User Manual

WORKING SETPOINT SETTING
If the parameter -/0 has value 3 the second working
setpoint does not exist.
The first/second working setpoint is programmable
within the limits established with the parameters rA1/
rb1 and rA2/rb2.
If the parameter rA5/rb5 has value 1 the first/second
working setpoint can not be modified as long as the
parameter rA5/rb5 gets set to 0.
To modify the first working setpoint value:
a) keep pushed the key
the instrument displays the actual value
the out 1 flashes quickly
b) push and release the key or as long
as the instrument displays the desired value
the first working setpoint value gets increased or de-
creased
c) after the modify release the key last
the instrument displays the set value.
To modify the second working setpoint value:
a) release and keep pushed the key during
the flashing of the LED out 1
the instrument displays the actual value
the out 2 flashes quickly
b) push and release the key or as long
as the instrument displays the desired value
the second working setpoint value gets increased or de-
creased
c) after the modify release the key last
the instrument automatically turns out from the working
setpoint setting procedure.
CONFIGURATION PARAMETERS SETTING
Configuration parameters are arranged on two levels.
To gain access to the first level:
a) keep pushed for four seconds at least the keys
and
passed four seconds the instrument displays the label
PA
To select a parameter:
a) push and release the key or as long
as the instrument displays the label of the de-
sired parameter
To modify a parameter value:
a) keep pushed the key
the instrument displays the actual value
b) push and release the key or as long
as the instrument displays the desired value
the parameter value gets increased or decreased
c) after the modify release the key last
the instrument displays the label of the parameter again
To gain access to the second level:
a) enter inside the first level and select the label
PA
b) keep pushed the key
the instrument displays the actual value
c) push and release the key or as long
as the instrument displays -19
the label value gets increased or decreased
d) after the modify release the key last
the instrument displays the label PA again
e) keep pushed for four seconds at least the keys
and
passed four seconds the instrument displays the first pa-
rameter of the second level
To turn out from the configuration parameters
setting procedure:
a) keep pushed for four seconds at least the keys
ENGLISH
EC 3-132EC 3-132
EC 3-132EC 3-132
EC 3-132
Quick reference
14
Label Min. Max. U.m. Stand. Connection in a serial network with EVCOBUS protocol
communication
L1 1 15 --- 1 instrument address
L2 0 7 --- 0 instrument group
Additional informations:
the symbol (§) indicates that the parameter is of the first level
if the parameter -/0 has value 3 the parameters of the family rB do not exist
the symbol (*) indicates that the value depends from the measure input presetting requested
if the instrument is preset to accept at the measure input “J”/”K” thermocouples the parameter /5 does not
exist
if the instrument is not preset to accept at the measure input 2 and 3 wires 0/4-20 mA temperature
transducers the parameters /6 and /7 do not exist.