Instruction Manual

EC 2-311EC 2-311
EC 2-311EC 2-311
EC 2-311
Small size digital thermometer supplied from
main voltage
Operating instructions
Version 1.00 of April the fifteenth 2002
File ec2311e_v1.00.pdf
PT
IMPORTANT:
The use of this new instrument is easy; but for safety reasons, it is
important read these instructions carefully before the installation or
before the use and follow all additional informations.
It is very important keep these instructions with the instrument for future
consultations.
ENGLISH
GENERAL INFORMAGENERAL INFORMA
GENERAL INFORMAGENERAL INFORMA
GENERAL INFORMA
TIONSTIONS
TIONSTIONS
TIONS
WHAT IS THE USE
EC 2-311 is a small size digital thermometer; the instrument can be supplied from main voltage
(230 Vac) with a very low power consumption (0.35 VA).
In factory the instrument gets preset to accept at the measure input PTC with 990 Ohm @ +25
°C, +77 °F or NTC with 10 KOhm @ +25 °C, +77 °F and B=3435 or NTC with 100 KOhm @ +25
°C, +77 °F and B=3977 probes; adjustments of the displayed value can be done through the
suitable trimmer.
EC 2-311 is available in the 62 x 28 mm (2.44 x 1.10 in.) case and it is studied for panel
mounting with elastic fins.
GETTING STGETTING ST
GETTING STGETTING ST
GETTING ST
ARAR
ARAR
AR
TEDTED
TEDTED
TED
INSTALLATION
EC 2-311 was studied for panel mounting, panel cutout 58 x 25 mm (2.28 x 0.98 in.), with
elastic fins (the overall dimensions and the panel cutout are related in Fig. 3, the fixing system
suggested by the builder is related in Fig. 4).
ADDITIONAL INFORMATIONS
- the panel thickness must be included from 1 to 3 mm (0.04 to 0.11 in.)
- verify if the using conditions (ambient temperature, humidity, etc.) are within the
limits indicated by the builder (see the chapter TECHNICAL DATA)
- install the instrument in a location with a suitable ventilation, to avoid the internal
overheating of the instrument
- do not install the instrument near surfaces that can to obstruct the air-grating (car-
pets, covers, etc.), heating sources (radiators, hot air ducts, etc.), locations sub-
ject to direct sunlight, rain, humidity, excessive dust, mechanical vibrations or
bumps, devices with strong magnetos (microwave ovens, big speakers, etc.)
- according with the safety norms, the protection against possible contacts with
electrical parts and parts protected with functional insulation only must be ensured
through a correct installation procedure of the instrument; all parts that ensure the
protection must be fixed so that they can not be removed if not with a tool.
ELECTRICAL CONNECTION
EC 2-311 is provided with two screw terminal blocks for cables up to 2.5 mm² (0.38 in.², for the
connection to the power supply and measure input), located on the instrument back panel (the
connections to derive are related in Fig. 5 and they are checkable on the polyester label stuck
on the instrument case).
ADDITIONAL INFORMATIONS
- if the instrument is brought from a cold to a warm location, the humidity may con-
dense inside the instrument; wait about an hour before supply the instrument
- verify if the operating power supply voltage, electrical frequency and power of the
instrument correspond to the local power supply (see the chapter TECHNICAL
DATA)
- do not supply more instruments with the same transformer
- if the instrument is installed on a vehicle, its power supply must be derived directly
from the battery of the vehicle
- give the instrument a protection able to limit the current absorbed in case of failure
- the instrument remains connected to the local power supply as long as the termi-
nals 1 and 2 are derived to the local power supply, even if the instrument is appar-
ently turned off
- give the probe a protection able to insulate it against possible contacts with metal
parts or use insulated probes
- do not try to repair the instrument; for the repairs apply to highly qualified staff
- if you have any questions or problems concerning the instrument please consult
Every Control (see the chapter BUILDER DATA).
USEUSE
USEUSE
USE
PRELIMINARY INFORMATIONS
After derived the connections related in Fig. 5, during the normal functioning the instrument
Fig. 1
f2-311.wmf
Fig. 2
adj2311.wmf
If an alarm should be active the instrument displays the alarm code flashing as long as the
cause that has given it does not disappear (see the chapter ALARMS).
