PROGRAMMABLE CONTROLLERS FOR MONO AND BI-CIRCUIT COMPRESSOR PACKS UP TO 4 COMPRESSORS APPLICATION MANUAL CODE 144RACKNUE05
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL Important Read carefully these instructions before installation and use and follow all the directions for the installation and for the electrical connection; keep these instructions together with the tool for future consultation. The tool must be disposed of according to the local regulation regarding collection of electrical and electronic equipments.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL Contents 1 2 3 4 5 6 GENERALITIES............................................................................................................................................ 5 1.1 Description ............................................................................................................................................. 5 Applications.......................................................................................................
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 6.6.1 Rotation of the fans ........................................................................................................................ 63 6.6.2 Fan timings ..................................................................................................................................... 64 6.6.3 Safety inputs .................................................................................................................................
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 1 GENERALITIES 1.1 Description This application uses control units of C-PRO NANO and C-PRO MICRO line for management of a refrigerator compressor pack composed by one or two circuits with maximum number of 4 compressors.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL C-PRO NANO RACK C-PRO MICRO RACK Built-in version C-PRO MICRO RACK Blind version Page 6 C-PRO MICRO RACK Open version
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2 Applications It is possible connecting to the control unit a 6 relays expansion through IntraBus proprietor protocol It is supposed the management of three types of compressor pack: 1) Application 1: C-PRO NANO RACK or C-PRO MICRO RACK (for monocircuit compressor packs) Total of digital outputs = 6 Total of digital inputs = 5 Total of analogue inputs = 4 Total of analogue outputs = 2 PWM (+2 optional ones).
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.1 Application 1a: use of compressor pack) C-PRO NANO RACK (monocircuit According to default setting, C-PRO NANO RACK is configured to manage monocircuit refrigerator compressor packs; the uses shown in the drawing below just refer to default settings.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.2 Application 1b: use of C-PRO MICRO RACK (monocircuit compressor pack) According to default setting, C-PRO MICRO RACK is configured to manage monocircuit refrigerator compressor packs; the uses shown in the drawing below just refer to default settings.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.3 Application 2a: use of C-PRO NANO RACK with expansion of I/O C-PRO EXP MICRO (bi-circuit compressor pack with single condensation) According to default setting, C-PRO NANO RACK is configured to manage monocircuit compressor packs; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with single condensation.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.4 Application 2b: use of C-PRO MICRO RACK with expansion of I/O C-PRO EXP MICRO (bi-circuit compressor pack with single condensation). According to default setting, C-PRO MICRO RACK is configured to manage monocircuit compressor packs ; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with single condensation.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.5 Application 3a: use of C-PRO NANO RACK with expansion of I/O C-PRO EXP MICRO (bi-circuit compressor pack with separated condensation). According to default setting, C-PRO MICRO NANO is configured to manage monocircuit compressor packs ; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with separated condensation.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.6 Application 3b: use of C-PRO MICRO RACK with expansion of I/O C-PRO EXP MICRO (bi-circuit compressor pack with separated condensation). According to default setting, C-PRO MICRO RACK is configured to manage monocircuit compressor packs ; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with separated condensation.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.7 Electrical connections of control units Here follows the layout of control units connection with tables concerning the inputs and outputs meaning.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL Connector 1 of C-PRO NANO RACK: Connection for relay outputs ; in brackets the that is associated according to default setting Description Normally open contact relay n.4 (fan 2) Normally open contact relay n. 3 (fan 1) Common relay n.1,2,3,4 Normally open contact relay n.5 Normally open contact relay n.2 (compressor 2) Normally open contact relay n.1 (compressor 1) Common relay n.1,2,3,4 Common relay n.1,2,3,4 Common relay n.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL Connector 3: Connector for the anlogical output (optional, not available in the open versions) Conn.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL 2.8 C-PRO EXP MICRO electrical connection Here follows the layout of connection of C-PRO EXP MICRO expansion with tables concerning the inputs and outputs meaning. Consult the hardware manual for the references about the connection cables’ maximum lenght. C-PRO EXP MICRO connections Connector 1: Connection for relay outputs Conn. Abbreviation Description C1-1 DO7 Normally open contact relay n.7 C1-2 COMMON DO7 Common relay n.
