PA17
Set the setpoint for high pressure alarm over
suction probe of circuit 1
4.0 PA15 PH02 Bar IS-S
PA18
Set the differntial for high pressure alarm
over suction probe of circuit 1
0.5 0.0 20.0 Bar IS-S
PA19
Set the setpoint for low pressure alarm over
discharging probe of circuit 1
2.0 PH03 PA21 Bar IS-S
PA20
Set the differntial for low pressure alarm
over discharging probe of circuit 1
0.5 0.0 20.0 Bar IS-S
PA21
Set the setpoint for high pressure alarm over
discharging probe of circuit 1
20.0 PA19 PH04 Bar IS-S
PA22
Set the differntial for high pressure alarm
over discharging probe of circuit 1
1.0 0.0 20.0 Bar IS-S
PA23
Set the rearmament type for fan’s thermal
alarm
M A (0) M (1) - IS-S
PA25
Set the setpoint for low pressure alarm over
suction probe of circuit 2
0.5 PH01 PA27 Bar IS-S
Visible if
PG01 > 1
PA26
Set the differntial for low pressure alarm
over suction probe of circuit 2
0.5 0.0 20.0 Bar IS-S
Visible if
PG01 > 1
PA27
Set the setpoint for high pressure alarm over
suction probe of circuit 2
4.0 PA25 PH02 Bar IS-S
Visible if
PG01 > 1
PA28
Set the differntial for high pressure alarm
over suction probe of circuit 2
0.5 0.0 20.0 Bar IS-S
Visible if
PG01 > 1
PA29
Set the setpoint for low pressure alarm over
discharging probe of circuit 2
2.0 PH03 PA31 Bar IS-S
Visible if
PG01 > 1
and
PG30 = 0
PA30
Set the differntial for high pressure alarm
over discharging probe of circuit 2
0.5 0.0 20.0 Bar IS-S
Visible if
PG01 > 1
and
PG30 = 0
PA31
Set the setpoint for high pressure alarm over
discharging probe of circuit 2
20.0 PA29 PH04 Bar IS-S
Visible if
PG01 > 1
and
PG30 = 0
PA32
Set the differntial for high pressure alarm
over discharging probe of circuit 2
1.0 0.0 20.0 Bar IS-S
Visible if
PG01 > 1
and
PG30 = 0
PSd3 Set the password of Installer level 0 -999 9999 n IS-V
PG01 Set the number of circuits of the machine 1 1 2 n CO-W
PG02 Enable the presence of the expansion 0 = No No (0) Si (1) - CO-W
PG03
Enable the management of different
compressors with different power
0 = No No (0) Si (1) - CO-W
PG04
Set the number of throttlings for each
compressor
0 0 2 n CO-W
PG05 Set the thermal security of the compressors 1 = Si 0 1 - CO-W
PG11 Set the number of compressors of circuit 1 2 0 4 n CO-W
PG12
Enable the inverter of compressors of circuit
1
0 = No No (0) Si (1) - CO-W
PG15 Set the number of compressors of circuit 2 0 0 4 n CO-W
Visible if
PG01 > 1
PG16
Enable the inverter of compressors of circuit
2
0 = No No (0) Si (1) - CO-W
Visible if
PG01 > 1
PG30
Set the singular condensation for the group
of the fans
0 = No 0 1 - CO-W
PG32 Enable the thermal security of the fans 1 = Si 0 1 - CO-W
PG41 Set the number of fans of circuit 1 2 0 4 n CO-W
PG42 Enable the fans' inverter of circuit 1 0 = No No (0) Si (1) - CO-W
PG45 Set the number of fans of circuit 2 0 0 4 n CO-W
Visible if
PG01 > 1
and
PG30 = 0