Retarder proofing controller specifications CT1SA0040101 CT1SA0040301 Vers. 1.11 Stop leavening specifications CT1SA0040101 Vers. 1.
Index 1. CONNECTION DIAGRAM _________________________________________________________ 3 1.1. Power Basic Connections ______________________________________________________ 3 1.2. Interface connections _________________________________________________________ 4 2. USER INTEFACE ________________________________________________________________ 4 2.1. Keys _______________________________________________________________________ 4 3.
1. CONNECTION DIAGRAM 1.1.
1.2. Interface connections RS 485 PWM - - + LCD Sw6 Sw1 Sw5 Sw2 Sw3 Sw4 PWM terminal is a 0/10 Volt (1 kHz) output used for the phase cut control of the evaporator fans. This control is enabled by a parameter. For more details about its functioning see paragraphs 16.4 and 23.2. 2. USER INTEFACE 2.1. Keys Stop leavening specifications CT1SA0040101 Vers. 1.
3. GENERAL DESCRIPTION This card provides the stop-rising cell control. Some automatic programs, a manual program and a cell pre-cooling cycle are available. Each automatic program consists of five phases: stop rising, preservation, awakening, rising and slowing down. The manual program consists of three phases: cooling, heating and climatization. 4. POWER SUPPLY When the card is on, the string “EVCO s.r.l.
7.
8. MANUAL CYCLE The manual cycle consists of the following three phases: • cooling • heating • climatization. Each phase is independent and no automatic switch from a phase to another phase is available. When the machine is in standby mode, press the MENU key and select the MANUAL menu by way of the INCREASE and DECREASE keys, as follows: Menu 01 Manual Press ENTER to access the Manual Cycle setting mode. By way of the INCREASE and DECREASE keys, you can switch from a phase to another.
9. AUTOMATIC CYCLE There are 7 programs available, P01… P07, and each automatic cycle consists of the following five phases: • stop rising • preservation • awakening • rising • slowing down At the end of each phase, the next phase will start automatically. When the machine is in standby mode, press the MENU key and select the AUTOMATIC menu by way of the INCREASE and DECREASE keys, as follows: Menu 02 Automatic Press ENTER to access the automatic cycle selection mode.
P2 Rising 13:50 29°C P2 Rising 13:50 28°C 80% 80% Press ENTER to confirm. The number will stop blinking and you can now modify the humidity setpoint (if present): P2 Rising 13:50 28°C P2 Rising 13:50 28°C 78% 75% Press ENTER to confirm. The number will stop blinking. Use the INCREASE and DECREASE buttons to select the other phases and modify their setpoints. Press MENU to save the program and return to the previous menu. Press the START/STOP key to start the program.
F4 = slowing down Press the MENU key or wait for 10 seconds to return to the previous screen. Press MENU to see the status of INPUT/OUTPUT: Press MENU or wait for 5 seconds to return to the previous screen. Press ENTER to display date and time: 08/02/2007 Mar 17:35 Press MENU or wait for 5 seconds to return to the previous screen. C D E R V H U 1 0 0 1 1 0 0 Press the START/STOP key at any time to stop the cycle. The cycle will remain selected. Stop leavening specifications CT1SA0040101 Vers. 1.
. PRE-COOLING CYCLE You can run a pre-cooling cycle before executing any manual or automatic cycle. While the machine is in standby mode, press the MENU key and select the COOL menu using the INCREASE and DECREASE keys: Menu 03 Cool Press ENTER to access the temperature SetPoint change mode, as follows: SetTemperature -12°C Press ENTER to access the change mode. The value in question will start blinking.
. START DEFROST While the card is in standby mode you can run a defrost cycle. While the machine is in standby mode, press the MENU key and select the DEFROST menu using the INCREASE and DECREASE keys: Menu 04 Defrost Press ENTER to access the defrost request. Start? No Ok Press ENTER to exit the menu. No defrost will start. Press INCREASE to start a defrost cycle. 13.
Press MENU to return to the Home Menu. 15. LANGUAGE SELECTION While the machine is in standby, press MENU and select the Language menu using the INCREASE e DECREASE keys: Menu 07 Language Press ENTER. The display will show this message, in the first language available: Language Italiano Use the INCREASE and DECREASE keys to access the other languages. When the desired language appears on the display, press ENTER to confirm it or the MENU key to exit without changing the configuration.