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL C2-9 C2-10 12Vac (Power) 12Vdc C2-11 C2-12 C2-13 C2-14 C2-15 C2-16 PWM DI10 DI9 DI8 DI7 DI6 Power supply of the tool (12Vac/dc) Transducers’ power supply (50 mA max. not protected against short circuits) Pulses output for phase cut module Digital input n.10 Digital input n.9 Digital input n.8 Digital input n.7 Digital input n.6 Connettore 3: Connector for control unit device Conn.
3 Elements and fittings network 3.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 3.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 3.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 4 USER INTERFACE 4.1 Display and keyboard There are two interface typologies for the application: ⋅ a 4 display interface with 7 Built-In segments. ⋅ a remote 4 display interface with 7 segments. They both have 4 keys for navigation/editing of the pages and they are different in the display through icons (built-in) or in the display through led (remote) of some associated sites.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL In the keyboard there are 4 keys for pages navigation and values editing with the following meaning: - UP and DOWN: parameters modification in editing; otherwise menu and parameters shift. If we are in alarms pages display mode, everytime we press it, it makes all the active alarms shift, otherwise it shows the “none” default word in order to signalize the absence of alarms.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL - LP icon: it is active when the value of suction probe is displayed. If it flashes with alarm icon switched on, it indicates the intervention of low pressure alarms on suction circuit or suction probe not-connected. - HP icon: it is active when the value of discharging probe is displayed. If it flashes with alarm icon switched on, it indicates the intervention of high pressure alarms on discharging circuit or discharging probe not-connected.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Remote terminals V LEDi V WALL Panel version Wall version In the keyboard there are 4 keys for pages navigation and values editing with the following meaning: - UP and DOWN: parameters modification in editing; otherwise shift of the cursor. UP key, if it is pressed for about 2 seconds during the display of an alarm, allows the alarm reset.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL - - L4 = compressor leds: it identifies the status of the compressors. If it is switched on it means that at least one compressor is switched on, otherwidse it remains switched off. If it flashes it means that at least one compressor is switched on or in manual function. L6 = alarm led: it identifies the possible presence of alarms. If it is switched on, it means that there are alarms, otherwise it remains switched off.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Besides it is possible to see only the icons. In case of two-circuit machine, pressing UP key for about two seconds, it is possible to change over to alternate display of suction pressures of the two circuits. General Menu The general menu does not have any level and it is the point for entering all the other system’s menus.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Installer Menu The installer menu is of level 3, it is then necessary to insert the installer level or builder password in order to see/modify the parameters in this branch.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Constructor Menu The constructor menu is of level 4, it is necessary then to insert the constructor level password in order to see/modify the parameters in this branch. Besides it can be reached only from the machine in OFF status.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Last but not least, conditioned visibility allows to avoid showing plenty of parameters; the display will only show relevant configuration parameters. In the configuration parameters table, one has signalled configuration parameters which visibility depends on this function and the condition setting the visibility.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 5 Configuration parameters Here are listed all the parameters managed by the application. For each parameter it is also provided a brief description of the range of values that can be admitted, of units of measurement, of default value in charge and of the menu where it is.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 5.