Instruction Manual
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 32
5.1 Parameters configuration list
Code Parameter description Default Min Max U.M. Menu Notes
SPC1
Set the setpoint value for the suction probe
of the compressors (circuit 1)
1.0 PC12 PC13 Bar UT-C1
PUC1
Set the offset value by digital input for the
use of compressors’ secondary setpoint
(circuit 1)
0.0 -20.0 20.0 Bar UT-C1
PUC4
Ses the offset value by supervision for the
use of compressors’ secondary setpoint
(circuit 1)
0.0 -20.0 20.0 Bar UT-C1
SPF1
Set the setpoint value for the discharging
probe of the fans (circuit 1)
15 PF12 PF13 Bar UT-C1
PUF1
It sets the offset value from digital input for
the use of fans’ secondary setpoint (circuit
1)
0.0 -20.0 20.0 Bar UT-C1
PUF4
Set the offset value by supervision for the
use of fans’ secondary setpoint (circuit 1)
0.0 -20.0 20.0 Bar UT-C1
SPC2
Set the setpoint value for the suction probe
of the compressors (circuit 2)
1.0 PC32 PC33 Bar UT-C2
Visibile if
PG01 > 1
PUC2
Set the offset value by digital input for the
use of compressors’ secondary setpoint
(circuit 2)
0.0 -20.0 20.0 Bar UT-C2
Visibile if
PG01 > 1
PUC5
Set the offset value by digital input for the
use of compressors’ secondary setpoint
(circuit 2)
0.0 -20.0 20.0 Bar UT-C2
Visibile if
PG01 > 1
SPF2
Set the setpoint value for the discharging
probe of the fans (circuit 2)
15 PF32 PF33 Bar UT-C2
Visibile if
PG01 > 1
PUF2
Set the offset value by digital input for the
use of fans’ secondary setpoint (circuit 2)
0.0 -20.0 20.0 Bar UT-C2
Visibile if
PG01 > 1
PUF5
Set the offset value by digital input for the
use of fans’ secondary setpoint (circuit 2)
0.0 -20.0 20.0 Bar UT-C2
Visibile if
PG01 > 1
PSd1 Modify the password on User level 0 -999 9999 UT
PM00
Set in tens the maximum limit of
compressors’ operation hours. Beyond this
limit the respective alarm will go off.
2000 0 9999
hours
x
10
MA-F
PM01 ..
.. PM04
Represent in tens the compressors’
operation hours. One for each compressor.
0 0 9999
hours
x
10
MA-F
Visibility
*1
PM40
Set in tens the maximum limit of fans’
operation hours. Beyond this limit the
respective alarm will go off.
2000 0 9999
hours
x
10
MA-F
PM41 ..
.. PM44
Represent in tens the fans’ operation hours.
One for each fan
0 0 9999
hours
x
10
MA-F
Visibility
*2
PM91
Set the last date when plant’s maintenance
has been done
2006 2000 2064 n MA-F
PM92
Set the last date when plant’s maintenance
has been done
1 1 12 n MA-F
PM93
Set the last date when plant’s maintenance
has been done
1 1 31 n MA-F
PM11 ..
.. PM14
Enable the compressor’s manual/automatic
operation:
Manu: manual
Auto: normal function
One for each compressor
Auto Auto (0)
Manu
(1)
- MA-M
Visibility
*1
PM21 ..
.. PM24
If it is in manual function, it sets the number
of steps to be forced to the compressor
One for each compressor
0 0 3 n MA-M
Visibility
*1
PM37
If it is in manual function, it forces the
compressors’ inverter value of circuit 1
0 0 100.0 % MA-M
Visibile if
PG12 = 1
PM38 If it is in manual operation, it forces the 0 0 100.0 % MA-M Visibile if