Instruction Manual

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 34
PC27
SpeedUp time for the inverter of circuit 1
compressors
0 0 999 Sec IS-R1
Visibile if
PG12 = 1
PC28
Time within which the inverter changes
from minimum value to its maximum value
for the neutral zone adjustments of circuit 1
compressors
10 0 999 Sec IS-R1
Visibile if
PG12 = 1
PF12
Minimum value of discharging setpoint of
circuit 1 fans
1.0 PH03 SPF1 Bar IS-R1
PF13
Maximum value of discharging setpoint of
circuit 1 fans
25.0 SPF1 PH04 Bar IS-R1
PF14
Set the regulation type for management of
circuit 1 fans
Sideband(
0)
Sideban
d (0)
Neutal
zone(1)
- IS-R1
PF16
Integral time of the sideband adjustment of
circuit 1 fans
600 0 999 Sec IS-R1
Visibile if
PF14 = 0
PF17
Proportional band for the sideband
adjustment of circuit 1 fans
0.5 0 20.0 Bar IS-R1
Visibile if
PF14 = 0
PF18
Value of the Zone for neutral zone
adjustment of circuit 1 fans
1.0 0 20.0 Bar IS-R1
Visibile if
PF14 = 1
PF20
Insertion / release time for the next fan in
neutral zone adjustment
10 0 999 Sec IS-R1
Visibile if
PF14 = 1
PF24
Differential for the inverter adjustment of
circuit 1 fans
0.5 0.0 20.0 Bar IS-R1
Visibile if
PG42 = 1
PF25
Offset in relation to the suction setpoint for
inverter adjustment of circuit 1 fans
0.0 -20.0 20.0 Bar IS-R1
Visibile if
PG42 = 1
PF26
Minimum value of the inverter of circuit 1
fans
0.0 0.0 100.0 % IS-R1
Visibile if
PG42 = 1
PF27
SpeedUp time for the inverter of circuit 1
fans
2 0 999 Sec IS-R1
Visibile if
PG42 = 1
PF28
Time within which the inverter changes
from minimum value to its maximum value
for the neutral zone adjustments of circuit 1
fans
10 0 999 Sec IS-R1
Visibile if
PG42 = 1
PC32
Minimum value of suction setpoint of
circuit 2 fans
0.1 PH01 SPC2 Bar IS-R2
Visible if
PG01 > 1
PC33
Maximum value of suction setpoint of
circuit 2 fans
2.5 SPC2 PH02 Bar IS-R2
Visible if
PG01 > 1
PC34
It sets the regulation type for management
of circuit 2 compressors
Neutral
zone (1)
Sideban
de (0)
Neutral
zone (1)
- IS-R2
Visible if
PG01 > 1
PC36
IT integral time of the sideband adjustment
of circuit 2 compressors
600 0 999 Sec IS-R2
Visible if
PG01 > 1
and
PC34 = 0
PC37
PB proportional band for the sideband
adjustment of circuit 2 compressors
0.5 0 20.0 Bar IS-R2
Visible if
PG01 > 1
and
PC34 = 0
PC38
Value of the Zone for neutral zone
adjustment of circuit 2 compressors
0.5 0 20.0 Bar IS-R2
Visible if
PG01 > 1
and
PC34 = 1
PC39
Differential for the neutral zone adjustment
of circuit 2, within which the calculation for
switching on/off of a further step varies
0.5 0 20.0 Bar IS-R2
Visible if
PG01 > 1
and
PC34 = 1
PC40
Minimum time of insertion for the further
step of circuit 2 compressors (Neutral zone)
20 0 999 Sec IS-R2
Visible if
PG01 > 1
and
PC34 = 1
PC41
Maximum time of insertion for the further
step of circuit 2 compressors (Neutral zone)
60 0 999 Sec IS-R2
Visible if
PG01 > 1
and
PC34 = 1
PC42 Minimum time of release for the further 10 0 999 Sec IS-R2 Visible if