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL compressors’ inverter value of circuit 2 PM51.. .. PM54 PM61.. .. PM64 PM77 PM78 PM81 PM82 PM83 PM84 PM85 PM86 PSd2 PC12 PC13 PC14 PC16 PC17 PC18 PC19 PC20 PC21 PC22 PC23 PC24 PC25 PC26 Enable the fan’s manual/automatic function:(Manu: manual Auto: normal function One for each compressor.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL PC27 PC28 PF12 PF13 PF14 PF16 PF17 PF18 PF20 PF24 PF25 PF26 PF27 PF28 PC32 PC33 PC34 SpeedUp time for the inverter of circuit 1 compressors Time within which the inverter changes from minimum value to its maximum value for the neutral zone adjustments of circuit 1 compressors Minimum value of discharging setpoint of circuit 1 fans Maximum value of discharging setpoint of circuit 1 fans Set the regulation type for management of circuit 1 fans Integra
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL step of circuit 2 compressors (Neutral zone) PC43 Maximum time of release for the further step of circuit 2 compressors (Neutral zone) 60 0 999 Sec IS-R2 PC44 Differential for the inverter adjustment of circuit 2 compressors 0.5 0.0 20.0 Bar IS-R2 PC45 Offset in relation to the suction setpoint for inverter adjustment of circuit 2 compressors 0.0 -20.0 20.0 Bar IS-R2 PC46 Minimum value of the inverter of circuit 2 compressors 0.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL PF44 Differential for the inverter adjustment of circuit 2 fans 0.5 0.0 20.0 Bar IS-R2 PF45 Offset in relation to the suction setpoint for inverter adjustment of circuit 2 fans 0.0 -20.0 20.0 Bar IS-R2 PF46 Minimum value of the inverter of circuit 2 fans 0.0 0.0 100.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL PC71 PC72 PC74 PC75 PC76 PC78 Set compressors’ throttlings pressure (circuit 1) Set compressors’ throttlings pressure (circuit 2) Differential of compressors’ throttlings pressure Minimum time for compressors’ throttlings maintenance Throttling percentage value Compressors’ sideband steps overlapping factor (sideband) 22.0 PH03 PH04 Bar IS-C 22.0 PH03 PH04 Bar IS-C 4.0 0.1 10.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL PH05 PH07 PH08 PH09 PH10 PH11 PH12 PH13 PH14 PH15 PH17 PH18 PH19 PH20 PH21 PH23 PH24 PH25 PH26 PH31 Enable the machine switching on/off pressing ESC/Stand- by key Enable the machine switching on/off from digital output Enable the single circuit’s switching on/off from respective digital output Enable the machine switching on/off from supervisor Enable the single circuits’ switching on/off by supervisor Modbus address of the card Baud Rate of com
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL PH32 PH33 PH35 PH36 PH40 PH43 PH44 PH50 PH51 PH52 PA01 PA02 PA03 PA04 PA05 PA06 PA07 PA08 PA09 PA10 PA11 PA12 PA14 PA15 PA16 5: R410A 6: R507 Set the unit of measurement of temperature: 0: °Celsius 1: °Fahrenheit Set the unit of measurement of pressure: 0: Bar 1: psi Enable load losses compensation on suction line (neutral zone) 0: NO 1: YES Load losses compensation factor Set the display in pressure or temperature 0: Pressure 1: Temperature Set
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL PA17 PA18 PA19 PA20 PA21 PA22 PA23 PA25 PA26 PA27 PA28 Set the setpoint for high pressure alarm over suction probe of circuit 1 Set the differntial for high pressure alarm over suction probe of circuit 1 Set the setpoint for low pressure alarm over discharging probe of circuit 1 Set the differntial for low pressure alarm over discharging probe of circuit 1 Set the setpoint for high pressure alarm over discharging probe of circuit 1 Set the differntial f
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL PG46 HC01 HC02 HC03 HC04 Enable the inverter of fans of circuit 2 Set the digital output position for compressor 1 Or Set the inverter compressor consent position for circuit 1 (if circuit 1 inverter is enabled) Set the digital output position for compressor 2 Or Set the inverter compressor consent position for circuit 2 (if circuit 2 inverter is enabled) Set the digital output position for compressor 3 Or Set the inverter compressor consent positi
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL HC24 HC31 HC32 HF01 HF02 HF03 HF04 Set the digital output position for the throttling 2 of compr.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL associated with the alarm signals of circuit 1 is enabled) HA21 Set the position of the digital output associated with the alarm signals of circuit 1 0 0 6 (12) n CO-Hw Visibile if PG01 > 1 Hd01 Set the position of the digital input for the Global On/Off Switch 0 0 5(10) n CO-Hw (10 if expansion is enabled) Set the position of the digital input relative to the secondary setpoint for the management of the compressors 0 0 5(10) n CO-
