User Manual

EC 3-132EC 3-132
EC 3-132EC 3-132
EC 3-132
ON-OFF two outputs digital thermoregulator
Operating instructions
Release 2/00 of December the twelfth 2000
Code EC 3-132 DOC E002
File 3132e.p65
IMPORTANT:
The use of this new instrument is easy; but for safety reasons, it is
important read these instructions carefully before the installation or
before the use and follow all additional informations.
It is very important keep these instructions with the instrument for future
consultations.
ENGLISH
GENERAL INFORMAGENERAL INFORMA
GENERAL INFORMAGENERAL INFORMA
GENERAL INFORMA
TIONSTIONS
TIONSTIONS
TIONS
WHAT IS THE USE
EC 3-132 is an ON-OFF two outputs digital thermoregulator able to cover a temperature range
from -99 to +999 °C (-99 to +999 °F).
In factory the instrument gets preset to accept at the measure input PTC/NTC probes or “J”/”K”
thermocouples or 2/3 wires Pt 100 probes or 2 and 3 wires 0/4-20 mA temperature transduc-
ers (in this last case it is possible to set the reading scale).
This device can be set to execute one of the following kind of regulation: with an independent
working setpoint and the second relative to the first, with two independent working setpoint (in
these two cases each output can be set for “cooling” or “heating” functioning), with “neutral
zone” functioning.
EC 3-132 is available in the 74 x 32 mm (2.91 x 1.25 in.) case and it is studied for panel
mounting with the equipped screw or spring brackets.
GETTING STGETTING ST
GETTING STGETTING ST
GETTING ST
ARAR
ARAR
AR
TEDTED
TEDTED
TED
INSTALLATION
EC 3-132 was studied for panel mounting, panel cutout 71 x 29 mm (2.79 x 1.14 in.), with the
equipped screw or spring brackets (the overall dimensions and the panel cutout are related in
Fig. 3, the fixing systems suggested by the builder are related respectively in Fig. 4 and in
Fig. 5).
ADDITIONAL INFORMATIONS
- the panel thickness must be included from 1 to 5 mm (0.04 to 0.19 in.)
- verify if the using conditions (ambient temperature, humidity, etc.) are within the
limits indicated by the builder (see the chapter TECHNICAL DATA)
- install the instrument in a location with a suitable ventilation, to avoid the internal
overheating of the instrument
- do not install the instrument near surfaces that can to obstruct the air-grating (car-
pets, covers, etc.), heating sources (radiators, hot air ducts, etc.), locations sub-
ject to direct sunlight, rain, humidity, excessive dust, mechanical vibrations or
bumps, devices with strong magnetos (microwave ovens, big speakers, etc.)
- according with the safety norms, the protection against possible contacts with
electrical parts and parts protected with functional insulation only must be ensured
through a correct installation procedure of the instrument; all parts that ensure the
protection must be fixed so that they can not be removed if not with a tool
- if not differently specified at the time of order, the instrument will be equipped with
screw brackets.
ELECTRICAL CONNECTION
EC 3-132 is provided with two screw terminal blocks for cables up to 2.5 mm² (0.38 in.², for the
connection to the power supply, measure input and outputs) and it is provided with one five
poles single line male connector (for the connection to the CLONE configurer/cloner and RICS
supervision systems), located on the instrument back panel (the connections to derive are
related in Fig. 6 and they are checkable on the polyester label stuck on the instrument case).
ADDITIONAL INFORMATIONS
- if the instrument is brought from a cold to a warm location, the humidity may con-
dense inside the instrument; wait about an hour before supply the instrument
- verify if the operating power supply voltage, electrical frequency and power of the
instrument correspond to the local power supply (see the chapter TECHNICAL DATA)
- do not supply more instruments with the same transformer
- if the instrument is installed on a vehicle, its power supply must be derived directly
from the battery of the vehicle
- give the instrument a protection able to limit the current absorbed in case of failure
- the instrument remains connected to the local power supply as long as the termi-
nals 8 and 9 are derived to the local power supply, even if the instrument is appar-
ently turned off
- give the probe a protection able to insulate it against possible contacts with metal
parts or use insulated probes
- give the outputs a protection able to protect them against short circuit and overload
Fig. 1
f3-132.wmf
Fig. 2
iu3132.wmf
If an alarm should be active the instrument displays the alarm code flashing and the buzzer
utters an intermittent beep as long as the cause that has given it does not disappear (see the
chapter SIGNALS AND ALARMS); pressure on the key T1 during an alarm permits to silence
the buzzer.
EC 3-132 is provided with two working setpoint and with some configuration parameters that
get stored in a non volatile memory and that permit to set the instrument according with one’s
requirements (see the chapter CONFIGURABILITY).
