7.2 Alarms Table
A list of all the alarms that are managed by the application is given below. The order of presentation is the same
as the order with which the alarms present themselves when they are active.
Code Description of the alarms Type Consequence Notes
EN01 Communication expansion error Auto Visualization Delay able to be set
ES01 Suction probe C1 broken or disconnected Auto
- Num. comp. ON
able to be set
- Inverter forced to
100% (if required and
if the only compressor
in the circuit)
Delay able to be set
ES02 Discharge probe C1 broken or disconnected Auto
- Num. fan ON able to
be set
- Inverter forced to
100% (if required and
if the only fan in the
circuit)
- OFF throttling HP
circuit 1 (if enabled)
Delay able to be set
ES03 Suction probe C2 broken or disconnected Auto
- Num. comp. ON
able to be set
- Inverter forced to
100% (if required and
if the only compressor
in the circuit)
Delay able to be set
ES04 Discharge probe C2 broken or disconnected Auto
- Num. fan ON able to
be set
- Inverter forced to
100% (if required and
if the only fan in the
circuit)
- OFF throttling HP
circuit 2 (if enabled)
Delay able to be set
AC21 Thermal compressor 1 Set OFF comp. 1 Delay able to be set
AC22 Thermal compressor 2 Set OFF comp. 2 Delay able to be set
AC23 Thermal compressor 3 Set OFF comp. 3 Delay able to be set
AC24 Thermal compressor 4 Set OFF comp. 4 Delay able to be set
AC01 Hours of operation compressor 1 Auto Visualization
AC02 Hours of operation compressor 2 Auto Visualization
AC03 Hours of operation compressor 3 Auto Visualization
AC04 Hours of operation compressor 4 Auto Visualization
AF21 Thermal fan 1 Set OFF fan 1
AF22 Thermal fan 2 Set OFF fan 2
AF23 Thermal fan 3 Set OFF fan 3
AF24 Thermal fan 4 Set OFF fan 4
AF01 Hours of operation fan 1 Auto Visualization
AF02 Hours of operation fan 2 Auto Visualization
AF03 Hours of operation fan 3 Auto Visualization
AF04 Hours of operation fan 4 Auto Visualization
AL31 High discharge pressure C1 Auto ON all fans
AL36 High suction pressure C1 Auto ON all comp. Delay able to be set
AL41 Low discharge pressure C1 Auto OFF all fans Delay able to be set *
AL46 Low suction pressure C1 Auto OFF all comp. Delay able to be set *
AL11 High discharge pressure pressure regulator C1 Set OFF all comp.
AL21 Low suction pressure pressure regulator C1 Auto OFF all comp. Delay able to be set *
AL61 Liquid level C1 Manu Visualization Delay able to be set
ACC1 Common oil differential C1 Set Visualization Delay able to be set
AFC1 Common thermal fans C1 Set Visualization