16. SETUP MENU While the machine is in standby, press MENU and select the SETUP menu using the INCREASE and DECREASE keys: Menu 08 Setup When you press ENTER, you will be asked to enter the necessary password to access the setup submenus. Set Password 0 Select your password using the INCREASE and DECREASE keys and press ENTER. The default password is -19. If your password is correct, the first submenu will be displayed; otherwise you will exit from the menu. Press MENU to return to the Home Menu.
16.1. Parameters Press ENTER to access the parameter setup mode. The first line of the display shows the first parameter with its current value and its unit of measurement. P01 = -5°C Use the INCREASE and DECREASE keys to scroll through all the control parameters. Press ENTER to access the parameter change: P01 = -5°C -5 Use the INCREASE and DECREASE keys to change the parameter value. Press ENTER to confirm. Press the MENU key to go back to the Home Menu. 16.2.
.3. Default parameter reset Press ENTER to access the request for the default parameter reset. Restore? No Ok Press ENTER to exit the menu without resetting the parameters. Press the INCREASE key to reset the parameters. 16.4. Fan speed adjustment Press ENTER to access the fan speed adjustment function, where you can select the minimum and maximum speed and the minimum speed during the dehumidification phase (present only if the humidity probe has been selected).
. STEAM GENERATOR There is an output available to activate a steam generator. This output will be switched on for every phase requiring the humidification phase, apart from any P32 parameter value (selection of the humidification mode). If parameter P72 has value 0, opening the door will result in no effect; if parameter P72 has value 1, when the door is opened the steam generator will be switched off.
T On P33 T On P33 Inizio fase Where T On is the preset number of minutes of activation. Humidity injection is inhibited if the temperature in the cell is lower than the value determined by parameter P31 for both the automatic and manual cycles. 18.2. Humidification with humidity probe You can enable the humidity probe by setting parameter P32 = zero. The humidifier output switching on/off follows the following curve.
bp ist is the proportional adjustment band (parameter P39) is the humidification adjustment hysteresis (parameter P37) This function is always active during the awakening, rising and slowing down phases, but it can also be enabled for the stop and preservation phases by way of parameter P36. Regarding the manual cycle, the humidification is only active during the heating and climatization phase. In case the temperature in the cell is lower than parameter P31, the humidification function will be disabled.
19. DEHUMIDIFICATION This function is always active when the humidity probe is enabled. By setting parameter P32 = zero, the humidity probe will be enabled. Dehumidification occurs by using the solenoid valve and the compressor switching on or by setting parameter P71 = 2, when output K3 can be used to control a humidity extraction fan or a dehumidifier.. 19.1. Dehumidification with compressor This type of dehumidification is possible when parameter P71 is different from 2.
Case 2 Setpoint Sonda Umidità Setpoint+zm+ist Setpoint+zm Setpoint tempo On Elettrovalvola Off P44 On Compressore Off P29 The solenoid valve is switched on for a period of time determined by parameter P44.
19.2. Dehumidification without compressor If parameter P71 is set at 2, when the humidity probe exceeds the preset setpoint output K3 is activated for the dehumidification, as illustrated in the graph below. Setpoint Sonda Umidità Setpoint+zm+ist Setpoint+zm Setpoint tempo On Deumidificatore Off Stop leavening specifications CT1SA0040101 Vers. 1.
20. CELL TEMPERATURE ADJUSTMENT Refer to the following graphic for the resistance and compressor switching on/off. Both compressor and resistance activation are always enabled for all phases.
Compressor activation may be enforced at the beginning of the awakening and rising phases; the duration of such enforced activation is determined by parameter P29. Compressor activation is subject to the safety times (parameters P26, P27 and P28) 21. SOLENOID VALVE Only present if P71 = 0. When P71 = 0, P44 must be configured correctly.
