26. CONFIGURATION PARAMETERS
26.1. List of Parameters
NAME DESCRIPTION MIN MAX DEF UNIT
General Configurations
P1
Display selection if power on
0 = none
1= EVCO s.r.l.
0 1 1
---
P2 0 = Celsius 1 = Fahrenheit 0 1 0 ---
P3 Cell probe offset -15 15 0 °C
P4 Evaporator probe offset -15 15 0 °C
P5 Humidity probe lower threshold 0 P6 0 %
P6 Humidity probe upper threshold P5 200 100 %
P7
Input polarity for door contact
0 = NC
1 = NO
0 1 0
---
P8
LV input polarity for thermostat
0 = NC
1 = NO
0 1 1
---
P9 Power down duration for automatic program reset 1 60 15 minutes
P10
Selection after power down for automatic program
0 = an automatic cycle starts again only if power down is less than P9 minutes
1 = an automatic cycle always starts again
0 1 1
---
P11 Power down duration for manual program reset 1 60 15 minutes
P12
Status selection after power down for the manual program
0 = a manual cycle starts again only if power down is less than P11 minutes
1 = a manual cycle always starts again
0 1 1
---
Setpoint
P13 Cold Min setpoint -30 P14 -3 °C
P14 Cold Max setpoint P13 90 15 °C
P15 Cold hysteresis 2 10 3 °C
P16 Cold dead zone for refrigeration, stop and preservation 0 10 1 °C
P17 Cold dead zone for heating, awakening and rising 0 10 3 °C
P18 Cold dead zone for climatization and slowing down 0 10 1 °C
P19 Hot Min setpoint 0 P20 0 °C
P20 Hot Max setpoint P19 90 35 °C
P21 Hot hysteresis 2 10 3 °C
P22 Hot dead zone for heating, awakening and rising 0 10 1 °C
P23 Hot dead zone for climatization and slowing down 0 10 3 °C
P24 Number of steps for resistance adjustment in the awakening phase 1 10 3 ---
P25 Number of steps for resistance adjustment in the rising phase 1 10 3 ---
Compressor Timing
P26 Delay between two successive compressor activations 0 60 2 minutes
P27 Delay between compressor activation and switch-off 0 60 2 minutes
P28 Compressor switch-on delay from power on 0 255 2 minutes
P29
Compressor enforced switching on duration at the awakening, rising and slowing
down phase start
0 60 0
minutes
Resistance Timing
P30 Resistance activation minimum time 0 255 0 seconds
Humidification and dehumidification
P31 Cell temperature lower limit for humidification/dehumidification 0 90 10 °C
P32
Humidity control mode
0 = with humidity probe
1 = time cycles based on the setup percentage
2 = one-minute steps
0 2 0
__
P33 Pause time if P32 = 2 0 60 10 minuts
P34 Humidification cycle duration if P32 = 1 30 600 60 seconds
P35 Max. humidification time if P32 = 1 0 P34 30 seconds