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Hd24 Set the position of the digital input associated with the high pressure alarm on the discharge pressure regulator of circuit 2 0 0 5(10) n CO-Hw Hd25 Set the position of the digital input associated with the oil differential alarm for compressors alarm of the circuit 2 0 0 5(10) n CO-Hw Hd26 Set the position of the digital input associated with the common thermal alarm for the fans of circuit 2 0 0 5(10) n CO-Hw 1 0 5(10) n
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Set the position of the digital inputs associated with the thermal alarm for fan 4 PSd4 Constructor password expansion is enabled); visibility *2 0 -999 9999 n CO-Pa Note. Once the parameters of the machine have been configured and at each modification of the configuration parameters, it is advised to shut off and restart the system to allow the motherboard to correctly configure itself.. (*1) Conditioned visibility compressor.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6 ADJUSTMENTS 6.1 Configuration of the machine Using a wizard (Constructor menu), it is possible to configure the machine with help. The first choice involves the number of circuits (1 or 2) through the parameter PG01; in the case of a bi-circuit, the choice of condensation type, either singular or separate (PG30), becomes important as does the presence or absence of expansion (PG02).
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.2 Status of the machine and of the single circuits There are multiple procedures for turning on/shutting off the unit or the single circuit: 1) By using the appropriate On/Off button (function enabled by parameter PH05) Turning On – push the ESC button for about 2 seconds: if all other enabled conditions are present, the machine will go to “ON”. Shutting Off – push the ESC button for about 2 seconds: the machine will go to “OFF”.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.3 Adjustment of the compressors Checking the suction pressure of the compressors implies the management of the compressors to reach and maintain a certain operating pressure value: according to the type of check (sideband adjustment or neutral zone adjustment) and the use or lack thereof of the inverter for a finer adjustment, four types of adjustment are considered. 6.3.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Gradini Rilascio Max Gradini Inserimento Aspirazione PC78 % SP SP + BP Steps will be loaded at PC78% of the proportional band; the steps will be unloaded at 100 – PC78% of the proportional band. If for example PC78 has value 60%, the steps will be loaded between 60% of the proportional band and its maximum value (100%); steps will be unloaded between 40% of the proportional band and its minimum value (0%).
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL As we can see from the figure, the adjustment foresees the setting of certain timings within which, depending on the zone, the turn-on and shutdown requests for the various steps must be adjusted to work according to established time intervals. Based on the difference between the actual suction pressure value and the reference value, the times will vary proportionally according to the values set.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL The use of this adjustment on the principal compressor is not linked to the adjustment of the other compressors, since the two functions are independent from each other. Example: 4 compressors without inverter Example: 4 compressors with 1 inverter Steps Max steps Steps Max steps Pressure SP SP + BP Inverter 100.00 % Pressure SP SP + BP MinI Pressure SP + OFSI 6.3.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL If the request for a shutdown remains, all the compressors are shut down, one by one, and at the end the value of the inverter is brought to zero. If the MinI parameter has been set, at every turn-on the inverter will keep that value as the starting value. If the parameter for the speedUp time has been set, at every breakaway the inverter will assume the maximum value for the seconds described by this parameter.