23.2. Phase cut control (P45 = 1) Refer to the following graphic regarding the fans.
• alternatively, when the evaporator probe is higher than parameter P60. All defrost cycles will be interrupted when passing from the preservation phase to the awakening phase of an automatic cycle. At the end of the defrost cycle, you must wait for the end of the dripping time (parameter P63) before switching the compressor on, and for the end of the fan stop time (parameter P63+P64) before switching the fans on.
ALL Evap High T Qualsiasi ciclo in corso viene bloccato e tutte le uscite disattivate. Il buzzer si può tacitare premendo qualsiasi tasto. Alla scomparsa dell’errore premere il tasto ON-STANDBY per riarmare la scheda. Humidity probe A probe breakdown causes a humidity probe breakdown alarm the buzzer will sound and the following alarm word will be blinking on display: ALL HumiditySensor The ongoing cycle will be interrupted and all outputs will be switched off. Press any key to silence the buzzer.
RTC malfunction In case of RTC malfunction, an RTC alarm will be shown; the buzzer will sound and the following alarm message will start blinking on display: ALL RTC The ongoing cycle will be interrupted and all outputs will be switched off. Press any key to silence the buzzer. Access the Time Set menu and set the RTC current values: the card will return to the standby mode.
26. CONFIGURATION PARAMETERS 26.1.
P36 P37 P38 P39 P40 P41 P42 P43 P44 Enables the humidification cycle during the stop phases of rising and preservation phases 0 = disabled 1 = enabled Hysteresis for humidification Humidification dead zone Proportional Adjustment Band for Humidification Cycle time for Humidification Proportional Adjustment Time base for Cycle Time in proportional regulation humidifying 0 = seconds 1 = minutes Dehumidification hysteresis Dehumidification dead zone Duration of Dehumidification attempt with solenoid valve --
P71 P72 P73 P74 P75 P79 P80 P81 P82 P83 P84 P85 P86 K3 management: 0 = solenoid valve; 1= light; 2 = dehumidification Compressor management with door open: 0 = no effect; 1 = switch off compressor Defrost mode: 0 = resistances; 1 = hot gas Evaporator high temperature alarm Enable evaporator high temperature alarm: 0 = not enabled; 1= enabled Maximum evaporator fans speed in heating Maximum evaporator fans speed in air conditioning Maximum evaporator fans speed in block Maximum evaporator fans speed in pres
27. APPENDIX 27.1. General Description of the Synoptic Using the serial RS485 communication port you can connect a synoptic which will display temperature and humidity in the cell and the status of the ongoing program.
Code EVC25T007XXX01 DY3 DY2 DL9 DL11 DL10 DL12 DL13 DL1 DY1 DL8 DL2 DL4 DL5 DL6 DL7 DY4 DL3 Temperature/humidity display (DY1, DY2, DY3) H13 mm and synoptic SOFT. Code EVC25T007XXX03 DY3 DY2 DL9 DL10 DL11 DL12 DL13 DL1 DY1 DL8 DL2 DL3 DL4 DL5 DL6 DL7 DY4 Temperature/humidity display (DY1, DY2, DY3) H13 mm and synoptic HARD. Stop leavening specifications CT1SA0040101 Vers. 1.
115,00 mm 27.2. Dimensions 320,00 mm 27.3. Electric Connection 9 8 1 5 4 3 2 1 1-2 Buzzer expansion 3 RS 485 + 4 RS 485 – 5 RS 485 RIF 8-9 Power supply 230Vac Stop leavening specifications CT1SA0040101 Vers. 1.
27.4. Visualization DISPLAY DY1 Displays the temperature in the cell. This is on during the cooling phase of a manual cycle, in the locking phase of the rising and during the preservation phase of an automatic cycle. DISPLAY DY2 Displays the relative humidity in the cell. It will remain on during all phases which require humidity control. DISPLAY DY3 Displays the temperature in the cell.
DL10 on, DL11 blinking during rising phase if the temperature setpoint was not reached. DL10, DL11 on during a rising phase if the temperature setpoint was reached. Slowing down DL11, DL12, DL13 on during slowing down phase configuration. DL12 on and DL13 off during slowing down phase if the temperature setpoint is equal to or higher than the temperature setpoint of the rising phase. DL12 off and DL13 on if the temperature setpoint is lower than the preset temperature setpoint for the rising phase.