Instruction Manual
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 38
PH05
Enable the machine switching on/off
pressing ESC/Stand- by key
Si No (0) Si (1) - IS-V
PH07
Enable the machine switching on/off from
digital output
No No (0) Si (1) - IS-V
PH08
Enable the single circuit’s switching on/off
from respective digital output
No No (0) Si (1) - IS-V
PH09
Enable the machine switching on/off from
supervisor
No No (0) Si (1) - IS-V
PH10
Enable the single circuits’ switching on/off
by supervisor
No No (0) Si (1) - IS-V
PH11 Modbus address of the card 1 1 247 n IS-V
PH12
Baud Rate of communication for the card
(1=2400, 2=4800, 3=9600, 4=19200)
3 1 4 n IS-V
PH13 ModBu parity (0=none, 1=Odd, 2=Even) 2 0 2 n IS-V
PH14 StopBit ModBus (0=1bit, 1=2bit) 0 0 1 n IS-V
PH15 Restore the default of parametes‘ factory No No (0) Si (1) -
IS-D
(MAP)
Wait that
the value
0 is reread
at the end
of
restoring
PH17
Set the logic of digital inputs used for
alarms management:
0: Normally open NO
1: Normally close NC
NC NO (0) NC (1) - IS-V
PH18
Set the logic of relays used for alarms
0: Normally openNO
1: Normally close NC
NO NO (0) NC (1) - IS-V
PH19
Set the logic of digital inputs used for the
management of the following functions:
- OnOff Remote global
- OnOff Remote circuits
- secondary setpoint of compressors
-secondary setpoint of fans
0: Normally open NO
1: Normally closet NC
NO NO (0) NC (1) - IS-V
PH20
Compressors inverter consent digital output
command logic
=0: Energized contact-100% consent
enabled
=1: Energized contact-100% consent
disabled
0 0 1 - IS-V
PH21
Fans inverter consent digital output
command logic
=0: Energized contact-100% consent
enabled
=1: Energized contact-100% consent
disabled
0 0 1 - IS-V
PH23
Set the habilitation of the probe for
detection of room temperature
0 = No 0 1 - IS-V
PH24
Set the habilitation of the probe for
detection of external temperature
0 = No 0 1 - IS-V
PH25
Set the habilitation of secondary setpoint
function by digital input
0 = No 0 1 - IS-V
PH26
Set the habilitation of secondary setpoint
function by supervisor
0 = No 0 1 - IS-V
PH31
Set the type of coolant used (temperature-
pressure conversion)
0: No coolant
1: R22
2: R134a
3: R404A
4: R407C
3
R404A
0 6 - IS-V