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL an alarm or that are in manual function mode and it is able to dynamically turn on other compressors if one or more are subject to a state of alarm. Through the PC01 parameter, the program is able to manage 4 types of rotation: FIFO, LIFO, FIFO + hours, LIFO + hours. 1) FIFO Follows the logic “First In First Out”, or in other words, the first compressor that turns on will then be the first that must shut off.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Example. 1 Turn-on : C1(3 hours) . C2(3 hours) . C3(3 hours) . C4(3 hours) Shutdown: C4(3 hours) . C3(3 hours) . C2(3 hours) . C1(3 hours) Example. 2 Turn-on : C1(1 hour) . C2(3 hours) . C3(3 hours) . C4(5 hours) Shutdown: C4(5 hours) . C3(3 hours) . C2(3 hours) . C1(1 hour) 6.4.2 Management of throttlings The program is capable of managing up to 4 throttled compressors.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.4.3 Protection timings Below, there is a list of all the timings related to the management of the compressors.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.4.5 Inverter configuration For each inverter used in the plant must be selected also the related digital output position for the command/consent at the inverter start; For the configuration the same parameters of the compressor digital outputs are used, parameters HC01, HC02, HC03, HC04.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Inverter consent with PWM In some applications it can be necessary to command the consent of the inverters with a PWM output configuring 0% or 100%.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Setpoint = 0.5 bar Proportional band = 2.0 bar Power Compressor 1 = 3 kW Power Compressor 2 = 5 kW Power Compressor 3 = 10 kW Measured Pressure (bar) 0.5 0.6 1.0 1.3 1.6 1.7 2.0 2.3 2.5 Power Required (kW) 0.9 4.5 7.2 9.9 10.8 13.5 16.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Disch.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.5 Adjustment of condensation The management of condensation foresees control through discharge pressure fans: according to the type of control (sideband control or neutral zone control) and according to the use or disuse of the inverter for a finer adjustment, four types of adjustment are considered. 6.5.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.5.2 Neutral zone adjustment This adjustment implies the definition of a neutral zone in which no decision of activation or deactivation is made, which means that there will be no requests for breakaways of any devices.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Inverter 100.00 % MinI Pressure SP + OFSI SP + OFSI + DI Based on the value measured by the discharge probe, the output of the regulator will assume different values. If the value measured by the probe is less than or equal to the value SP + OFSI, the output of the regulator will assume the value of 0.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL If the parameter for the speedUp time has been set, at every breakaway, the inverter will assume the maximum value for the seconds described by this parameter. 6.5.5 Single condensation (only bi-circuit) Single condensation makes it possible to perform the ventilation process through only one circuit. For this input, it is possible to set the type of resetting (automatic or manual) through the parameters.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Example with 4 fans. Turn-on : F1 . F2 . Shutdown: F1 . F2 . Turn-on : F3. F4. Shutdown: F3. F4. Turn-on : F1 . F2 . F3. F4. Shutdown: F1 . F2 . F3. F4. 2) LIFO It follows the “Last In First Out” logic, which means that the last fan turned on will be the first one to be shut down. Example. Turn-on : F1 . F2 . F3 . F4 Shutdown: F4 . F3 . F2 . F1 The turn-on order will always start from the C1 compressor.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Protection timings These times serve to protect the fans from the various breakaways to which they are subjected. PF07 – Minimum time between turn-ons of different fans. Establishes the minimum amount of time that must pass between the turn-on of one fan and the next. If it is set, it makes it possible to avoid simultaneous breakaways. PF08 – Minimum time between shutdowns of different fans.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.7 Various management issues 6.7.1 Digital input or supervisor setpoint variation It is sometimes important to reduce the energy consumption of the compressors or the noise level of the fans (for example at night).
