Manual
Stop leavening specifications
CT1SA0040101
Vers. 1.11 30/36
P36
Enables the humidification cycle during the stop phases of rising and
preservation phases
0 = disabled
1 = enabled
0 1 0
---
P37 Hysteresis for humidification 1 100 5 %
P38 Humidification dead zone 0 100 2 %
P39 Proportional Adjustment Band for Humidification 0 20 10 %
P40 Cycle time for Humidification Proportional Adjustment 1 255 30 seconds/minutes
P41
Time base for Cycle Time in proportional regulation humidifying
0 = seconds
1 = minutes
0 1 0
---
P42 Dehumidification hysteresis 1 100 5 %
P43 Dehumidification dead zone 0 100 13 %
P44 Duration of Dehumidification attempt with solenoid valve 1 255 1 seconds
Fans
P45
Evaporator Fan Proportional Adjustment Enabling
0 = ON/OFF adjustment
1 = proportional adjustment
0 1 0
--
P46
Evaporator fan operation for rising stop
0 = simultaneous operation
1 = continuous operation
0 1 0
--
P47
Evaporator fan operation for preservation
0 = simultaneous operation
1 = continuous operation
0 1 0
--
P48
Evaporator fan operation for awakening
0 = simultaneous operation
1 = continuous operation
0 1 1
--
P49
Evaporator fan operation for rising
0 = simultaneous operation
1 = continuous operation
0 1 1
--
P50
Evaporator fan operation for slowing down
0 = simultaneous operation
1 = continuous operation
0 1 1
--
P51
Evaporator fan operation for refrigeration
0 = simultaneous operation
1 = continuous operation
0 1 0
--
P52
Evaporator fan operation for heating
0 = simultaneous operation
1 = continuous operation
0 1 1
--
P53
Evaporator fan operation for climatization
0 = simultaneous operation
1 = continuous operation
0 1 1
--
P54 Evaporator fan off delay in simultaneous operation 0 255 1 minutes
P55 Evaporator fan working time in simultaneous operation 0 255 3 minutes
P56 Evaporator fan pause time in simultaneous operation 0 255 1 minutes
P57 Evaporator fan minimum speed 0 100 0 %
P58 Evaporator fan speed during pre cooling cycle P57 100 100 %
P59 Evaporator fan minimum speed during dehumidification P57 100 20 %
Defrost
P60 Evaporator temperature for defrost end -40 99 2 °C
P61
Time between two consecutive defrost cycles
0 = no defrost will be repeated
0 10 6
ore
P62 Defrost cycle max. duration 1 120 30 minutes
P63 Dripping time 0 30 2 minutes
P64 Fan status during the defrost cycle 0 1 0 --
P65 Fan stop duration after dripping 0 15 3 minutes
Cooling
P66 Minimum setpoint for cooling -30 P67 -3 °C
P67 Maximum setpoint for cooling P66 30 10 °C
P68 Cooling preset P66 P67 2 °C
Program setting and change
P69 Enable program setting 0 1 1 --
P70 Enable program change 0 1 1 --