUAL 6. Remote User interface The user interfaces allow to install a display and keyboard remotely far from the controller . “V-VIEW” user interface (with a alfanumeric 4 x 20 characters LCD display) can be connected to one of the CAN port of the C-PRO MEGA controller. On request a graphic 240 x 128 pixel LCD display (V-GRAPH) user interface is also available . 6.
C-PRO MEGA HARDWARE MANUAL The following table summarizes the keyboard button meaning: BUTTONS MAIN FUNCTION SECONDARY FUNCTION Predefined as UP Predefined as DOWN Predefined as LEFT Predefined as RIGHT Predefined as ESC Stand-By command Predefined as ENTER 1° programming level command Programmable Alarm reset / identification Programmable Programmable Programmable Programmable Programmable + + + Controller configuration parameters command 2° programming level command 3° programming level command
C-PRO MEGA HARDWARE MANUAL 6.1.2 V-VIEW wiring layout 6.1.3. V-VIEW specifications General specifications Safety standards references EN 60730-1 Purpose of the device Electronic control device connections To be integrated in equipment Plug-in terminal block 5mm pitch for conductors up to 2.
C-PRO MEGA HARDWARE MANUAL Type Serial CAN Communication Buzzer LCD Dispay Keyboard CAN V2.0B not optoisolated 2 wires + common, ISO 11898 standard 20K 50K 125K 500K Sconnectable terminals Physical Layer Baud rate (L max. = 10 m) Baud rate (L max. = 5 m) Baud rate (L max. = 2 m) Baud rate (L max. = 1 m) Connector Note: baud rate can be selected by parameter Note: The physical level of the CAN consists of a cable with twisted pair (both shielded and not shielded). The terminator's impedance is 120Ω.
C-PRO MEGA HARDWARE MANUAL 7 Accessories 7.1 C-PRO AL switching feeder C-PRO AL is a two output switching feeder able to provide the power supply to C-PRO MEGA programmable controllers. The range of the C-PRO AL input voltage can be between 18 and 60 Vac/dc , while the output voltage of feeder’s output is 13 Vdc (1,5 A) and 15 Vdc (0,15 A). C-PRO AL is available in 6 DIN modules housing dimensions for DIN rail mounting installation.
C-PRO MEGA HARDWARE MANUAL 7.1.1.
C-PRO MEGA HARDWARE MANUAL In the previous page, example of connection of C-PRO AL with C-PRO MEGA. With the same secondary of the transformer, is possible to feed both C-PRO AL and the C-PRO MEGA low voltage digital input (they work with 12-24 VAC/DC). It is preferable : • To connect the possible remote user interface to Local CAN (not optoinsulated) port (providing the remote user interface with the necessary 12 Vdc power supply) • To connect the possible expansion to the Wide CAN (optoinsulated) port.
C-PRO MEGA HARDWARE MANUAL 8 Configuration of the supplied analogic outputs signal C-PRO MEGA has four analogic outputs. Each analogic output can be configured to supply one of the following signal : • 0,5-10 V (called “voltage”) • 0-20 mA (called “current”) • 4-20 mA (called “current”).
C-PRO MEGA HARDWARE MANUAL or button to select the 11. Press and release 4-20 mA or 0-10 V). 12. Press and release 13. Repeat the selection for each analogic output “Type AO1 … AO4”. 14. Switch – off the controller wanted value button to confirm the selected choice. For a quick closing procedure: 8.1.2 Closing the analogic output configuration procedure 1. Press and release repeatedly button.
C-PRO MEGA HARDWARE MANUAL 9 CAN Connection C-PRO MEGA can be connected to other controllers, to expansion modules and to one or more user interfaces using either local or wide CAN serial port. The CAN bus uses the ISO 11898 standard, a balanced two-wire communication very similar to the RS 485 standard. Resistors with a recommended rating of 120-124 ohm have to be fitted at each end of the bus.
C-PRO MEGA HARDWARE MANUAL 9.1.1. Notes on the parameter of the controller relative to the CAN net configuration To log on the controller parameters configuration procedure relative to the analogic output act in the following way : Both for the remote or built-in user interface : 1. Ensure that the controller and the user interface are both switched on and no utilization is connected with the analogic output 2.
C-PRO MEGA HARDWARE MANUAL • • • “My Node” (represents the data sender ID ). “Network Node” (represents the receiver ID) Baud rate (represent the data transmissions speed; initially it can be useful to let this value set at “Auto”; in this way the device will try to connect a few time with different speed); Local CAN port baud rate can be set with “JMP4” jumper.
C-PRO MEGA HARDWARE MANUAL Hardware Manual C-PRO MEGA. 1.01 Versioni September 2007. Codice 114CPRMHWE01. File 114CPRMHWE01.pdf. This document is the exclusive property of Evco, whereby any reproduction or distribution is strictly forbidden, unless expressly directly authorised by Evco. Evco assume no responsibility in relation to the characteristics, technical data and any possible errors reported in this document or deriving from the use of the same.
HEADQUARTERS Evco Via Mezzaterra 6, 32036 Sedico Belluno ITALIA Tel. 0437-852468 Fax 0437-83648 info@evco.it www.evco.it SUBSIDIARIES Control France 155 Rue Roger Salengro, 92370 Chaville Paris FRANCE Tel. 0033-1-41159740 Fax 0033-1-41159739 control.france@wanadoo.fr Evco Latina Larrea, 390 San Isidoro, 1609 Buenos Aires ARGENTINA Tel. 0054-11-47351031 Fax 0054-11-47351031 evcolatina@anykasrl.com.ar Evco Pacific 59 Premier Drive Campbellfield, 3061, Victoria Melbourne, AUSTRALIA Tel.