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL Inverters When it is an inverter that must be manually forced, the procedure is slightly different.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 6.7.5 Restoration of default parameters Through the “Parameter restoration” procedure, it is possible to restore all the parameters of the system to the default values. This function is simple to activate by acting on the value of the appropriate parameter PH15 present in the Map menu, accessible only when the machine is turned off; setting it to “1”, the system will automatically see to the restoration of all parameters.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 7 DIAGNOSTICS The application is able to manage a series of alarms related to system compressors, fans, circuits and functions. Depending on the various types of alarm, it is possible to configure their resetting (if manual or automatic), a possible delay in signal and certain actions to perform in specific circumstances. When one or more alarms are active, the alarm icon on the screens blinks.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 7.2 Alarms Table A list of all the alarms that are managed by the application is given below. The order of presentation is the same as the order with which the alarms present themselves when they are active.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL AL32 AL37 AL42 AL47 AL12 AL22 AL62 ACC2 AFC2 ES07 ES08 AH01 High discharge pressure C2 High suction pressure C2 Low discharge pressure C2 Low suction pressure C2 High discharge pressure pressure regulator C2 Low suction pressure pressure regulator C2 Liquid level C2 Common oil differential C2 Common thermal fans C2 Environment probe broken or disconnected External probe broken or disconnected Hardware configuration alarm Auto Auto Auto Auto Set Auto Ma
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 7.3 Alarm relays The program has the possibility of managing up to three alarm relays. The activation of each of these devices is linked to the setting or lack thereof of the relative DO alarm position parameter. For activation, it is sufficient to set this value to a value that is different than zero; if the zero value is maintained, the alarm relay is not used.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 8 List of the MODBUS variables It is possible to check the application through a supervisor, using the Modbus protocol. The communication occurs through a serial TTL interface, which is already integrated in the controller; we suggest using the external TTL/RS-485 interface (the interface is not supplied with the instrument). The various parameters that are exported by the application in the three versions of the application are reported below.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 770 PackedAlarm2 0 0 65535 771 PackedAlarm3 0 0 65535 1025 1026 1027 1028 1029 1030 1031 OnOffBySuperv OnOffBySuperv_Circuit1 EnableSecSP_bySup_Cmp_Circuit1 EnableSecSP_bySup_Fan_Circuit1 OnOffBySuperv_Circuit2 EnableSecSP_bySup_Cmp_Circuit2 EnableSecSP_bySup_Fan_Circuit2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1281 StatusMachine 0 0 3 1282 StatusCircuit1 0 0 6 -145.0 -145.0 -145.0 -145.0 0 625.5 625.5 625.5 625.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 1288 PowerSupplied_Circuit1 0 0 100 1289 StatusCircuit2 0 0 6 0 0 1.0 0.0 0.0 15.0 0.0 0.0 1.0 0.0 0.0 15.0 0.0 0.0 2000.0 -145.0 -145.0 -145.0 -145.0 0 0 -145.0 -290.0 -290.0 -145.0 -290.0 -290.0 -145.0 -290.0 -290.0 -145.0 -290.0 -290.0 0.0 625.5 625.5 625.5 625.5 100 100 625.5 290.0 290.0 625.5 290.0 290.0 625.5 290.0 290.0 625.5 290.0 290.0 9999.0 0.0 0.0 9999.0 R/W 0.0 0.0 9999.0 R/W 0.0 0.0 9999.0 R/W 0.0 0.0 9999.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 1585 1586 1587 1588 1589 1590 1591 1592 1593 1594 1595 1596 1597 PM6x_V_suppStepsFan[2] PM6x_V_suppStepsFan[3] PM77_Forz_Fans_Inverter1 PM78_Forz_Fans_Inverter2 PM81_Calibration_SuctionC1 PM82_Calibration_SupplyC1 PM83_Calibration_SuctionC2 PM84_Calibration_SupplyC2 PM85_Calibration_EnvProbe PM86_Calibration_ExtProbe PM91_Last_maintenanceYEAR PM92_Last_maintenanceMONTH PM93_Last_maintenanceDAY 0 0 0.00 0.00 0.0 0.0 0.0 0.0 0.0 0.0 2006 1 1 0 0 0.00 0.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 1636 1637 1638 1639 1640 1641 1642 1643 1644 1645 1646 1647 1648 1649 1650 1651 1652 1653 60 0.5 0.0 0 10 0 0 22.0 22.0 4.0 2 50 0 0 0 0 0 0 0.0 -290.0 0.00 0 0 0 0 -145.0 -145.0 0.1 0 0 0 0 0 0 0 999 290.0 290.0 100.00 999 999 999 1 625.5 625.5 10.0 999 100 100 5000 5000 5000 5000 1654 PF01_Fan_Rotation_Type 0 0 3 1655 PF02_Fan_EnRegulationByCmp 0 0 1 2 2 1 1.0 25.0 0 0 0 -145.0 -145.0 999 999 4 625.5 625.5 0 0 1 600 0.5 1.0 10 0.5 0.