ALARMSALARMS
ALARMSALARMS
ALARMS
ALARMS
If the instrument displays the indication “E0” flashing (probe failure alarm) it means that: the
kind of connected probe is not proper (verify the kind of connected probe), the probe is faulty
(verify the probe integrity), there is a mistake in the instrument-probe connection (verify the
instrument-probe connection integrity), the temperature read by the probe is outside the limits
permitted by the probe in use (verify that the temperature near the probe be inside the limits
permitted by the probe); inactive.
TECHNICAL DATECHNICAL DA
TECHNICAL DATECHNICAL DA
TECHNICAL DA
TT
TT
T
AA
AA
A
TECHNICAL DATA
Case: plastic black (PPO), self-extinguishing, open case.
Size: 62 x 28 x 40 mm (2.44 x 1.10 x 1.57 in.).
Installation: panel mounting, panel cutout 58 x 25 mm (2.28 x 0.98 in.),
with elastic fins.
Type of protection: IP 54.
Connections: screw terminal blocks with pitch 7.5 mm (0.29 in., power
supply) and with pitch 5 mm (0.19 in., measure input) for
cables up to 2.5 mm² (0.38 in.²).
Ambient temperature: from 0 to +60 °C (+32 to +140 °F, 10 ... 90 % of not con-
densing relative humidity).
Power supply: 230 Vac or 115 Vac, 50/60 Hz, 0.35 VA.
Insulation class: II.
Measure inputs: 1 configurable, hardware depending, for PTC with 990 Ohm
@ +25 °C, +77 °F or NTC with 10 KOhm @ +25 °C, +77 °F
and B=3435 or NTC with 100 KOhm @ +25 °C, +77 °F and
B=3977 probes.
Working range: from -50 to +150 °C (-58 to +302 °F) for PTC with 990
Ohm @ +25 °C, +77 °F probe, from -40 to +110 °C (-40 to
+230 °F) for NTC with 10 KOhm @ +25 °C, +77 °F and
B=3435 probe, from +50 to +300 °C for NTC with 100 KOhm
@ +25 °C, +77 °F and B=3977 probe.
Resolution: 1 °C (1 °F).
Display: 3-digit display 12.5 mm (0.49 in.) high red LED display
with automatic minus sign.
ADDITIONAL INFORMATIONS
- the effective probes working range principally depends from the kind of sensor and
from the material that forms the bulb and the cable.
HOW TO ORDERHOW TO ORDER
HOW TO ORDERHOW TO ORDER
HOW TO ORDER
CODING SYSTEM
Instrument name: EC 2-311.
Desired measure input: P (for PTC with 990 Ohm @ +25 °C, +77 °F probes),
N (for NTC with 10 KOhm @ +25 °C, +77 °F and B=3435
probes),
1
DIMENSIONAL DADIMENSIONAL DA
DIMENSIONAL DADIMENSIONAL DA
DIMENSIONAL DA
TT
TT
T
AA
AA
A
OVERALL DIMENSIONS AND PANEL CUTOUT
The dimensions are expressed in millimetres and inches (third-scale drawing).
Fig. 3
ds2ae.wmf
INSTINST
INSTINST
INST
ALLAALLA
ALLAALLA
ALLA
TIONTION
TIONTION
TION
WITH THE FIXING SYSTEM SUGGESTED BY THE BUILDER
Panel mounting, with elastic fins (third-scale drawing).
Fig. 4
ms2.wmf
ELECTRICAL CONNECTIONELECTRICAL CONNECTION
ELECTRICAL CONNECTIONELECTRICAL CONNECTION
ELECTRICAL CONNECTION
CONNECTIONS TO DERIVE
Instance of typical application.
BUILDER DABUILDER DA
BUILDER DABUILDER DA
BUILDER DA
TT
TT
T
AA
AA
A
EVERY CONTROL S.r.l.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Phone 0039/0437852468 (a.r.) Fax 0039/043783648
Internet addresses
e-mail: info@everycontrol.it
http://www.everycontrol.it
TO BE CAREFUL
This publication exclusively belongs to EVERY CONTROL and shall not be reproduced and distributed if not expressly authorized by the same EVERY CONTROL.
EVERY CONTROL does not assume any responsibility in order to the characteristics, to the technical data and to the possible mistakes related herein or deriving from the use of the same.
EVERY CONTROL can not be considered responsible for damages caused from the inobservance of the additional informations.
EVERY CONTROL reserves the right to make any modification without prior notice and at any time without prejudice the basic functioning and safety characteristics.
Fig. 5
c2-311e.wmf
4
displays the temperature read by the probe; adjustments of the displayed value can be done
through the suitable trimmer.

Summary of content (2 pages)