8 List of the MODBUS variables
It is possible to check the application through a supervisor, using the Modbus protocol. The communication
occurs through a serial TTL interface, which is already integrated in the controller; we suggest using the
external TTL/RS-485 interface (the interface is not supplied with the instrument).
The various parameters that are exported by the application in the three versions of the application are reported
below.
Modbus Table
REGISTER VARS LIST
Id Name Value Min Max Description Mode
257 PackedDI 0 0 65535
bit00=DI01,
bit01=DI02,
bit02=DI03,
bit03=DI04,
bit04=DI05,
bit05=DI06,
bit06=DI07,
bit07=DI08,
bit08=DI09,
bit09=DI10,
bit10=free,
bit11=free,
bit12=free,
bit13=free,
bit14=free,
bit15=free
R/W
385 PackedDO 0 0 65535
bit00=DO01,
bit01=DO02,
bit02=DO03,
bit03=DO04,
bit04=DO05,
bit05=DO06,
bit06=DO07,
bit07=DO08,
bit08=DO09,
bit09=DO10,
bit10=DO11,
bit11=DO12,
bit12=free,
bit13=free,
bit14=free,
bit15=free
R/W
513 AI_Pressure_SuctionC1 - - - Bar R/W
514 AI_Pressure_SupplyC1 - - - Bar R/W
515 AI_Pressure_SuctionC2 - - - Bar R/W
516 AI_Pressure_SupplyC2 - - - Bar R/W
517 AI_EnvironmentProbe - - - _C R/W
518 AI_ExternalProbe - - - _C R/W
641 CmpInverter_Circuit1 0.00 0.00 100.00 % R/W
642 FanInverter_Circuit1 0.00 0.00 100.00 % R/W
643 CmpInverter_Circuit2 0.00 0.00 100.00 % R/W
644 FanInverter_Circuit2 0.00 0.00 100.00 % R/W
769 PackedAlarm1 0 0 65535
bit00=EN01,
bit01=ES01,
bit02=ES02,
bit03=ES03,
bit04=ES04,
bit05=free,
R/W