Stop leavening specifications
CT1SA0040101
Vers. 1.11 31/36
P71 K3 management: 0 = solenoid valve; 1= light; 2 = dehumidification 0 2 1 --
P72
Compressor management with door open: 0 = no effect; 1 = switch off
compressor
0 1 0 --
P73 Defrost mode: 0 = resistances; 1 = hot gas 0 1 1 --
P74 Evaporator high temperature alarm 0 70 55 °C
P75 Enable evaporator high temperature alarm: 0 = not enabled; 1= enabled 0 1 1 --
P79 Maximum evaporator fans speed in heating P57 100 100 %
P80 Maximum evaporator fans speed in air conditioning P57 100 100 %
P81 Maximum evaporator fans speed in block P57 100 100 %
P82 Maximum evaporator fans speed in preservation P57 100 100 %
P83 Maximum evaporator fans speed in awaking P57 100 100 %
P84 Maximum evaporator fans speed in rising P57 100 100 %
P85 Maximum evaporator fans speed in slowing down P57 100 100 %
P86 Maximum evaporator fans speed in cooling P57 100 100 %
NOTE
Check the compressor protection time, as it is zero by default.
Parameters P5 and P6 are used to establish the humidity probe range. Parameter P5 must be equal to the
humidity percentage corresponding to 4mA and parameter P6 must be equal to the humidity percentage
corresponding to 20mA.
Check the automatic and manual program humidity setpoint after changing parameter P32