Instruction Manual

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 39
5: R410A
6: R507
PH32
Set the unit of measurement of temperature:
0: °Celsius
1: °Fahrenheit
0 (°C) 0 1 - IS-V
PH33
Set the unit of measurement of pressure:
0: Bar
1: psi
0 (Bar) 0 1 - IS-V
PH35
Enable load losses compensation on suction
line (neutral zone)
0: NO
1: YES
0 (NO) 0 1 - IS-V
PH36 Load losses compensation factor 0.2 0.1 5.0 Bar IS-V
PH40
Set the display in pressure or temperature
0: Pressure
1: Temperature
0 0 1 - IS-V
PH43
Set the type of A/3 universal analogue input
2: NTC
3: 0-20mA
4: 4-20mA
5: reserved
4
4-20mA
2 5 - IS-V
PH44
Set the type of A/4 universal analogue
2: NTC
3: 0-20mA
4: 4-20mA
5: reserved
4
4-20mA
2 5 - IS-V
PH50
Set the display with the icons only
0: NO
1: YES
1 (SI) 0 1 - IS-V
PH51
Set the display of numeric icons
0: NO
1: YES
1 (SI) 0 1 - IS-V
PH52
Set the display of Evco icon
0: NO
1: YES
1 (SI) 0 1 - IS-V
PA01
Enable the alarm of compressors’ operation
hours
No No (0) Si (1) - IS-S
PA02 Enable the alarm of fans’ operation hours No No (0) Si (1) - IS-S
PA03
Set the activation delay of high pressure
suction alarms
1 0 999 Sec IS-S
PA04 Set the detection delay of expansion alarm 5 0 999 Sec IS-S
PA05 Set the activation delay of liquid level alarm 90 0 999 Sec IS-S
PA06
Set the detection delay of the alarms over
suction and discharging probes
5 0 240 Sec IS-S
PA07
Set the activation delay of low pressure
discharging alarm
30 0 999 Sec IS-S
PA08
Set the activation delay of low pressure
suction alarms
30 0 999 Sec IS-S
PA09
Set the activation delay of compressor’s
thermal alarm
0 0 999 Sec IS-S
PA10
Set the activation delay of common
diffrerential oil alarm and for compressors
10 0 999 Sec IS-S
PA11
Set the rearmament type for high pressure
discharging alarm
M A (0) M (1) - IS-S
PA12
Set the rearmament type for compressor’s
thermal alarm
M A (0) M (1) - IS-S
PA14
Set the rearmament type for compressor’s
differential oil
M A (0) M (1) - IS-S
PA15
Set the setpoint for low pressure alarm over
suction probe of circuit 1
0.5 PH01 PA17 Bar IS-S
PA16
Set the differntial for low pressure alarm
over suction probe of circuit 1
0.5 0.0 20.0 Bar IS-S