During the regulations with an independent working setpoint and the second relative to the first
and with two independent working setpoint, the output K 1 is associated to the first working
setpoint, the output K 2 is associated to the second working setpoint, they remain activated
continuously as long as the temperature read by the probe reaches the working setpoint and
when it rises above (if the outputs were set for “cooling” functioning) or it falls below (if the
outputs were set for “heating” functioning) the respective working setpoint of the hysteresis
value (differential) the outputs get reactivated.
During the regulation with “neutral zone” the output K 1 remains activated continuously as long
as the temperature read by the probe reaches the working setpoint and when it rises above the
working setpoint of the “neutral zone” value the output gets reactivated; likewise the output
K 2 remains activated continuously as long as the temperature read by the probe reaches the
working setpoint and when it falls below the working setpoint of the “neutral zone” value the
output gets reactivated.
WORKING SETPOINT SETTING (WORKING TEMPERATURE)
To modify the first working setpoint value keep pushed the key T3 (the instrument displays the
actual value) and at the same time push and release over and over the key T1 or T2 as long as
the instrument displays the desired value (keeping pushed the key T1 or T2 the value gets
decreased or increased more quickly): after the modification release the key T3 last; for the
two seconds following the release of the key T3 the instrument displays the established value
and the LED L1 flashes quickly to indicate that a first working setpoint setting procedure is
running (passed the two seconds from the release of the key T3 without operated with the keys
the instrument automatically turns out from the working setpoint setting procedure).
To modify the second working setpoint value release and keep pushed the key T3 during the
flashing of the LED L1 (the instrument displays the actual value) and at the same time push
and release over and over the key T1 or T2 as long as the instrument displays the desired value
(keeping pushed the key T1 or T2 the value gets decreased or increased more quickly): after
the modification release the key T3 last; during the pressure of the key T3 the LED L2 flashes
quickly to indicate that a second working setpoint setting procedure is running (to the release
of the key T3 the instrument automatically turns out from the working setpoint setting proce-
dure).
ADDITIONAL INFORMATIONS
- for the whole period of a corrupted memory data alarm the access to the working
setpoint setting procedure is refused
- if the parameter -/0 has value 3 the second working setpoint does not exist
- the first working setpoint is programmable within the limits established with the
parameters rA1 and rA2
1
DIMENSIONAL DADIMENSIONAL DA
DIMENSIONAL DADIMENSIONAL DA
DIMENSIONAL DA
TT
TT
T
AA
AA
A
OVERALL DIMENSIONS AND PANEL CUTOUT
The dimensions are expressed in millimetres and inches (third-scale drawing).
Fig. 3
ds3ve.wmf
INSTINST
INSTINST
INST
ALLAALLA
ALLAALLA
ALLA
TIONTION
TIONTION
TION
WITH THE FIXING SYSTEMS SUGGESTED BY THE BUILDER
Panel mounting, with the equipped screw (Fig. 4) or spring brackets (Fig. 5) (third-scale drawing).
Fig. 4
ms3vv.wmf
Fig. 5
ms3vm.wmf
ELECTRICAL CONNECTIONELECTRICAL CONNECTION
ELECTRICAL CONNECTIONELECTRICAL CONNECTION
ELECTRICAL CONNECTION
CONNECTIONS TO DERIVE
Instance of typical application.
BUILDER DABUILDER DA
BUILDER DABUILDER DA
BUILDER DA
TT
TT
T
AA
AA
A
EVERY CONTROL S.r.l.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Phone 0039/0437852468 (a.r.) Fax 0039/043783648
Internet addresses
e-mail: info@everycontrol.it
http://www.everycontrol.it
TO BE CAREFUL
This publication exclusively belongs to EVERY CONTROL and shall not be reproduced and distributed if not expressly authorized by the same EVERY CONTROL.
EVERY CONTROL does not assume any responsibility in order to the characteristics, to the technical data and to the possible mistakes related herein or deriving from the use of the same.
EVERY CONTROL can not be considered responsible for damages caused from the inobservance of the additional informations.
EVERY CONTROL reserves the right to make any modification without prior notice and at any time without prejudice the basic functioning and safety characteristics.
Fig. 6
c3-132e.wmf
4
- do not try to repair the instrument; for the repairs apply to highly qualified staff
- if you have any questions or problems concerning the instrument please consult
Every Control (see the chapter BUILDER DATA).
USEUSE
USEUSE
USE
PRELIMINARY INFORMATIONS
After derived the connections related in Fig. 6, during the normal functioning the instrument
displays the temperature read by the probe.

Summary of content (4 pages)