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 1690 1691 1692 1693 1694 1695 1696 1697 1698 PA02_En_Alarm_ManutHourFan PA03_HighPressureSuction_Delay PA04_ExpOffline_Delay PA05_LiquidLevel_Delay PA06_ProbeError_Delay PA07_LowPressureSupply_Delay PA08_LowPressureSuction_Delay PA09_ThermalCmp_Delay PA10_OilDiffCmp_Delay 0 1 5 90 5 30 30 0 10 0 0 0 0 0 0 0 0 0 1 999 999 999 240 999 999 999 999 1699 PA11_PressureSwitchSupply_ResetType 1 0 1 1700 PA12_ThermalCmp_ResetType 1 0 1 1701 PA14_OilD
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 1741 1742 1743 1744 1745 1746 1747 1748 1749 1750 1751 1752 1753 1754 1755 1756 1757 1758 1759 1760 1761 1762 1763 1764 1765 1766 1767 1768 1769 1770 1771 1772 1773 1774 1775 1776 1777 1778 1779 1780 1781 1782 1783 1784 1785 1786 1787 1788 1789 1790 1791 1792 1793 1794 1795 PH32_Temp_UM PH33_Press_UM PH35_EnSuctionCompensation PH36_OffsetSuctionCompensation PH40_Pressure_or_Temperature PH43_Select_UniversalAI3 PH44_Select_UniversalAI4 PH50_OnlyIcons PH
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL 1796 Hd15_Pos_DI_CommonOilDiff_Circuit1 Hd16_Pos_DI_CommonThermalOverloadFan_Cir 1797 cuit1 1798 Hd21_Pos_DI_Remote_OnOff_C2 1799 Hd22_Pos_DI_LiquidLevel_Circuit2 1800 Hd23_Pos_DI_LowPressSwitchSuction_Circuit2 1801 Hd24_Pos_DI_HighPressSwitchSupply_Circuit2 1802 Hd25_Pos_DI_CommonOilDiff_Circuit2 Hd26_Pos_DI_CommonThermalOverloadFan_Cir 1803 cuit2 1804 Hd4x_Pos_DI_ThermalOverloadCmps[0] 1805 Hd4x_Pos_DI_ThermalOverloadCmps[1] 1806 Hd4x_Pos_DI_ThermalOve
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL C-PRO NANO RACK and C-PRO MICRO RACK application manual 1.05 version , February 2011. Code 144RACKNUE05. File 144RACKNUE05.pdf. The present publication is the exclusive property of Evco, which absolutely prohibits its reproduction and publication, if not clearly authorized by Evco itself.
HEADQUARTERS Evco Via Mezzaterra 6, 32036 Sedico Belluno ITALY Tel. 0437-852468 Fax 0437-83648 info@evco.it www.evco.it FOREIGN HEADQUARTERS Control France 155 Rue Roger Salengro, 92370 Chaville Paris FRANCE Tel. 0033-1-41159740 Fax 0033-1-41159739 control.france@wanadoo.fr Latin Evco Larrea, 390 San Isidoro, 1609 Buenos Aires ARGENTINA Tel. 0054-11-47351031 Fax 0054-11-47351031 evcolatina@anykasrl.com.ar Pacific Evco 59 Premier Drive Campbellfield, 3061, Victoria Melbourne, AUSTRALIA Tel.